background image

41 

 

 

the ERM wheel is off 

 
2. 

Recovery mode in heating: Economizer is opened at the 
minimum position and the space temperature is higher than 
the outside temperature. The ERM wheel is on. 
 

3. 

Recovery mode in cooling: The economizer opened at  the 
minimum position and the space temperature is lower than 
the outside temperature. The ERM wheelis on. 

 
4. 

The unit is in free-cooling mode, the economizer is opened, 
the space temperature is higher than the outside 
temperature. The ERM wheel is off. 

 

 

6.27 

– Thermodynamic energy recovery (THR) 

 

The ERM energy recovery wheel is replaced by a refrigeration 
circuit in the THR. 
 
THR is considered as additional refrigeration circuit with 
equal role as regular refrigeration citcuit(s). THR’s ON/OFF 
is requested by capacity control logic and compressor  load/ 
unload sequence. It is possible to be used as lead or lag  
refrigeration source depend on user configured minimum  
fresh air. 
 
THR is always used with return fan option. When THR is 
ON, supply air flow rate shall be minimum 80% nominal air  
flow rate, economizer damper shall modulate to guatantee 
safe function of THR. 
 

6.28 

– Demand limit 

 

The demand limit is used to restrict the unit power consumption. 
The SmartVu control system allows 
limitation of the unit capacity, using user-controlled 
volt-free contacts. 
 
The unit capacity can never exceed the limit setpoint 
activated by these contacts. The limit setpoints can be 
modified in the GENCONF menu. 

 

6.29 - VAV option 

 

When this option is equipped, the indoor fan airflow can be 
managed in three ways: 

 

Constant air volume: Allows to provide a constant airflow in 
the product lifetime 

 

Variable air volume 1: Variable airflow in cooling only mode 
to fit the ventilation needs as a function of circuit 

 

Variable air volume 2: Variable airflow for both cooling and 
heating modes. 

 
The three modes use PID logic to maintain the required airflow. 
When coupled to the economizer option, the fresh air rate is 
maintained automatically. 
The system has to be calibrated by Carrier Service 

 

6.30 

– Return fan option 

 

In some applications with high return duct ESP, a return fan 
may be applied to help maintain the air flow rate and the 
building pressure. Return fan’s ON/OFF is in same status with 
the supply fan and the return fan’s speed is command. 
However, any faults active when the supply is interrupted are 
saved and may in certain cases prevent a circuit or a unit from 
restarting. 

 
A manual reset must be run from the touch screen interface or the 
web via the Reset alarms menu, item RST_ALM. Alarm reset can 
be protected by a basic user level password. 
 
 

6.31 

– Night mode 

 

Night mode allows users to configure the unit to operate with 
specific parameters in a specific time period. During the night 
period,  the  fan  runs  atlow  speed,  if  permitted  by  the  current 
operating conditions.In addition, the user can reduce the unit 
capacity.  

The night period is defined by a start time and an end time that 
are  the  same  for  each  day  of  the  week.  The  Night  mode 
settings  can  be  configured  via  the  Configuration  menu 
(GEN_CONF 

– General Configuration). Only logged-in users 

can modify the night mode settings. 

 

To set the night mode 

1. Navigate to the Configuration menu (logged-in users only). 
2. Select 

General Configuration 

(GEN_CONF). 

3. Set parameters corresponding to the night mode. 

Night Mode Start Hour [nh_start] 

00:00 to 24:00 

Night Mode End Hour [nh_end] 

00:00 to 24:00 

 

 
 
 

6.32  Refrigerant leak  detection option  

 

When the normally closed refrigerant leak detection contact is 
open, 
the unit is shut down. 

 

6.33  BACnet  

 

The BACnet/IP communication protocol is used by BMS or the 
programmable controllers to communicate with the control. 
This protocol is available as a 

standard

 

To enable/disable BACnet communication option 

1. 

Go to the Main menu. 

2. 

Navigate to the Configuration menu, and then the 
Network menu. 

3. 

Select the BACnet Parameters menu (BACNET). 

4. 

Set the "BACnet Enable" parameter to "enable". 

 

6.34  Modbus 

The modbus protocol is used for communication with  the 
building management( BMS )or the programmable controllers 
,which is acting as the master, while the multiple units are 
watched as slaves. This protocol is available as a 

standard

 

To enable/disable MODBUS communication option 

1. 

Go to the Main menu. 

2. 

Navigate to the Configuration menu, and then the 
Network menu. 

3. 

Select the MODBUSParameters menu (MODBUS). 

4. 

Set the "MODBUS Enable" parameter to "enable". 

 

6.35- Schedule setting 

The control incorporates two time schedules, where the first one 

(OCCPC01S) is used for controlling the unit start/stop, whereas 
the  second  one  (OCCPC02S)  is  used  for  controlling  the  dual 
setpoint. 

Summary of Contents for SmartVu control

Page 1: ...CONTROLS MANUAL SmartVu Control 50 48 UC V UP V 025 220 Original document...

Page 2: ...9 Alarms menu 34 6 STANDARD CONTROL OPERATIONS AND OPTIONS 36 6 1 External thermostat control 36 6 2 Cooling only unit 37 6 3 Single circuit heat pump unit 37 6 4 Dual circuit dual compressor heat pu...

Page 3: ...aying current alarms 49 8 3 E mail notifications 49 8 4 Resetting alarms 49 8 5 Alarm history 49 8 6 Alarm codes 50 9 MAINTENANCE 57 The cover photos are solely for illustration and forms no part of a...

Page 4: ...The information provided herein is solely for the purpose of allowing customers to operate and service Carrier manufactured equipment and it is not to be reproduced modified or used for any other purp...

Page 5: ...ools to move heavy objects Move units carefully and set them down gently CAUTION Only qualified service technicians should be allowed to install and service the equipment 1 2 Safety precautions Only p...

Page 6: ...users tocontrol the unit viathe SmartVuuser interface Provides web connectivity technology Includes the trending functionality Supports Carrier Connect Services Remote connectivity alarm notification...

Page 7: ...7 Fire damper output Defrost mechanism reversible HP Refrigerant leak detection Diagnostics...

Page 8: ...ction 5 6 One Ethernet ports allow for TCP IP communication connection Connections on the bottom side of the controller 3 4 Power supply to boards All boards are supplied from a common 24 VAC supply r...

Page 9: ...lpy contact SIOB2 circuit B DI 04 J1 Supply fan status contact SIOB1 circuit A DI 07 J1 Indoor air flow verification input Fire contact SIOB1 circuit A DI 05 Fire safety input Alarm relay output SIOB1...

Page 10: ...gle circuit unit Y1 compressor 1 on off Y2 compressor 2 on off W additional heating stage 1 on off W2 additional heating stage 2 on off O cycle reversing valve on off heat pump units TSTAT Types TSTAT...

Page 11: ...to be reduced by as much as 3K and to be increased by as much as 3K a button to extend the occupied period extension value entered in the configuration menu see GENCONF menu Supply air temperature sen...

Page 12: ...eft is return fan and the values below are return airflow and RAT Outdoor Air Temperature OAT This parameter is displayed only in case of units fitted with OAT sensor Current freshair supply fan RTU I...

Page 13: ...rol mode Unit is currently stopped blue icon Unit is currently running green icon Alarm menu Press the button to go to the Alarms menu The grey bell means there is currently no alarm active on the uni...

Page 14: ...left 4 8 Screen calibration Thepurposeofscreencalibrationistomakesurethatthesoftware acts correctly upon pressing icons on the user interface To calibrate the screen 1 Press and hold anywhere on the s...

Page 15: ...Configuration menu See section 5 2 Home Previous screen Main Menu System Menu User Login Start Stop Alarms Menu General Parameters Parameters Temperatures Pressures Inputs Outputs Run Times Modes Qui...

Page 16: ...yp 0 to 3 0 Local 0 CCN 1 Remote 2 0 3 blank TSTAT 3 STATUS CHARS8 0 Run Status ALM CHARS8 0 Alarm state min_left 0 to 0 0 min Minutes Left for Start 0 0 HEATCOOL CHARS8 0 Heat Cool status HC_SEL 0 to...

Page 17: ...aving Water Temp 0 0 SCT_A 0 to 0 0 F Saturated Condensing T A 0 0 SST_A 0 to 0 0 F Saturated Suction Temp A 0 0 SUCT_A 0 to 0 0 F EXV Suction Temp A 0 0 DEFRT_A 0 to 0 0 F Defrost Temperature A 0 0 S...

Page 18: ...tch 0 1 SP_SW1 OPEN_CLOSE 0 Remote Setpoint Switch 1 0 1 SP_SW2 OPEN_CLOSE 0 Remote Setpoint Switch 2 0 1 lim_sw1 OPEN_CLOSE 0 Limit Switch 0 1 HS_FBK OPEN_CLOSE 0 Heat Stages status 0 1 PRE_HS OPEN_C...

Page 19: ...E hpsw_b OPEN_CLOSE 0 High Pressure Switch B 0 1 hpsw_c OPEN_CLOSE 0 High Pressure Switch THR 0 1 exvA_fbk 0 to 0 0 EXV Position Circuit A 0 0 exvB_fbk 0 to 0 0 EXV Position Circuit B 0 0 exvC_fbk 0 t...

Page 20: ...Output 0 1 cp_c2 OFF_ON 0 THR Compressor 2 Output 0 1 rv_c OFF_ON 0 4Way Refrig Valve THR 0 1 ecopos 0 to 0 0 Economizer Position 0 0 gas_on OFF_ON 0 Modulated Gas Enable 0 1 gas_v 0 to 0 0 Modulated...

Page 21: ...0 0 EXV Position Circuit THR 0 0 hs_1 OFF_ON 0 Heater Stage 1 0 1 hs_2 OFF_ON 0 Heater Stage 2 0 1 hs_3 OFF_ON 0 Heater Stage 3 0 1 hs_4 OFF_ON 0 Heater Stage 4 0 1 pre_hs_1 OFF_ON 0 Pre heater Stage...

Page 22: ...s Compressor A2 Hours 0 0 st_cp_a2 0 to 0 0 Compressor A2 Starts 0 0 hr_cp_b1 0 to 0 0 hours Compressor B1 Hours 0 0 st_cp_b1 0 to 0 0 Compressor B1 Starts 0 0 hr_cp_b2 0 to 0 0 hours Compressor B2 Ho...

Page 23: ...1 m_dehumi NO_YES 0 Dehumidification Mode 0 1 m_iaq NO_YES 0 IAQ Mode 0 1 m_gas NO_YES 0 OAT Gas Threshold 0 1 m_fire NO_YES 0 Fire Shutdown Active 0 1 m_enth NO_YES 0 Enthalpy Lockout 0 1 m_start NO...

Page 24: ...T High Limit 60 110 purg_du 1 to 5 2 min Purge Duration 1 5 iaq_sp 50 to 10000 700 IAQ Setpoint 50 10000 Trendings TRENDING Name Status Unit Displayed text Description GENUNIT_cap_t 0 to 100 Perecent...

Page 25: ...n menu Date Time Configuration Home Previous screen Main Menu User Login Start Stop Alarms Menu Genunit Config User Configuration Hea Cool Config Schedule Menu Holiday Menu Reset Config Configuration...

Page 26: ...NO_YES 0 Thermostat Control 0 1 frst_sel NO_YES 0 Frost Protection Select 0 1 spt_ctrl 0 to 4 0 SPT Calculation Select 0 4 blank 0 Average Temp Meth blank 1 High Temp Sensor blank 2 Low Temp Sensor bl...

Page 27: ...ARTVU CONTROL MENU STRUCTURE synoptic NO_YES 0 Synoptic Is Displayed 0 1 User Configuration USERCONF Point Name Status Default Unit Description Low Limit High Limit use_pass 1 to 9999 11 User Password...

Page 28: ...mer months and back again in the fall in order to make better use of natural daylight Greenwich Mean Time UTC Location Time zone YYYY MM DD HH MM SS Date Time Current date and time must be set manuall...

Page 29: ...ule setting please see section 6 24 5 4 Holiday menu The Holiday menu allows the user to set up to 16 holiday periods which are defined by the start month start day and duration Holiday Menu HOLIDAY I...

Page 30: ...ion RAM usage 0 to 100 FLASH Memory utilization Flash memory usage Depends on the selected language English by default EOL Resistor Menu EOLRES Status Default Displayed text Description disable enable...

Page 31: ...me zone YYYY MM DD HH MM SS Date Time Current date and time must be set manually no yes Today is a Holiday Information about holidays read only Please note that holidays are set in the Holiday menu se...

Page 32: ...NN N SDK Version SDK version number NN UI Version User interface version CARRIER Brand Brand name Depends on the selected language English by default Hardware Info Menu HWINFO Status Displayed text De...

Page 33: ...ess the User Login button and then select User Login 2 Press the Password box 3 Provide the password 11 and press the Confirm button 4 The User Login screen appears 5 6 3 User password User password c...

Page 34: ...layed 5 7 3 Unit stop To stop the unit 1 Press the Start Stop button 2 ConfirmtheunitshutdownbypressingConfirmStoporcancel the unit shutdown by pressing the Backbutton Unit start stop screen operating...

Page 35: ......

Page 36: ...ocess failure compressor failure and VFD drives IMPORTANT For more information about alarms please go to section 8 6 Current Alarms Menu CUR_ALM No Name Date Hour Alarm text 1 Alarm YYYY MM DD HH MM A...

Page 37: ...urrent Alarm 1 Alarm code see section 8 6 4 alarm_2c Current Alarm 2 Alarm code see section 8 6 5 alarm_3c Current Alarm 3 Alarm code see section 8 6 6 alarm_4c Current Alarm 4 Alarm code see section...

Page 38: ...ed 6 3 Single circuit heat pump unit Contact G open The internal fan is stopped and the economizer is closed Contact G closed The internal fan is activated and the economizer is opened to its minimum...

Page 39: ...le 1 Remote start stop contact status Onoff_sw Start stop contact status can be used to control the unit state in the Remote operating type G This contact is used when unit is in thermostat operating...

Page 40: ...In this case the function is generally used to limit the difference between the indoor and outdoor temperatures in order to prevent thermal shock IMPORTANT It is not possible to use both types of off...

Page 41: ...be vspd_max 10 Volts 6 16 Head pressure control Condensing pressure control is automatically ensured by a two speed fan no adjustment 6 17 Defrost function Defrost is activated when the unit is in hea...

Page 42: ...horised If the unit is fitted with a power exhaust fan this shall be open if the position of the economizer is in excess of 50 this threshold may be modified by Carrier Service 6 22 Purge This functio...

Page 43: ...is in same status with the supply fan and the return fan s speed is command However any faults active when the supply is interrupted are saved and may in certain cases prevent a circuit or a unit from...

Page 44: ...Press the Save button to save your changes or the Cancel button to exit the screen without making modifications Legend 1 Selection of days for the time schedule 2 Start end of the schedule 3 Previous...

Page 45: ...on to display the graph showing trends for the set of selected parameters Set the time range start end dates and time and press the Arrowbutton todisplaythegraphshowingtheperformance of the unit withi...

Page 46: ...y the unit IP address Example https 169 254 1 1 3 Press Enter 4 The web interface will be loaded IMPORTANT Three users can be connected simultaneously with no priority between them The last modificati...

Page 47: ...sting alarms have been reset To define e mail recipients 1 Press theMain menu buttonandnavigatetotheConfiguration menu 2 Go to the Network menu 2 Select Email Configuration EMAILCFG 3 Define user e ma...

Page 48: ...r installation fault Circuit is shut down 15 Pr 02 Circuit B Discharge Transducer As above As above As above 16 Pr 03 Circuit THR Discharge Transducer As above As above As above 17 Pr 04 Circuit A Suc...

Page 49: ...d low suction temp overrides Manual Pressure sensor defective or refrigerant charge too low Circuit is shut down 41 P 41 Circuit B Repeated low suction temp overrides Manual As above As above 42 P 42...

Page 50: ...Superheat B Manual Circuit B shuts down 66 P 10 High Suction Superheat THR As above As above Circuit THR shuts down 67 P 11 Low Suction Superheat A Manual Circuit A shuts down 68 P 12 Low Suction Sup...

Page 51: ...ensure your Carrier equipment is regularly inspected by Carrier Service specialists so that any malfunction is detected and corrected quickly and no serious damage can occur to your equipment The Car...

Page 52: ...o 10508 04 2019 Supersedes order No 10508 04 2019 Manufactured by Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the Europea...

Reviews: