background image

36 

 

 

 

6-  STANDARD  CONTROL OPERATIONS AND  OPTIONS 

 

 

6.1  External thermostat control 
 

 

In appropriate cases the unit may be controlled by an 
external thermostat approved by Carrier. This function 
requires the use of a thermostat with volt-free contacts 
(contacts without potential), as well as a specific 
configuration of the SmartVu control. The function is only 
active when operating type Thermostat (TSTAT) is selected 
in the GENCONF menu. 
 
In this operating type, the thermostat controls the 
following functions: 

 

Stopping/starting the internal fan 

 

Determining the space temperature control point, 

 

Selecting heating/cooling 

 

Controlling compressor capacity, gas or electric 

 

Controlling the economizer (fully open position or 

minimum closed position only). 
 
The SmartVu system continues to control the following 
functions: 

 

Defrosting related to the heat pumps 

 

Head pressure control 

 

Power exhaust control 

 

Minimum stop/start times on the compressors 

 

Unit diagnostics. 

 
 
The following functions are disabled: 

 

Humidification 

 

Controlling a hot-water system 

 

Timer programming 

 

Purge. 

 
The description of the thermostat outputs, based on the 
unit type, is given in the chapter 3.6 - 

“Connections at the 

user terminal block”. 

 

6.2  Cooling only unit 

 
 

 

Contact G open: The internal fan is stopped and the 
economizer is closed. 

 

Contact G closed: The internal fan is activated and the 

 

economizer is opened to its minimum position. 

 

Contact Y1 closed and Y2 open: If the unit is fitted with 
an economizer, it is opened to its maximum position, if 

 

external conditions permit (see chapter 5.16 - 
“Economizer”). 

 

Otherwise the economizer is set to its minimumposition 
and the first compressor is started up. If the unit has no 
economizer, the first compressor is started up. 

Contacts Y1 and Y2 closed: The economizer is held fully 
open if external conditions are still acceptable. A compressor 
is started up. If external conditions nolonger permit the 
economizer to be used, it is set to itsminimum position and 
the second compressor is started up. If the outdoor 
temperature is lower than 15°C, thecompressors will not be 
authorised to start up and onlythe economizer will be used. If 
the unit has no economizer, the second compressor is 
started up. 

 
 
 

 

 
 

 

Contact W1 closed and W2 open: The first gas or 

electric stage is started. 

 

Contacts W1 and W2 closed: The second gas or 

electric stage is started. 
 

 

6.3  Single-circuit heat pump unit 

 

 

Contact G open: The internal fan is stopped and the 
economizer is closed. 

 

Contact G closed: The internal fan is activated and the 
economizer is opened to its minimum position. 

 

Contact O closed and Y closed: If the unit is fitted with 
an economizer, it is modulated to maintain the minimum  
supply air temperature setpoint at +2.8°C, if external 
conditions permit (see chapter 5.16 - 

“Economizer”). 

Otherwise the economizer is set to its minimum position 
and the compressor is started up in cooling mode. If 
the unit has no economizer, the compressor is started 
up in cooling mode. 

 

Contacts O open and Y closed: If the unit is fitted with an 
economizer, it is set to its minimum position and 
the first compressor is started up in heating mode.  

 

Contact W1 closed and W2 open: The first gas or electric 
stage is started. 

 

Contacts W1 and W2 closed: The second gas or 
electric stage is started. 

 

6.4  Dual-circuit/dual-compressor heat pump unit

 

 
 

 

Contact G open: The internal fan is stopped and the 
economizer is closed. 

 

Contact G closed: The internal fan is activated and the 
economizer is opened to its minimum position. 

 

Contact O closed, Y1 closed and Y2 open: If the unit is 
fitted with an economizer, it is opened to its maximum 
position, if external conditions permit (see chapter 5.16 - 
“Economizer”). Otherwise the economizer is set to its 
minimum position and the first compressor is started up 
in cooling mode. If the unit has no economizer, the first 
compressor is started up in cooling mode. 

 

Contacts O, Y1 and Y2 closed: The economizer is held 
fully open , if external conditions are still acceptable.  A 
compressor is started up in cooling mode. If external 
conditions no longer permit the economizer to be used, it 
is set to its minimum position and the second 
compressor is started up in cooling mode. If the outdoor 
temperature 

is lower than 15°C, the compressors will not 

be authorised to start up and only the economizer will be 
used. If the unit has no economizer, the second 
compressor is started up in cooling mode. 

 

Contact O open, Y1 closed and Y2 open: If the unit is 
fitted with an economizer, it is set to its minimum 
position and the first compressor is started up in heating 
mode. If the unit has no economizer, the first 
compressor is started up in heating mode. 

 

Contact O open, Y1 and Y2 closed: The economizer is 
held in its minimum position. The second compressor is 
started up in heating mode. 

 

Contact W1 closed: The first gas or electric stage is  
started. 

NOTE: All compressor anti-short cycles remain 
activated 

 

 
 
 
 

Summary of Contents for SmartVu control

Page 1: ...CONTROLS MANUAL SmartVu Control 50 48 UC V UP V 025 220 Original document...

Page 2: ...9 Alarms menu 34 6 STANDARD CONTROL OPERATIONS AND OPTIONS 36 6 1 External thermostat control 36 6 2 Cooling only unit 37 6 3 Single circuit heat pump unit 37 6 4 Dual circuit dual compressor heat pu...

Page 3: ...aying current alarms 49 8 3 E mail notifications 49 8 4 Resetting alarms 49 8 5 Alarm history 49 8 6 Alarm codes 50 9 MAINTENANCE 57 The cover photos are solely for illustration and forms no part of a...

Page 4: ...The information provided herein is solely for the purpose of allowing customers to operate and service Carrier manufactured equipment and it is not to be reproduced modified or used for any other purp...

Page 5: ...ools to move heavy objects Move units carefully and set them down gently CAUTION Only qualified service technicians should be allowed to install and service the equipment 1 2 Safety precautions Only p...

Page 6: ...users tocontrol the unit viathe SmartVuuser interface Provides web connectivity technology Includes the trending functionality Supports Carrier Connect Services Remote connectivity alarm notification...

Page 7: ...7 Fire damper output Defrost mechanism reversible HP Refrigerant leak detection Diagnostics...

Page 8: ...ction 5 6 One Ethernet ports allow for TCP IP communication connection Connections on the bottom side of the controller 3 4 Power supply to boards All boards are supplied from a common 24 VAC supply r...

Page 9: ...lpy contact SIOB2 circuit B DI 04 J1 Supply fan status contact SIOB1 circuit A DI 07 J1 Indoor air flow verification input Fire contact SIOB1 circuit A DI 05 Fire safety input Alarm relay output SIOB1...

Page 10: ...gle circuit unit Y1 compressor 1 on off Y2 compressor 2 on off W additional heating stage 1 on off W2 additional heating stage 2 on off O cycle reversing valve on off heat pump units TSTAT Types TSTAT...

Page 11: ...to be reduced by as much as 3K and to be increased by as much as 3K a button to extend the occupied period extension value entered in the configuration menu see GENCONF menu Supply air temperature sen...

Page 12: ...eft is return fan and the values below are return airflow and RAT Outdoor Air Temperature OAT This parameter is displayed only in case of units fitted with OAT sensor Current freshair supply fan RTU I...

Page 13: ...rol mode Unit is currently stopped blue icon Unit is currently running green icon Alarm menu Press the button to go to the Alarms menu The grey bell means there is currently no alarm active on the uni...

Page 14: ...left 4 8 Screen calibration Thepurposeofscreencalibrationistomakesurethatthesoftware acts correctly upon pressing icons on the user interface To calibrate the screen 1 Press and hold anywhere on the s...

Page 15: ...Configuration menu See section 5 2 Home Previous screen Main Menu System Menu User Login Start Stop Alarms Menu General Parameters Parameters Temperatures Pressures Inputs Outputs Run Times Modes Qui...

Page 16: ...yp 0 to 3 0 Local 0 CCN 1 Remote 2 0 3 blank TSTAT 3 STATUS CHARS8 0 Run Status ALM CHARS8 0 Alarm state min_left 0 to 0 0 min Minutes Left for Start 0 0 HEATCOOL CHARS8 0 Heat Cool status HC_SEL 0 to...

Page 17: ...aving Water Temp 0 0 SCT_A 0 to 0 0 F Saturated Condensing T A 0 0 SST_A 0 to 0 0 F Saturated Suction Temp A 0 0 SUCT_A 0 to 0 0 F EXV Suction Temp A 0 0 DEFRT_A 0 to 0 0 F Defrost Temperature A 0 0 S...

Page 18: ...tch 0 1 SP_SW1 OPEN_CLOSE 0 Remote Setpoint Switch 1 0 1 SP_SW2 OPEN_CLOSE 0 Remote Setpoint Switch 2 0 1 lim_sw1 OPEN_CLOSE 0 Limit Switch 0 1 HS_FBK OPEN_CLOSE 0 Heat Stages status 0 1 PRE_HS OPEN_C...

Page 19: ...E hpsw_b OPEN_CLOSE 0 High Pressure Switch B 0 1 hpsw_c OPEN_CLOSE 0 High Pressure Switch THR 0 1 exvA_fbk 0 to 0 0 EXV Position Circuit A 0 0 exvB_fbk 0 to 0 0 EXV Position Circuit B 0 0 exvC_fbk 0 t...

Page 20: ...Output 0 1 cp_c2 OFF_ON 0 THR Compressor 2 Output 0 1 rv_c OFF_ON 0 4Way Refrig Valve THR 0 1 ecopos 0 to 0 0 Economizer Position 0 0 gas_on OFF_ON 0 Modulated Gas Enable 0 1 gas_v 0 to 0 0 Modulated...

Page 21: ...0 0 EXV Position Circuit THR 0 0 hs_1 OFF_ON 0 Heater Stage 1 0 1 hs_2 OFF_ON 0 Heater Stage 2 0 1 hs_3 OFF_ON 0 Heater Stage 3 0 1 hs_4 OFF_ON 0 Heater Stage 4 0 1 pre_hs_1 OFF_ON 0 Pre heater Stage...

Page 22: ...s Compressor A2 Hours 0 0 st_cp_a2 0 to 0 0 Compressor A2 Starts 0 0 hr_cp_b1 0 to 0 0 hours Compressor B1 Hours 0 0 st_cp_b1 0 to 0 0 Compressor B1 Starts 0 0 hr_cp_b2 0 to 0 0 hours Compressor B2 Ho...

Page 23: ...1 m_dehumi NO_YES 0 Dehumidification Mode 0 1 m_iaq NO_YES 0 IAQ Mode 0 1 m_gas NO_YES 0 OAT Gas Threshold 0 1 m_fire NO_YES 0 Fire Shutdown Active 0 1 m_enth NO_YES 0 Enthalpy Lockout 0 1 m_start NO...

Page 24: ...T High Limit 60 110 purg_du 1 to 5 2 min Purge Duration 1 5 iaq_sp 50 to 10000 700 IAQ Setpoint 50 10000 Trendings TRENDING Name Status Unit Displayed text Description GENUNIT_cap_t 0 to 100 Perecent...

Page 25: ...n menu Date Time Configuration Home Previous screen Main Menu User Login Start Stop Alarms Menu Genunit Config User Configuration Hea Cool Config Schedule Menu Holiday Menu Reset Config Configuration...

Page 26: ...NO_YES 0 Thermostat Control 0 1 frst_sel NO_YES 0 Frost Protection Select 0 1 spt_ctrl 0 to 4 0 SPT Calculation Select 0 4 blank 0 Average Temp Meth blank 1 High Temp Sensor blank 2 Low Temp Sensor bl...

Page 27: ...ARTVU CONTROL MENU STRUCTURE synoptic NO_YES 0 Synoptic Is Displayed 0 1 User Configuration USERCONF Point Name Status Default Unit Description Low Limit High Limit use_pass 1 to 9999 11 User Password...

Page 28: ...mer months and back again in the fall in order to make better use of natural daylight Greenwich Mean Time UTC Location Time zone YYYY MM DD HH MM SS Date Time Current date and time must be set manuall...

Page 29: ...ule setting please see section 6 24 5 4 Holiday menu The Holiday menu allows the user to set up to 16 holiday periods which are defined by the start month start day and duration Holiday Menu HOLIDAY I...

Page 30: ...ion RAM usage 0 to 100 FLASH Memory utilization Flash memory usage Depends on the selected language English by default EOL Resistor Menu EOLRES Status Default Displayed text Description disable enable...

Page 31: ...me zone YYYY MM DD HH MM SS Date Time Current date and time must be set manually no yes Today is a Holiday Information about holidays read only Please note that holidays are set in the Holiday menu se...

Page 32: ...NN N SDK Version SDK version number NN UI Version User interface version CARRIER Brand Brand name Depends on the selected language English by default Hardware Info Menu HWINFO Status Displayed text De...

Page 33: ...ess the User Login button and then select User Login 2 Press the Password box 3 Provide the password 11 and press the Confirm button 4 The User Login screen appears 5 6 3 User password User password c...

Page 34: ...layed 5 7 3 Unit stop To stop the unit 1 Press the Start Stop button 2 ConfirmtheunitshutdownbypressingConfirmStoporcancel the unit shutdown by pressing the Backbutton Unit start stop screen operating...

Page 35: ......

Page 36: ...ocess failure compressor failure and VFD drives IMPORTANT For more information about alarms please go to section 8 6 Current Alarms Menu CUR_ALM No Name Date Hour Alarm text 1 Alarm YYYY MM DD HH MM A...

Page 37: ...urrent Alarm 1 Alarm code see section 8 6 4 alarm_2c Current Alarm 2 Alarm code see section 8 6 5 alarm_3c Current Alarm 3 Alarm code see section 8 6 6 alarm_4c Current Alarm 4 Alarm code see section...

Page 38: ...ed 6 3 Single circuit heat pump unit Contact G open The internal fan is stopped and the economizer is closed Contact G closed The internal fan is activated and the economizer is opened to its minimum...

Page 39: ...le 1 Remote start stop contact status Onoff_sw Start stop contact status can be used to control the unit state in the Remote operating type G This contact is used when unit is in thermostat operating...

Page 40: ...In this case the function is generally used to limit the difference between the indoor and outdoor temperatures in order to prevent thermal shock IMPORTANT It is not possible to use both types of off...

Page 41: ...be vspd_max 10 Volts 6 16 Head pressure control Condensing pressure control is automatically ensured by a two speed fan no adjustment 6 17 Defrost function Defrost is activated when the unit is in hea...

Page 42: ...horised If the unit is fitted with a power exhaust fan this shall be open if the position of the economizer is in excess of 50 this threshold may be modified by Carrier Service 6 22 Purge This functio...

Page 43: ...is in same status with the supply fan and the return fan s speed is command However any faults active when the supply is interrupted are saved and may in certain cases prevent a circuit or a unit from...

Page 44: ...Press the Save button to save your changes or the Cancel button to exit the screen without making modifications Legend 1 Selection of days for the time schedule 2 Start end of the schedule 3 Previous...

Page 45: ...on to display the graph showing trends for the set of selected parameters Set the time range start end dates and time and press the Arrowbutton todisplaythegraphshowingtheperformance of the unit withi...

Page 46: ...y the unit IP address Example https 169 254 1 1 3 Press Enter 4 The web interface will be loaded IMPORTANT Three users can be connected simultaneously with no priority between them The last modificati...

Page 47: ...sting alarms have been reset To define e mail recipients 1 Press theMain menu buttonandnavigatetotheConfiguration menu 2 Go to the Network menu 2 Select Email Configuration EMAILCFG 3 Define user e ma...

Page 48: ...r installation fault Circuit is shut down 15 Pr 02 Circuit B Discharge Transducer As above As above As above 16 Pr 03 Circuit THR Discharge Transducer As above As above As above 17 Pr 04 Circuit A Suc...

Page 49: ...d low suction temp overrides Manual Pressure sensor defective or refrigerant charge too low Circuit is shut down 41 P 41 Circuit B Repeated low suction temp overrides Manual As above As above 42 P 42...

Page 50: ...Superheat B Manual Circuit B shuts down 66 P 10 High Suction Superheat THR As above As above Circuit THR shuts down 67 P 11 Low Suction Superheat A Manual Circuit A shuts down 68 P 12 Low Suction Sup...

Page 51: ...ensure your Carrier equipment is regularly inspected by Carrier Service specialists so that any malfunction is detected and corrected quickly and no serious damage can occur to your equipment The Car...

Page 52: ...o 10508 04 2019 Supersedes order No 10508 04 2019 Manufactured by Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the Europea...

Reviews: