Appendix B - BACnet Protocol Implementation Conformance Statement
34
RTU-MP Controller
XX
ISO 8859-1
XX
ISO 10646 (UCS-2)
XX
ISO 10646 (ICS-4)
XX
JIS C 6226
Analog Input
1. Creatable?
Analog Input, Analog Input (TLO), Analog Input (PTA), Analog Input (RS):
NO
2. Deletable?
NO
3. Optional Properties
Supported:
acked_transitions
cov_increment
deadband
description
device_type
event_enable
event_time_stamps
high_limit
limit_enable
low_limit
max_pres_value
min_pres_value
notification_class
notify_type
reliability
resolution
time_delay
update_interval
4. Writeable Properties:
cov_increment
deadband
description
device_type
event_enable
high_limit
limit_enable
low_limit
notification_class
notify_type
out_of_service
time_delay
units
5. Proprietary properties:
None
6. Range Restrictions:
description
limited to 50 octets in length
device_type
limited to 50 octets in length
present_value
limited by min_pres_value and max_pres_value properties
notification_class
must be valid notification_class
time_delay
0 to 4294967295
Analog Output
1. Creatable?
Analog Output, Analog Output (FM), and Analog Output (PWM):
NO
2. Deletable?
NO
Summary of Contents for RTU-MP
Page 2: ......
Page 6: ...Introduction 2 RTU MP Controller...
Page 54: ......
Page 56: ......
Page 57: ......