RTU-MP Controller 

15 

 

The BAS is scheduling the unit via an On/Off command to the BAS ON/OFF software point. The Building 

Automation System can be speaking BACnet, Modbus, or N2 and is writing to the BAS On/Off point in the 

open protocol point map. 

BAS On/Off

 

 

A hard-wired input on the RTU-MP will command the unit to start/stop. Inputs 3, 5, 8, and 9 on plug 

J5

 

can be hard-wired to command the unit to start/stop. 

DI On/Off 

NOTE  

Scheduling can either be controlled via the unit or the BAS, but NOT both. 

  
 

 

Indoor Fan 

The indoor fan will be turned on whenever any one of the following conditions is true:  

 

It is in the occupied mode - this will be determined by its own internal occupancy schedule  

 

Whenever there is a demand for cooling or heating in the unoccupied mode  

 

Whenever the remote occupancy switch is closed during 

DI On/Off 

schedule type or if occupancy is 

forced occupied by the BAS during BAS 

On/Off

 schedule type.  

When transitioning from unoccupied to occupied, there will be a configured time delay of 5 to 600 seconds 

before starting the fan. The fan will continue to run as long as compressors, heating stages, or the 

dehumidification relays are on when transitioning from occupied to unoccupied, with the exception of 

Shutdown mode.  
If Fire Shutdown, safety chain, SAT alarm or SPT alarm are active, the fan will be shutdown immediately, 

regardless of the occupancy state or demand.  
The RTU-MP does not include controls/algorithms for additional building smoke-control functions such as 

smoke-purge, zone-pressurization or smoke-ventilation.  Each of these requires a field-designed circuit to 

input the proper signals to the RTU-MP and to operate the following, as required by local fire codes: 

 

de-activation of smoke alarm signal 

 

RTU Indoor Fan 

 

RTU economizer 

 

RTU power exhaust 

The RTU-MP has an optional Supply Fan Status input to provide proof of airflow. If this is enabled, the point 

will look for a contact closure whenever the Supply Fan Relay is on. If it is not enabled, then it will always be 

the same state as the Supply Fan Relay. The cooling, economizer, heating, dehumidification, CO2 and power 

exhaust routines will use this input point for fan status.  
  
 

 

Cooling 

The compressor outputs are controlled by the Cooling Control PID Loop and Cooling Stages Capacity 

algorithm. They will be used to calculate the desired number of stages needed to satisfy the space by 

comparing the Space Temperature (SPT) to the Occupied Cool Setpoint, plus the T56 slider offset, when 

occupied and the Unoccupied Cool Setpoint (UCSP), plus the T56 slider offset, if unoccupied. The economizer, 

if available, will be used for cooling in addition to the compressors.  
The following conditions must be true in order for this algorithm to run:  

 

Indoor Fan has been ON for at least 30 seconds  

Summary of Contents for RTU-MP

Page 1: ...P C Co on nt tr ro ol ll le er r I In nt te eg gr ra at ti io on n G Gu ui id de e CARRIER CORPORATION 2011 A member of the United Technologies Corporation family Stock symbol UTX Catalog No 48 50H T...

Page 2: ......

Page 3: ...n 13 Scheduling 13 Indoor Fan 15 Cooling 15 Economizer 16 Power Exhaust 17 Heating 17 Indoor Air Quality 18 Dehumidification 18 Demand Limiting 19 Troubleshooting 20 LED s 20 BACnet MSTP 21 Modbus 23...

Page 4: ...ue STAT 42 Notification Class 43 Program 43 Schedule 43 Trend_log 44 Appendix D Johnson Controls N2 Protocol Implementation Conformance Statement 45 Appendix C Modbus Protocol Implementation Conforman...

Page 5: ...ation System BAS On board DIP switches allow you choose your protocol and baud rate BACnet Modbus Johnson N2 or LonWorks This document will serve as the reference guide for integrating RTU MP into the...

Page 6: ...Introduction 2 RTU MP Controller...

Page 7: ...ert symbol When you see this symbol on the unit in the instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used...

Page 8: ...tus fanstat DI 24 VAC J5 1 2 or J5 3 4 or J5 5 6 or J5 7 8 Filter Status filstat DI 24 VAC J5 1 2 or J5 3 4 or J5 5 6 or J5 7 8 Remote Occupancy Input remocc DI 24 VAC J5 1 2 or J5 3 4 or J5 5 6 or J5...

Page 9: ...o communicate using one of four different protocols BACnet Modbus N2 or LonWorks The default setting is BACnet Switch 3 SW3 on the board is used to set protocol and baud rate Switches 1 and 2 SW1 and...

Page 10: ...re 16 is the BACnet vendor ID for Carrier Carrier Corporation and xx equals the rotary switch address EXAMPLE To set the RTU MP s MS TP MAC address to 01 point the arrow on the MSB SW1 switch to 0 and...

Page 11: ...ent 7 Turn on the RTU MP s power Configuring the RTU MP for Modbus RTU Refer to Appendix C of this document for the Modbus Protocol Implementation Conformance Statement PICS 1 Turn off the RTU MP s po...

Page 12: ...6 for Modbus See example below 5 Leave DS7 and DS8 in the OFF position These switches are not applicable to Modbus SW3 Protocol Switch Settings for Modbus DS8 DS7 DS6 DS5 DS4 DS3 Off Off Off On On Off...

Page 13: ...slave address to 01 point the arrow on the MSB SW1 switch to 0 and the arrow on the LSB SW1 switch to 1 3 Set the Comm Selector DIP switches DS1 and DS2 for the 9600 baud NOTE Use the same baud rate...

Page 14: ...uit board with fingerprints moisture or any foreign material Do not touch components or leads Handle the board by its edges Isolate from high voltage or electrostatic discharge Ensure that you are pro...

Page 15: ...ion to enable the LON OC 5 Leave Comm Selector DIP Switch DS8 on SW3 in the OFF position since it is not used SW3 Protocol Switch Settings for LonWorks DS8 DS7 DS6 DS5 DS4 DS3 Off On On Off On Off The...

Page 16: ...hese variables can be bound or accessed by the network management tool NOTE Contact your local Carrier representative for a copy of the XIF file The Browse feature of the Network Management Tool also...

Page 17: ...own hardware clock that is set automatically when the software is installed on the board The default is to control to occupied setpoints all the time until a type of occupancy control is set Occupancy...

Page 18: ...times 7 Edit these times following Steps 5 and 6 8 Scroll down to Days section and highlight the days required for the Daily schedule by INCR or DECR softkeys 9 Press the OK softkey The Holiday schedu...

Page 19: ...SPT alarm are active the fan will be shutdown immediately regardless of the occupancy state or demand The RTU MP does not include controls algorithms for additional building smoke control functions su...

Page 20: ...the supply air temperature has increased above the low supply air setpoint After a compressor is staged off it may be started again after a normal time guard period and the supply air temperature has...

Page 21: ...e true in order for this algorithm to run Indoor Fan has been ON for at least 30 seconds Cool mode is not active and the time guard between modes equals zero If occupied and SPT occupied heat setpoint...

Page 22: ...mum damper position configuration then it will be clamped to the configured value Dehumidification The RTU MP provides occupied and unoccupied dehumidification on units that are equipped with the Carr...

Page 23: ...degree offset 2 two degree offset or a 3 4 degree offset to the BACnet demand limit variable the controller expands the heating and cooling setpoints by the configured demand limit setpoint value and...

Page 24: ...erator should begin troubleshooting the unit equipment rather than the RTU MP or network Third party network may also help in troubleshooting the controller and rooftop unit Third party network troubl...

Page 25: ...the same communication settings 8 data bits No Parity and 1 stop bit 5 Verify proper connection wiring between the BAS and the controller 6 Verify that the controller has a unique MAC address on the M...

Page 26: ...software asks the controllers Who Is This is to auto locate devices on the network Only controllers set as masters will answer this request See Appendix A for Points Mapping tables See Appendix B for...

Page 27: ...controller s unique slave address 7 BAS must be reading or writing to the proper point addresses on the controller 8 BAS is sending requests to the proper slave address of the controller NOTES Refer t...

Page 28: ...w the active protocol and baud rate 2 Verify that the BAS and the controller are both set for the same baud rate 38 4k for LonWorks Comm Selector DIP switches DS2 and DS1 By getting a Modstat of the c...

Page 29: ...se harmful interference in which case the user will be required to correct the interference at his own expense CAUTION Changes or modifications not expressly approved by the responsible party for comp...

Page 30: ...101 AV 4101 AV 2102 AV 4102 AV 3003 AV 4002 AV 2002 AV 4006 AV 2001 AV 4004 AV 4005 AV 2004 AV 2005 AV 2015 AV 4025 AV 3004 AV 4003 AV 2003 AV 4011 AV 4010 AV 4009 BACnet Point Name lstat zone_temp ls...

Page 31: ...dbus Register Type float value float value float value float value float value float value float value float value float value float value float value float value float value float value float value f...

Page 32: ...e in discrete out discrete in discrete in discrete in discrete in discrete in discrete in discrete in discrete in BACnet Info BACnet Object ID AV 4022 AV 4020 BV 4006 BV 4005 BV 2101 BV 4101 BV 2102 B...

Page 33: ...Set 1 no function 2 Enthalpy Switch 3 Fan status 4 Filter status 5 Remote occupancy BACnet Point Name test_c2 test_hmz test_h1 test_h2 test_x2 test_sf sf sf_rt_clear fanstat sys_down inp_01_func inp_0...

Page 34: ...t status 1 Off 2 Fan Only 3 Free Cooling 4 Cooling 5 Heating 6 Dehumidification 7 Test 8 Shutdown BACnet Info BACnet Object ID MSV 3018 MSV 3009 MSV 3019 MSV 4003 MSV 4002 MSV 4001 MSV 2001 MSV 2002 B...

Page 35: ...e in discrete in BACnet Info BACnet Object ID BV 7021 BV 7005 BV 7020 BV 7022 BV 7019 BV 7006 BV 7003 BV 7023 BV 7002 BV 7024 BV 7010 BV 7012 BV 7001 BV 7004 BV 7008 BV 7009 BV 7011 BV 6001 BACnet Poi...

Page 36: ...e protocols BACnet Standardize Device Profile Annex K B AAC List of all BACnet Interoperability Building Blocks Supported Annex K DS RP A AE N I B SCHED I B T VMT I B DM DDB A DS RP B AE ACK B T ATR B...

Page 37: ...dium __________ Other Device Address Binding Methods Supported XX Send Who Is receive I Am BIBB DM DDB A XX Receive Who Is send I Am BIBB DM DDB B XX Send Who Has receive I Have BIBB DM DOB A XX Recei...

Page 38: ...ue notification_class notify_type reliability resolution time_delay update_interval 4 Writeable Properties cov_increment deadband description device_type event_enable high_limit limit_enable low_limit...

Page 39: ...ited by min_pres_value and max_pres_value properties relinquish_default limited by min_pres_value and max_pres_value properties notification_class must be valid notification_class time_delay 0 to 4294...

Page 40: ...s None 6 Range Restrictions None Analog Value STAT Analog Value STAT 1 Creatable NO 2 Deletable NO 3 Optional Properties Supported acked_transitions cov_increment deadband description event_enable eve...

Page 41: ...4967295 description limited to 50 octets in length device_type limited to 50 octets in length elapsed_active_time 0 to 4294967295 inactive_text limited to 50 octets in length notification_class must b...

Page 42: ...NO 3 Optional Properties Supported acked_transitions active_text alarm_value change_of_state_count change_of_state_time description elapsed_active_time event_enable event_time_stamps inactive_text mi...

Page 43: ..._off_time minimum_on_time notification_class notify_type reliability time_delay time_of_active_time_reset time_of_state_count_reset 4 Writeable Properties active_text alarm_value change_of_state_count...

Page 44: ...es alarm_value event_enable notification_class notify_type out_of_service time_delay 5 Proprietary properties None 6 Range Restrictions notification_class must be valid notification_class time_delay 0...

Page 45: ...etries object_identifier object_name time_synchronization_recipients utc_offset 5 Proprietary properties None 6 Range Restrictions description limited to 50 octets in length location limited to 50 oct...

Page 46: ...s description limited to 50 octets in length notification_class must be valid notification_class present_value must be valid state relinquish_default must be valid state time_delay 0 to 4294967295 Mul...

Page 47: ...le Program NO 2 Deletable NO 3 Optional Properties Supported description description_of_halt instance_of program_location reason_for_halt reliability 4 Writeable Properties description program_change...

Page 48: ...upported acked_transitions client_cov_increment cov_resubscription_interval current_notify_time description event_enable event_time_stamps log_device_object_property log_interval notification_class no...

Page 49: ...s The RTU MP controller speaks the Johnson N2 Open Protocol as described in the Metasys N2 System Protocol Specification for Vendors document revision 6 13 96 Further details on the N2 supported imple...

Page 50: ...RTU MP Controller Read Analog Output Read Binary Output Read Internal Parameter Write Analog Input Write Binary Input Write Analog Output Write Binary Output Write Internal Parameter Override Analog I...

Page 51: ...egister Numbers 01 Read Coil Status Read Discrete Outputs 00001 09999 02 Read Input Status Read Discrete Inputs 10001 19999 03 Read Holding Registers Read Holding Registers 40001 49999 04 Read Input R...

Page 52: ...TU MP Controller Signed Integer SINT 32768 32767 3 Read Holding Register 6 Preset Single Register 16 Preset Multiple Register Discrete Input DI 0 Off 1 On 2 Read Input Status Discrete Output DO 0 Off...

Page 53: ...management tool can design and configure the RTU MP prior to installation Contact your Carrier representative for this XIF file LonWorks is an open protocol that requires the use Echelon s Neuron mic...

Page 54: ......

Page 55: ...s table 4 J Johnson N2 5 9 23 45 L LonWorks 5 10 24 49 LonWorks Option Card 10 M Modbus 5 7 23 47 N Network Points List 26 S Sequence of operation Cooling 15 Dehumidification 18 Demand limiting 19 Eco...

Page 56: ......

Page 57: ......

Page 58: ...RTU MP Controller 54 CARRIER CORPORATION 2011 A member of the United Technologies Corporation family Stock symbol UTX Catalog No 48 50H T 1SB 1 27 2011...

Reviews: