background image

39 

 

 

6.13 - Controlling space temperature 

 

 

The controller uses two loops in tandem to control space 
temperature. The purpose of the first loop (called the external  
loop) is to calculate the blower temperature required to 
maintain space temperature at space setpoint. This blower 
temperature, which is called the blower setpoint or forced 
air setpoint, is transmitted to a second loop (called the 
internal loop). This second loop determines the cooling or 
heating capacity needed to maintain blower temperature  
 
at the setpoint transmitted to it by the external loop. This 
enables it to actuate the compressors and if necessary the 
additional heating stages or a valve on the hot water system.  
The precision of the controller depends on the load and the  
number of stages available on the unit. 
On high inertia systems such as these, tandem control has 
the advantage of allowing space temperature to be finely 
controlled whilst guaranteeing a good response to disturbing  
elements associated with non-linear systems. 

NOTE: In some cases Carrier Service may adjust the loop 
gains to suit the installed configurations. 

6.14 

– Capacity limitation 

 

 

Capacity limitation is generally used by an energy management  
system to restrict the amount of electricity consumed by the 
unit. The SmartVu control system enables the capacity 
of the unit to be limited by means of a user-controlled voltfree 
contact (active when closed). 

The action of this contact depends on the type of unit and 

the configuration (see GENCONF configuration):  

 

Heat Pump unit with gas heater: All compressors are 
stopped and only gas is used. 

 

Heat Pump unit with hot water system: The compressor 
heater authorised to operate are limited to the value 
configured and the hot water system is used. 

 

Electric stages: The electric stages authorised to operate 
are limited to the value configured. 

 

Compressor stages: The compressor stages authorized to 
operate are limited to the value configured. 

 

Unit in defrosting mode: The electric stages are authorised 
to operate if authorised by the configuration. 

 

6.15 

– Capacity control 

 

In heating or cooling mode the capacity control regulates 
the compressor start-up and shut-down sequence. The 
control determines the compressor start-up in a way that 
equalises the start-up number for each compressor (value 
weighted by the operating time). This means, the compressor 
with the least number of start-ups is always the first to start 
up and the first to shut down. 
For VSPD unit with dual circuits, when capacity need to be 
loaded, one fixed speed compressor shall be firstly turned  
ON. Then VSPD compressor shall be added to control 
more precisely the capacity. Its capacity can vary between  
25% with step of 5%. If capacity is not enough, then another 
fixed speed compressor shall start. 
Moreover, the VSPD speed will be equal to the circuit A 
capacity. It means maximum SIOB output will be vspd_max/10 
Volts. 
 
 
 
 

6.16 

– Head pressure control

 

 

Condensing pressure control is automatically ensured by a 
two-speed fan (no adjustment). 
 

6.17 

– Defrost function 

 

Defrost is activated, when the unit is in heating mode, in 
order to reduce frost build-up on the air heat exchanger. 
The defrost cycle can only be applied to one circuit at a 
time. During the defrost cycle the fans of that circuit are 
stopped, and the four-way refrigerant valve is reversed, 
forcing the circuit to cooling mode. The fan can 
temporarily be restarted during the defrost cycle. The  
defrost cycle is fully automatic and does not require any  
setting. A condensate heater prevents ice formation at the 
 

 
 

bottom of the heat exchangers, if the defrost cycles are 
taking place at low outdoor temperature. 
 

NOTE: The indoor fans run during the defrost cycle except 
in single-circuit units without additional heat option 
(electric heat stage or hot-water coil). 
 

6.18 

– Additional heater 

 

 

Additional heater can be used on both cooling  only and 
heat pump unit. There are three types of additional  
heaters: electrical heater, hot water coil and gas heater. On 
heat pump unit, electrical and hot water coil can only be 
used as backup heater, but modulated type gas heater can  
be used both as primary or backup heater. 

 
 
 

6.19 

– Electrical heater 

 

Electrical heater is staged type. Up to 4 staged electrical 
heaters can be controlled independently by the unit. 
On cooling only unit, electrical heaters may be switched on 
when unit need to do heating. On heat pump unit, electrical 
heaters may only be switched on when the unit is at 100% 
of its available compressor capacity and when outside 
temperature is below OAT threshold (default value is 5 °C 
with 1°C hysteresis to be switched off). When a circuit is in 
defrost mode, electric heaters are authorized to start up 
regardless of the compressor capacity. 

6.19.1 

– Gas heater 

 

Gas heater is modulated type. On cooling only unit, the 
modulated type gas heaters will be switched on when unit  
need to do heating. 
On heatpump unit, modulated type gas heater can be used 
as primary heater(default) or backup heater. If used as 
primary heater, gas will be the first heating source to 
satisfy the load. The compressors can be added after the 
gas capacity is 100%. In reverse, compressor will be the 
first to satisfy the load and modulated type gas heater may 
only be switched on when the unit is at 100% of available  
compressor capacity and when outside temperature is  
below OAT threshold (default value is 1.6 °C with 1.6°C 
hysteresis to be switched off).  
For only 190-220 heat pump sizes, gas heater cannot be 
used at the same time with the compressors. It will be used   
when the outside temperature is below OAT threshold   
(default value is 1.6 °C with 1.6°C hysteresis to be switched  
off). Above that temperature, the compressors are used  
again and the gas heater is halte 

6.19.2 

– Hot water coil 

 
 

Hot water coil is modulated type. Units may control the 
heating capacity by adjusting a valve on a hot water 
system. It is always used as backup heater. 
When the unit is operating in heating mode and 

Summary of Contents for SmartVu control

Page 1: ...CONTROLS MANUAL SmartVu Control 50 48 UC V UP V 025 220 Original document...

Page 2: ...9 Alarms menu 34 6 STANDARD CONTROL OPERATIONS AND OPTIONS 36 6 1 External thermostat control 36 6 2 Cooling only unit 37 6 3 Single circuit heat pump unit 37 6 4 Dual circuit dual compressor heat pu...

Page 3: ...aying current alarms 49 8 3 E mail notifications 49 8 4 Resetting alarms 49 8 5 Alarm history 49 8 6 Alarm codes 50 9 MAINTENANCE 57 The cover photos are solely for illustration and forms no part of a...

Page 4: ...The information provided herein is solely for the purpose of allowing customers to operate and service Carrier manufactured equipment and it is not to be reproduced modified or used for any other purp...

Page 5: ...ools to move heavy objects Move units carefully and set them down gently CAUTION Only qualified service technicians should be allowed to install and service the equipment 1 2 Safety precautions Only p...

Page 6: ...users tocontrol the unit viathe SmartVuuser interface Provides web connectivity technology Includes the trending functionality Supports Carrier Connect Services Remote connectivity alarm notification...

Page 7: ...7 Fire damper output Defrost mechanism reversible HP Refrigerant leak detection Diagnostics...

Page 8: ...ction 5 6 One Ethernet ports allow for TCP IP communication connection Connections on the bottom side of the controller 3 4 Power supply to boards All boards are supplied from a common 24 VAC supply r...

Page 9: ...lpy contact SIOB2 circuit B DI 04 J1 Supply fan status contact SIOB1 circuit A DI 07 J1 Indoor air flow verification input Fire contact SIOB1 circuit A DI 05 Fire safety input Alarm relay output SIOB1...

Page 10: ...gle circuit unit Y1 compressor 1 on off Y2 compressor 2 on off W additional heating stage 1 on off W2 additional heating stage 2 on off O cycle reversing valve on off heat pump units TSTAT Types TSTAT...

Page 11: ...to be reduced by as much as 3K and to be increased by as much as 3K a button to extend the occupied period extension value entered in the configuration menu see GENCONF menu Supply air temperature sen...

Page 12: ...eft is return fan and the values below are return airflow and RAT Outdoor Air Temperature OAT This parameter is displayed only in case of units fitted with OAT sensor Current freshair supply fan RTU I...

Page 13: ...rol mode Unit is currently stopped blue icon Unit is currently running green icon Alarm menu Press the button to go to the Alarms menu The grey bell means there is currently no alarm active on the uni...

Page 14: ...left 4 8 Screen calibration Thepurposeofscreencalibrationistomakesurethatthesoftware acts correctly upon pressing icons on the user interface To calibrate the screen 1 Press and hold anywhere on the s...

Page 15: ...Configuration menu See section 5 2 Home Previous screen Main Menu System Menu User Login Start Stop Alarms Menu General Parameters Parameters Temperatures Pressures Inputs Outputs Run Times Modes Qui...

Page 16: ...yp 0 to 3 0 Local 0 CCN 1 Remote 2 0 3 blank TSTAT 3 STATUS CHARS8 0 Run Status ALM CHARS8 0 Alarm state min_left 0 to 0 0 min Minutes Left for Start 0 0 HEATCOOL CHARS8 0 Heat Cool status HC_SEL 0 to...

Page 17: ...aving Water Temp 0 0 SCT_A 0 to 0 0 F Saturated Condensing T A 0 0 SST_A 0 to 0 0 F Saturated Suction Temp A 0 0 SUCT_A 0 to 0 0 F EXV Suction Temp A 0 0 DEFRT_A 0 to 0 0 F Defrost Temperature A 0 0 S...

Page 18: ...tch 0 1 SP_SW1 OPEN_CLOSE 0 Remote Setpoint Switch 1 0 1 SP_SW2 OPEN_CLOSE 0 Remote Setpoint Switch 2 0 1 lim_sw1 OPEN_CLOSE 0 Limit Switch 0 1 HS_FBK OPEN_CLOSE 0 Heat Stages status 0 1 PRE_HS OPEN_C...

Page 19: ...E hpsw_b OPEN_CLOSE 0 High Pressure Switch B 0 1 hpsw_c OPEN_CLOSE 0 High Pressure Switch THR 0 1 exvA_fbk 0 to 0 0 EXV Position Circuit A 0 0 exvB_fbk 0 to 0 0 EXV Position Circuit B 0 0 exvC_fbk 0 t...

Page 20: ...Output 0 1 cp_c2 OFF_ON 0 THR Compressor 2 Output 0 1 rv_c OFF_ON 0 4Way Refrig Valve THR 0 1 ecopos 0 to 0 0 Economizer Position 0 0 gas_on OFF_ON 0 Modulated Gas Enable 0 1 gas_v 0 to 0 0 Modulated...

Page 21: ...0 0 EXV Position Circuit THR 0 0 hs_1 OFF_ON 0 Heater Stage 1 0 1 hs_2 OFF_ON 0 Heater Stage 2 0 1 hs_3 OFF_ON 0 Heater Stage 3 0 1 hs_4 OFF_ON 0 Heater Stage 4 0 1 pre_hs_1 OFF_ON 0 Pre heater Stage...

Page 22: ...s Compressor A2 Hours 0 0 st_cp_a2 0 to 0 0 Compressor A2 Starts 0 0 hr_cp_b1 0 to 0 0 hours Compressor B1 Hours 0 0 st_cp_b1 0 to 0 0 Compressor B1 Starts 0 0 hr_cp_b2 0 to 0 0 hours Compressor B2 Ho...

Page 23: ...1 m_dehumi NO_YES 0 Dehumidification Mode 0 1 m_iaq NO_YES 0 IAQ Mode 0 1 m_gas NO_YES 0 OAT Gas Threshold 0 1 m_fire NO_YES 0 Fire Shutdown Active 0 1 m_enth NO_YES 0 Enthalpy Lockout 0 1 m_start NO...

Page 24: ...T High Limit 60 110 purg_du 1 to 5 2 min Purge Duration 1 5 iaq_sp 50 to 10000 700 IAQ Setpoint 50 10000 Trendings TRENDING Name Status Unit Displayed text Description GENUNIT_cap_t 0 to 100 Perecent...

Page 25: ...n menu Date Time Configuration Home Previous screen Main Menu User Login Start Stop Alarms Menu Genunit Config User Configuration Hea Cool Config Schedule Menu Holiday Menu Reset Config Configuration...

Page 26: ...NO_YES 0 Thermostat Control 0 1 frst_sel NO_YES 0 Frost Protection Select 0 1 spt_ctrl 0 to 4 0 SPT Calculation Select 0 4 blank 0 Average Temp Meth blank 1 High Temp Sensor blank 2 Low Temp Sensor bl...

Page 27: ...ARTVU CONTROL MENU STRUCTURE synoptic NO_YES 0 Synoptic Is Displayed 0 1 User Configuration USERCONF Point Name Status Default Unit Description Low Limit High Limit use_pass 1 to 9999 11 User Password...

Page 28: ...mer months and back again in the fall in order to make better use of natural daylight Greenwich Mean Time UTC Location Time zone YYYY MM DD HH MM SS Date Time Current date and time must be set manuall...

Page 29: ...ule setting please see section 6 24 5 4 Holiday menu The Holiday menu allows the user to set up to 16 holiday periods which are defined by the start month start day and duration Holiday Menu HOLIDAY I...

Page 30: ...ion RAM usage 0 to 100 FLASH Memory utilization Flash memory usage Depends on the selected language English by default EOL Resistor Menu EOLRES Status Default Displayed text Description disable enable...

Page 31: ...me zone YYYY MM DD HH MM SS Date Time Current date and time must be set manually no yes Today is a Holiday Information about holidays read only Please note that holidays are set in the Holiday menu se...

Page 32: ...NN N SDK Version SDK version number NN UI Version User interface version CARRIER Brand Brand name Depends on the selected language English by default Hardware Info Menu HWINFO Status Displayed text De...

Page 33: ...ess the User Login button and then select User Login 2 Press the Password box 3 Provide the password 11 and press the Confirm button 4 The User Login screen appears 5 6 3 User password User password c...

Page 34: ...layed 5 7 3 Unit stop To stop the unit 1 Press the Start Stop button 2 ConfirmtheunitshutdownbypressingConfirmStoporcancel the unit shutdown by pressing the Backbutton Unit start stop screen operating...

Page 35: ......

Page 36: ...ocess failure compressor failure and VFD drives IMPORTANT For more information about alarms please go to section 8 6 Current Alarms Menu CUR_ALM No Name Date Hour Alarm text 1 Alarm YYYY MM DD HH MM A...

Page 37: ...urrent Alarm 1 Alarm code see section 8 6 4 alarm_2c Current Alarm 2 Alarm code see section 8 6 5 alarm_3c Current Alarm 3 Alarm code see section 8 6 6 alarm_4c Current Alarm 4 Alarm code see section...

Page 38: ...ed 6 3 Single circuit heat pump unit Contact G open The internal fan is stopped and the economizer is closed Contact G closed The internal fan is activated and the economizer is opened to its minimum...

Page 39: ...le 1 Remote start stop contact status Onoff_sw Start stop contact status can be used to control the unit state in the Remote operating type G This contact is used when unit is in thermostat operating...

Page 40: ...In this case the function is generally used to limit the difference between the indoor and outdoor temperatures in order to prevent thermal shock IMPORTANT It is not possible to use both types of off...

Page 41: ...be vspd_max 10 Volts 6 16 Head pressure control Condensing pressure control is automatically ensured by a two speed fan no adjustment 6 17 Defrost function Defrost is activated when the unit is in hea...

Page 42: ...horised If the unit is fitted with a power exhaust fan this shall be open if the position of the economizer is in excess of 50 this threshold may be modified by Carrier Service 6 22 Purge This functio...

Page 43: ...is in same status with the supply fan and the return fan s speed is command However any faults active when the supply is interrupted are saved and may in certain cases prevent a circuit or a unit from...

Page 44: ...Press the Save button to save your changes or the Cancel button to exit the screen without making modifications Legend 1 Selection of days for the time schedule 2 Start end of the schedule 3 Previous...

Page 45: ...on to display the graph showing trends for the set of selected parameters Set the time range start end dates and time and press the Arrowbutton todisplaythegraphshowingtheperformance of the unit withi...

Page 46: ...y the unit IP address Example https 169 254 1 1 3 Press Enter 4 The web interface will be loaded IMPORTANT Three users can be connected simultaneously with no priority between them The last modificati...

Page 47: ...sting alarms have been reset To define e mail recipients 1 Press theMain menu buttonandnavigatetotheConfiguration menu 2 Go to the Network menu 2 Select Email Configuration EMAILCFG 3 Define user e ma...

Page 48: ...r installation fault Circuit is shut down 15 Pr 02 Circuit B Discharge Transducer As above As above As above 16 Pr 03 Circuit THR Discharge Transducer As above As above As above 17 Pr 04 Circuit A Suc...

Page 49: ...d low suction temp overrides Manual Pressure sensor defective or refrigerant charge too low Circuit is shut down 41 P 41 Circuit B Repeated low suction temp overrides Manual As above As above 42 P 42...

Page 50: ...Superheat B Manual Circuit B shuts down 66 P 10 High Suction Superheat THR As above As above Circuit THR shuts down 67 P 11 Low Suction Superheat A Manual Circuit A shuts down 68 P 12 Low Suction Sup...

Page 51: ...ensure your Carrier equipment is regularly inspected by Carrier Service specialists so that any malfunction is detected and corrected quickly and no serious damage can occur to your equipment The Car...

Page 52: ...o 10508 04 2019 Supersedes order No 10508 04 2019 Manufactured by Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the Europea...

Reviews: