RTU-MP Controller
35
3. Optional Properties
Supported:
Analog Output, Analog Output (FM), and Analog Output (PWM):
acked_transitions
cov_increment
deadband
description
device_type
event_enable
event_time_stamps
high_limit
limit_enable
low_limit
max_pres_value
min_pres_value
notification_class
notify_type
reliability
resolution
time_delay
4. Writeable Properties:
cov_increment
deadband
description
device_type
event_enable
high_limit
limit_enable
low_limit
notification_class
notify_type
out_of_service
present_value
relinquish_default
time_delay
units
5. Proprietary properties:
None
6. Range Restrictions:
description
limited to 50 octets in length
device_type
limited to 50 octets in length
present_value
limited by min_pres_value and max_pres_value properties
relinquish_default
limited by min_pres_value and max_pres_value properties
notification_class
must be valid notification_class
time_delay
0 to 4294967295
Analog Value (PAR)
Analog Value (PAR):
1. Creatable?
NO
2. Deletable?
NO
3. Optional Properties
Supported:
acked_transitions
cov_increment
deadband
description
device_type
event_enable
event_time_stamps
high_limit
limit_enable
low_limit
notification_class
notify_type
priority_array
reliability
relinquish_default
time_delay
4. Writeable Properties:
cov_increment
deadband
description
device_type
event_enable
high_limit
limit_enable
low_limit
notification_class
notify_type
out_of_service
present_value
relinquish_default
time_delay
units
5. Proprietary properties:
None
6. Range Restrictions:
description
limited to 50 octets in length
present_value
limited by min_pres_value and max_pres_value properties
Summary of Contents for RTU-MP
Page 2: ......
Page 6: ...Introduction 2 RTU MP Controller...
Page 54: ......
Page 56: ......