background image

3 -  HARDWARE 

 

 

 

 
 

3.6  - Pressure transducers 

Three  types  of  transducers  (high  pressure,  low  pressure,  air 
differential pressure) are used to measure various pressures in 
each  circuit.  These  transducers  deliver  0  to  5  VDC.  They  are 
connected to the SIOB board. 

■ 

Discharge  pressure  transducers  (high  pressure  type) 

These transducers measure the discharge pressure in each 
circuit. They are used to control condensing pressure or high 
pressure  load  shedding.  Discharge  pressure  sensors  are 
mounted on the discharge line piping of each circuit. 

■ 

Suction pressure transducers (low pressure type) 

These  transducers  measure  the  suction  pressure  in  each 
circuit. They are used to control EXV, evaporating pressure 
(in  heating  mode)  and  monitor  suction  pressure  safeties 
related  to  the  compressor  operating  envelope.  Suction 
pressure sensors are located on the common suction piping 
of each circuit. 

■ 

Air differential pressure transducers 

These  tranducers  are  used  to  estimate  the  airflow  or  to 
control  the  building  pressure  by  measuring  the  differential 
pressure. 

 

3.7  - Temperature sensors 

Temperature  sensors  constantly  measure  the  temperature  of 
various components of the unit, ensuring the correct operation 
of the system. 

■ 

Space temperature sensors 

Up  to  two  sensors  may  be  used.  They  take  into  account 
either  an  average  space  temperature  or  minimum  and 
maximum 

space 

temperatures, 

depending 

on 

the 

configuration. 

 

Sensor T-55: This is a 10K sensor 

 

Optional sensor T-56: This 10K sensor is fitted with 
:  
- an offset slider to adjust the temperature setpoint. 
Moving  the  slider  to  the  left  (cold)  allows  the 
temperature setpoint to be reduced by as much as 
3K and moving it to the right (warm) allows it to be 
increased by up to 3K (in steps of ± 1K). When the 
slider is in its central position there is no offset. 
-  a  button  for  extending  the  occupied  period  from 
one  to  four  hours  depending  on  the  occupied 
period extension value entered in the configuration 
menu (see GENCONF menu). 

 

Optional sensor T-55: This 10K snesor is fitted with 
a button for extending the occupied period. 

 

Optional room-mate comfort controller (sensor T-59): 
This 10K sensor is fitted with : 

 

-  a  customised  liquid  crystal  display  (LLCD)  that 
indicates space temperature and setpoint offset. 

 

-  an  on/off  function  to  start  and  stop  the  unit  using 
remote contacts. 
-  temperature  offset  adjustement  which  allows  the 
temperature setpoint to be reduced by as much as 3K 
and to be increased by as much as 3K. 
-  a  button  to  extend  the  occupied  period  extension 
value  entered  in  the  configuration  menu  (see 
GENCONF menu). 

■ 

Supply air temperature sensor 

The control system uses this to maintain a constant space 
temperature. This is a Carrier 10K sensor. 

■ 

Return air temperature sensor 

The control system uses this to calculate the fresh air rate 
when  using  economizer  with  VAV  option.  This  is  a  Carrier 
10K sensor. 
 
 
 
 

 

 
 

■ 

Outdoor air temperature sensor 

This Carrier 5K system controls the economizer, allows the 
gas heating stages to be used on the heat pumps and offsets 
he space temperature setpoint where this is appropriate. 

■ 

Water coil frost protection sensor 

This Carrier 5K sensor is used on units fitted with hot-water 
systems. 

■ 

Defrost termination sensor 

This sensor measures the common water temperature in the 
master/slave system capacity control. It is installed only in the 
case of master/slave units. 

■ 

Defrost temperature sensors (heat pumps) 

This Carrier 5K sensor is used by the defrost function on heat 
pump units. 

■ 

Air quality sensor 

This sensor controls room air quality. It is an optional sensor 
of the 0-10V d.c type. 
 
 
 

3.8 

– The controls 

■ 

Electronic expansion valve (EXV) 

The electronic expansion valve (EXV) is used to adjust the 
refrigerant flow to changes in the operating conditions of the 
machine. The high degree of accuracy with which the piston 
is positioned provides precise control of the refrigerant flow 
and suction superheat. 

■ 

Indoor supply fan 

The controller can start or stop the indoor fan thanks to the 
time schedule. With VAV option, the indoor supply fan speed 
is adjusted to fit the ventilation needs. 
Two types of fan are compatible  with the unit, sandard fan 
or  high  static  fan.  They  can  be  chhosen  upon  the  field 
environment. 

■ 

Return fan 

In some applications with high return duct ESP, a return fan 
may be applied to help supply fan to maintain the airflow and 
the buiding pressure. 

■ 

Heaters 

The controller can control additional heaters for cooling only 
or  heat  pump  unit.  The  additional  heater  can  be  electrical; 
hot water coil or gas heater. 

■ 

Pre-heaters 

With the option, the unit can control 2 electrical pre-heaters, 
if unit size < 125 and 3 if unit size >= 125. 

■ 

Energy recovery module (ERM) 

SmartVu can control an optional energy recovery module for 
optimised energy management of the exhaust air. 

■ 

High ambient fresh air option 

With  this  option,  the  unit  can  control  supply  airflow%  or 
Fresh Air% according to OAT or SST values. It is working in 
cooling mode, with economizer and without ERM.

Summary of Contents for SmartVu control

Page 1: ...CONTROLS MANUAL SmartVu Control 50 48 UC V UP V 025 220 Original document...

Page 2: ...9 Alarms menu 34 6 STANDARD CONTROL OPERATIONS AND OPTIONS 36 6 1 External thermostat control 36 6 2 Cooling only unit 37 6 3 Single circuit heat pump unit 37 6 4 Dual circuit dual compressor heat pu...

Page 3: ...aying current alarms 49 8 3 E mail notifications 49 8 4 Resetting alarms 49 8 5 Alarm history 49 8 6 Alarm codes 50 9 MAINTENANCE 57 The cover photos are solely for illustration and forms no part of a...

Page 4: ...The information provided herein is solely for the purpose of allowing customers to operate and service Carrier manufactured equipment and it is not to be reproduced modified or used for any other purp...

Page 5: ...ools to move heavy objects Move units carefully and set them down gently CAUTION Only qualified service technicians should be allowed to install and service the equipment 1 2 Safety precautions Only p...

Page 6: ...users tocontrol the unit viathe SmartVuuser interface Provides web connectivity technology Includes the trending functionality Supports Carrier Connect Services Remote connectivity alarm notification...

Page 7: ...7 Fire damper output Defrost mechanism reversible HP Refrigerant leak detection Diagnostics...

Page 8: ...ction 5 6 One Ethernet ports allow for TCP IP communication connection Connections on the bottom side of the controller 3 4 Power supply to boards All boards are supplied from a common 24 VAC supply r...

Page 9: ...lpy contact SIOB2 circuit B DI 04 J1 Supply fan status contact SIOB1 circuit A DI 07 J1 Indoor air flow verification input Fire contact SIOB1 circuit A DI 05 Fire safety input Alarm relay output SIOB1...

Page 10: ...gle circuit unit Y1 compressor 1 on off Y2 compressor 2 on off W additional heating stage 1 on off W2 additional heating stage 2 on off O cycle reversing valve on off heat pump units TSTAT Types TSTAT...

Page 11: ...to be reduced by as much as 3K and to be increased by as much as 3K a button to extend the occupied period extension value entered in the configuration menu see GENCONF menu Supply air temperature sen...

Page 12: ...eft is return fan and the values below are return airflow and RAT Outdoor Air Temperature OAT This parameter is displayed only in case of units fitted with OAT sensor Current freshair supply fan RTU I...

Page 13: ...rol mode Unit is currently stopped blue icon Unit is currently running green icon Alarm menu Press the button to go to the Alarms menu The grey bell means there is currently no alarm active on the uni...

Page 14: ...left 4 8 Screen calibration Thepurposeofscreencalibrationistomakesurethatthesoftware acts correctly upon pressing icons on the user interface To calibrate the screen 1 Press and hold anywhere on the s...

Page 15: ...Configuration menu See section 5 2 Home Previous screen Main Menu System Menu User Login Start Stop Alarms Menu General Parameters Parameters Temperatures Pressures Inputs Outputs Run Times Modes Qui...

Page 16: ...yp 0 to 3 0 Local 0 CCN 1 Remote 2 0 3 blank TSTAT 3 STATUS CHARS8 0 Run Status ALM CHARS8 0 Alarm state min_left 0 to 0 0 min Minutes Left for Start 0 0 HEATCOOL CHARS8 0 Heat Cool status HC_SEL 0 to...

Page 17: ...aving Water Temp 0 0 SCT_A 0 to 0 0 F Saturated Condensing T A 0 0 SST_A 0 to 0 0 F Saturated Suction Temp A 0 0 SUCT_A 0 to 0 0 F EXV Suction Temp A 0 0 DEFRT_A 0 to 0 0 F Defrost Temperature A 0 0 S...

Page 18: ...tch 0 1 SP_SW1 OPEN_CLOSE 0 Remote Setpoint Switch 1 0 1 SP_SW2 OPEN_CLOSE 0 Remote Setpoint Switch 2 0 1 lim_sw1 OPEN_CLOSE 0 Limit Switch 0 1 HS_FBK OPEN_CLOSE 0 Heat Stages status 0 1 PRE_HS OPEN_C...

Page 19: ...E hpsw_b OPEN_CLOSE 0 High Pressure Switch B 0 1 hpsw_c OPEN_CLOSE 0 High Pressure Switch THR 0 1 exvA_fbk 0 to 0 0 EXV Position Circuit A 0 0 exvB_fbk 0 to 0 0 EXV Position Circuit B 0 0 exvC_fbk 0 t...

Page 20: ...Output 0 1 cp_c2 OFF_ON 0 THR Compressor 2 Output 0 1 rv_c OFF_ON 0 4Way Refrig Valve THR 0 1 ecopos 0 to 0 0 Economizer Position 0 0 gas_on OFF_ON 0 Modulated Gas Enable 0 1 gas_v 0 to 0 0 Modulated...

Page 21: ...0 0 EXV Position Circuit THR 0 0 hs_1 OFF_ON 0 Heater Stage 1 0 1 hs_2 OFF_ON 0 Heater Stage 2 0 1 hs_3 OFF_ON 0 Heater Stage 3 0 1 hs_4 OFF_ON 0 Heater Stage 4 0 1 pre_hs_1 OFF_ON 0 Pre heater Stage...

Page 22: ...s Compressor A2 Hours 0 0 st_cp_a2 0 to 0 0 Compressor A2 Starts 0 0 hr_cp_b1 0 to 0 0 hours Compressor B1 Hours 0 0 st_cp_b1 0 to 0 0 Compressor B1 Starts 0 0 hr_cp_b2 0 to 0 0 hours Compressor B2 Ho...

Page 23: ...1 m_dehumi NO_YES 0 Dehumidification Mode 0 1 m_iaq NO_YES 0 IAQ Mode 0 1 m_gas NO_YES 0 OAT Gas Threshold 0 1 m_fire NO_YES 0 Fire Shutdown Active 0 1 m_enth NO_YES 0 Enthalpy Lockout 0 1 m_start NO...

Page 24: ...T High Limit 60 110 purg_du 1 to 5 2 min Purge Duration 1 5 iaq_sp 50 to 10000 700 IAQ Setpoint 50 10000 Trendings TRENDING Name Status Unit Displayed text Description GENUNIT_cap_t 0 to 100 Perecent...

Page 25: ...n menu Date Time Configuration Home Previous screen Main Menu User Login Start Stop Alarms Menu Genunit Config User Configuration Hea Cool Config Schedule Menu Holiday Menu Reset Config Configuration...

Page 26: ...NO_YES 0 Thermostat Control 0 1 frst_sel NO_YES 0 Frost Protection Select 0 1 spt_ctrl 0 to 4 0 SPT Calculation Select 0 4 blank 0 Average Temp Meth blank 1 High Temp Sensor blank 2 Low Temp Sensor bl...

Page 27: ...ARTVU CONTROL MENU STRUCTURE synoptic NO_YES 0 Synoptic Is Displayed 0 1 User Configuration USERCONF Point Name Status Default Unit Description Low Limit High Limit use_pass 1 to 9999 11 User Password...

Page 28: ...mer months and back again in the fall in order to make better use of natural daylight Greenwich Mean Time UTC Location Time zone YYYY MM DD HH MM SS Date Time Current date and time must be set manuall...

Page 29: ...ule setting please see section 6 24 5 4 Holiday menu The Holiday menu allows the user to set up to 16 holiday periods which are defined by the start month start day and duration Holiday Menu HOLIDAY I...

Page 30: ...ion RAM usage 0 to 100 FLASH Memory utilization Flash memory usage Depends on the selected language English by default EOL Resistor Menu EOLRES Status Default Displayed text Description disable enable...

Page 31: ...me zone YYYY MM DD HH MM SS Date Time Current date and time must be set manually no yes Today is a Holiday Information about holidays read only Please note that holidays are set in the Holiday menu se...

Page 32: ...NN N SDK Version SDK version number NN UI Version User interface version CARRIER Brand Brand name Depends on the selected language English by default Hardware Info Menu HWINFO Status Displayed text De...

Page 33: ...ess the User Login button and then select User Login 2 Press the Password box 3 Provide the password 11 and press the Confirm button 4 The User Login screen appears 5 6 3 User password User password c...

Page 34: ...layed 5 7 3 Unit stop To stop the unit 1 Press the Start Stop button 2 ConfirmtheunitshutdownbypressingConfirmStoporcancel the unit shutdown by pressing the Backbutton Unit start stop screen operating...

Page 35: ......

Page 36: ...ocess failure compressor failure and VFD drives IMPORTANT For more information about alarms please go to section 8 6 Current Alarms Menu CUR_ALM No Name Date Hour Alarm text 1 Alarm YYYY MM DD HH MM A...

Page 37: ...urrent Alarm 1 Alarm code see section 8 6 4 alarm_2c Current Alarm 2 Alarm code see section 8 6 5 alarm_3c Current Alarm 3 Alarm code see section 8 6 6 alarm_4c Current Alarm 4 Alarm code see section...

Page 38: ...ed 6 3 Single circuit heat pump unit Contact G open The internal fan is stopped and the economizer is closed Contact G closed The internal fan is activated and the economizer is opened to its minimum...

Page 39: ...le 1 Remote start stop contact status Onoff_sw Start stop contact status can be used to control the unit state in the Remote operating type G This contact is used when unit is in thermostat operating...

Page 40: ...In this case the function is generally used to limit the difference between the indoor and outdoor temperatures in order to prevent thermal shock IMPORTANT It is not possible to use both types of off...

Page 41: ...be vspd_max 10 Volts 6 16 Head pressure control Condensing pressure control is automatically ensured by a two speed fan no adjustment 6 17 Defrost function Defrost is activated when the unit is in hea...

Page 42: ...horised If the unit is fitted with a power exhaust fan this shall be open if the position of the economizer is in excess of 50 this threshold may be modified by Carrier Service 6 22 Purge This functio...

Page 43: ...is in same status with the supply fan and the return fan s speed is command However any faults active when the supply is interrupted are saved and may in certain cases prevent a circuit or a unit from...

Page 44: ...Press the Save button to save your changes or the Cancel button to exit the screen without making modifications Legend 1 Selection of days for the time schedule 2 Start end of the schedule 3 Previous...

Page 45: ...on to display the graph showing trends for the set of selected parameters Set the time range start end dates and time and press the Arrowbutton todisplaythegraphshowingtheperformance of the unit withi...

Page 46: ...y the unit IP address Example https 169 254 1 1 3 Press Enter 4 The web interface will be loaded IMPORTANT Three users can be connected simultaneously with no priority between them The last modificati...

Page 47: ...sting alarms have been reset To define e mail recipients 1 Press theMain menu buttonandnavigatetotheConfiguration menu 2 Go to the Network menu 2 Select Email Configuration EMAILCFG 3 Define user e ma...

Page 48: ...r installation fault Circuit is shut down 15 Pr 02 Circuit B Discharge Transducer As above As above As above 16 Pr 03 Circuit THR Discharge Transducer As above As above As above 17 Pr 04 Circuit A Suc...

Page 49: ...d low suction temp overrides Manual Pressure sensor defective or refrigerant charge too low Circuit is shut down 41 P 41 Circuit B Repeated low suction temp overrides Manual As above As above 42 P 42...

Page 50: ...Superheat B Manual Circuit B shuts down 66 P 10 High Suction Superheat THR As above As above Circuit THR shuts down 67 P 11 Low Suction Superheat A Manual Circuit A shuts down 68 P 12 Low Suction Sup...

Page 51: ...ensure your Carrier equipment is regularly inspected by Carrier Service specialists so that any malfunction is detected and corrected quickly and no serious damage can occur to your equipment The Car...

Page 52: ...o 10508 04 2019 Supersedes order No 10508 04 2019 Manufactured by Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the Europea...

Reviews: