5 - SMARTVU CONTROL: MENU STRUCTURE
The
Configuration menu
gives access to a number of us-
er-modifiable parameters such as pump configuration, schedule
menu, etc. The Configuration menu is password-protected.
■ To access the Configuration menu, press the
Main menu
button
located in the upper-left part of the Home screen, and then
select
Configuration Menu
.
■ Once all the necessary modifications have been made, press
the
Save
button to confirm your changes or the
Cancel
button
to exit the screen without making modifications.
General Configuration
–
GENCONF
System configuration override:
In some cases it is possible to
override system configuration. Note that not all parameters can
be overridden by the control.
CAUTION
: Since specific units may not include additional
features, some tables may contain parameters that cannot be
configured for a given unit.
Point Name
Status
Default
Unit
Description
Low Limit
High Limit
tst_ctrl
NO_YES
0
-
Thermostat Control 0
1
frst_sel
NO_YES
0
-
Frost Protection
Select
0
1
spt_ctrl
0 to 4
0
-
SPT Calculation
Select
0
4
blank
-
0 = Average Temp
Meth
blank
-
1 = High Temp
Sensor
blank
-
2 = Low Temp
Sensor
blank
-
3 = Cool LowT,
heat HiT
blank
-
4 = Cool HiT, heat
LowT
blank
-
ifan_sel
0 to 2
0
-
Indoor Fan
Management
0
2
blank
-
0 = Always On
blank
-
1 = Occ, On
blank
-
Unocc, Cycling
blank
-
2 = Occ, Cycling
blank
-
Unocc, Cycling
blank
-
blank
-
Occupied Period
Start :
purg_sel
NO_YES
0
-
Purge Mode Select 0
1
ovrd_hr
0 to 4
0
hours
Timed Override
Hours
0
4
start_k
0 to 30
0
-
Optimal Start
Factor
0
30
blank
-
blank
-
Demand Limit :
c_limit
0 to 100
0
-
Cooling Demand
Limit
0
100
h_limit
0 to 100
0
-
Heating Demand
Limit
0
100
d_limit
NO_YES
0
-
Defrost Demand
Limit
0
1
hr_limit
0 to 100
0
-
Heater Demand
Limit
0
100
blank
-
off_on_d
1 to 15
1
min
Unit Off to On
Delay
1
15
nh_start
0.00:0.00 to
0.00:0.00
0.00:0.00
-
Night Mode Start
Hour
0.00:0.00
0.00:0.00
nh_end
0.00:0.00 to
0.00:0.00
0.00:0.00
-
Night Mode End
Hour
0.00:0.00
0.00:0.00
bas_menu
0 to 3
0
-
Basic Menu
Configuration
0
3
blank
-
0 = All Access
blank
-
1 = no alarm menu
blank
-
2 = no setpoint
menu
blank
-
3 = 1 + 2