background image

Switch B - Select Smart or Normal Setback Recovery

Selects between normal and smart recovery from setback. Normal
recovery changes to the new set point at the programmed time.
Smart recovery, which is active in heating mode only, starts earlier
and adjusts the set point slowly so that room temperature will
arrive at the programmed temperature at the programmed time.
TO SET:
OFF—for smart recovery. This is the factory default.
ON—for normal recovery.

Switch C - Select Enable/Disable of Low-Ambient Cooling

Use to allow or prevent cooling operation below an outdoor
temperature of 55°F. Prevention of cooling below 55°F adds to
compressor reliability. If outdoor temperature sensor fails or is
disconnected, cooling is allowed regardless of switch setting.
TO SET:
OFF—cooling is disabled at outdoor temperatures below 55°F.
ON—cooling is enabled at outdoor temperatures below 55°F.

Switch D - Select Single-Speed or 2-Speed HP

Use this switch to tell dual fuel thermostat whether it is controlling
a single- or 2-speed HP. It must be set properly.
TO SET:
OFF—for single-speed HP.
ON—for 2-speed HP.

Step 3—Install Thermostat

Before installing thermostat, turn off all power to unit. There
may be more than 1 power disconnect. Electrical shock can
cause personal injury or death.

1. Turn OFF all power to unit.

2. If an existing thermostat is being replaced:

a. Remove existing thermostat from wall.

b. Disconnect wires from existing thermostat, 1 at a time. Be

careful not to allow wires to fall back into the wall.

c. As each wire is disconnected, record wire color and

terminal marking.

d. Discard or recycle old thermostat.

NOTE:

Mercury is a hazardous waste and MUST be disposed of

properly.

3. Open thermostat rear door (mounting base) to expose mount-

ing holes. The base can be removed to simplify mounting.
Snap apart carefully at hinge to separate mounting base from
remainder of thermostat.

4. Route thermostat wires through large hole in mounting base.

Level mounting base against wall (for aesthetic value
only—thermostat need not be leveled for proper operation)
and mark wall through 2 mounting holes.

5. Drill two 3/16-in. mounting holes in wall where marked.

6. Secure mounting base to wall with 2 screws and anchors

provided, (additional anchoring holes available for more
secure mounting if needed) making sure all wires extend
through hole in mounting base.

7. Adjust length and routing of each wire to reach proper

terminal and connector block on mounting base with 1/4 in. of
extra wire. Strip only 1/4 in. of insulation from each wire to
prevent adjacent wires from shorting together when con-
nected.

8. Match and connect equipment wires to proper terminals of the

connector blocks. (See Fig. 2 through 9.) Both R and C must
be connected for proper thermostat operation.

Improper wiring or installation may damage the thermostat.
Check to make sure wiring is correct before proceeding with
installation or turning on unit.

9. Push any excess wire into wall and against mounting base.

Seal hole in wall to prevent air leaks. Leaks can affect
operation.

10. Snap hinge back together.

11. Close thermostat assembly making sure pins on back of circuit

board align with sockets in connector.

12. If this is a replacement installation, be sure to remove the

interface control which may have been used to interface a
standard thermostat to a dual fuel installation. All the wires
(with the exception of the outdoor sensor S1 and S2 wires)
from the thermostat go directly to the furnace. The interface
control must be removed and not used.

13. Turn ON power to unit.

On power up, display shows dF or d2 for a few seconds to indicate
that it is a dual fuel thermostat. (See page 11.)

Step 4—Set Thermostat Configuration

Configuration options, like DIP switch settings, are intended to be
selected at installation and normally are not modified by the
homeowner. These options are not discussed in the Homeowner’s
Manual and therefore must be selected as part of the installation.
A special procedure allows entry into the configuration mode.
While in the configuration mode, 7 selections can be made. A
description of each of these and how to use the configuration mode
follows.

CONFIGURATION OPTIONS—SUMMARY:

Option 01—Anticipator adjustment

Option 02—Clean filter timer adjustments

Option 03—Fahrenheit or Celsius operation

Option 04—07—Not applicable

Option 08—Auxiliary heat lockout setting

Option 09—10—Not applicable

Option 11—Balance point setting

Option 12—Not applicable

Option 13—Room temperature offset adjustment

Option 14—Not applicable

Option 15—Enable AUTO mode

TO ENTER THE CONFIGURATION MODE:

Press and hold FAN button for approximately 10 sec until COOL
set point display indicates a flashing 01. The thermostat is now in
the configuration mode. It will automatically exit this mode if no
button is pressed for 3 minutes. Pressing END button will exit the
configuration mode immediately.

WHILE IN THE CONFIGURATION MODE:

The upper small (COOL set point) display indicates the selected
option number and the large display indicates the selection made
within that option. One of these will be flashing. The up and down
buttons are used both to move between the available options and to
make selection for each option. When the option number (small
display) is flashing, the up and down buttons adjust it, moving
between the available option numbers. After the desired option
number has been selected, press SET TIME/TEMP button once.
The large disply will now flash, indicating that the up and down
buttons now control the available choices within that option. Each

4

Summary of Contents for Programmable Dual Fuel Thermostats

Page 1: ...ettings per 24 hour period for 7 independent days may be programmed Batteries are not required during a power interruption the internal memory stores programs for an unlimited time and the clock continues to run for at least 72 hrs SYSTEM CONSIDERATIONS The dual fuel thermostat is designed to be used only in HP furnace installations It replaces a conventional 2 stage HP thermostat and a HP furnace...

Page 2: ...ing The temperature range is 5 55 F When the outdoor temperature is above the auxiliary heat lockout setting the heat pump will become the primary source and the gas furnace cannot come on except in defrost or emergency heat mode The auxiliary heat lockout setting can never be set below the balance point setting and likewise the balance point can never be set above the auxiliary heat lockout setti...

Page 3: ...lied with the unit and must be installed Plan installation so that 2 wires can be run from the thermostat to an outdoor location preferably on the north side of the house or refer to Installation Instructions included with the outdoor temperature sensor for simplified connection Sensor can be mounted to outdoor unit and existing control wires may be used for its connection Details are provided in ...

Page 4: ...s See Fig 2 through 9 Both R and C must be connected for proper thermostat operation Improper wiring or installation may damage the thermostat Check to make sure wiring is correct before proceeding with installation or turning on unit 9 Push any excess wire into wall and against mounting base Seal hole in wall to prevent air leaks Leaks can affect operation 10 Snap hinge back together 11 Close the...

Page 5: ...gain to flash upper small display for selection of another option or press END to exit the configuration mode Option 8 Auxiliary Heat Lockout Setting This option allows selection of an outdoor temperature of 5 through 55 F in 5 steps or equivalent values in C or OF off Furnace is prevented from operating for outdoor temperatures above the selected temperature If OF off is selected furnace operatio...

Page 6: ...ater due to a staging timer which requires 15 minutes of low before high comes on The UP and FAN buttons cannot be used to defeat this timer This timer can be defeated by reducing the set point to more than 5 below room temperature bringing on a high speed demand within 5 seconds Remember 2 speed units have a 1 minute off time between lo and high speed so the thermostat s demand will not show imme...

Page 7: ... The FAN button may be used to select between AUTO fan on only with equipment and ON fan on continuously fan modes Step 7 Checklist 1 Put away tools and instruments and clean up debris 2 Review Homeowner s Guide with owner 3 Leave literature packet with owner 4 Fill out and return survey card Table 4 Dual Fuel Thermostat Quick Reference THERMOSTAT OUTPUTS Outdoor Unit Set DIP Switch D 24v Hot Comm...

Page 8: ... notes 1 2 3 4 and 9 SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF OFF OFF Fig 5 Two Stage Furnace with 2 Speed Heat Pump A98563 O W2 Y1 W2 W W1 G R R G DUAL FUEL THERMOSTAT TWO STAGE FURNACE TWO SPEED HEAT PUMP W W1 C Y2 W2 O Y1 W3 C B L S1 S2 R Y Y2 C HUM W2 HEAT STAGE 3 FURNACE HEAT COOL STAGE 2 COMPRESSOR HI HEAT COOL STAGE 1 COMPRESSOR LO RVS COOLING FAN 24 VAC HOT 24 VAC COM N A RVS SENSI...

Page 9: ...GS ON A B C D OFF OFF OFF OFF FURNACE BOARD O Y1 VARIABLE SPEED 80 NON CONDENSING FURNACE Fig 9 Variable Speed Furnace with 2 Speed Heat Pump A98446 O W2 Y1 W2 W W1 G R R G DUAL FUEL THERMOSTAT VARIABLE SPEED CONDENSING FURNACE TWO SPEED HEAT PUMP W W1 C Y2 W2 O Y1 W3 C B L S1 S2 R C HUM W2 HEAT STAGE 3 FURNACE HEAT COOL STAGE 2 COMPRESSOR HI HEAT COOL STAGE 1 COMPRESSOR LO RVS COOLING FAN 24 VAC ...

Page 10: ...ot select the FURNACE INTERFACE or BALANCE POINT option on the 2 speed heat pump control board This is controlled internally by the Dual Fuel Thermostat 7 As an option lock the furnace into low fire operation and let Y1 W2 control high fire operation Refer to indoor equipment Installation Instructions for proper setup 8 Furnace must control its own second stage heat operation via furnace control a...

Page 11: ...imum brownout level all outputs are turned off and the display indicates E2 If the AC line voltage disappears completely the display will immediately go blank E3 If thermostat cannot properly read outdoor temperature E3 will alternate with room temperature on the room temperature display and the outdoor temperature will read 2 dashes E6 If defrost timer continues for longer than 15 minutes E6 will...

Page 12: ...ctory default 2 3 Fahrenheit or Celsius F or C factory default F 4 7 N A 8 Auxiliary Heat Lockout Off or 5 55 F factory default Off 9 10 N A 11 Balance Point Temperature Off or 5 55 F factory default 40 12 N A 13 Room Temperature Offset 5 to 5 factory default 0 14 N A 15 Enable Auto Mode Off or On factory default On Mon Tue Wed Thu Fri Sat Sun TIME HEAT COOL TIME HEAT COOL TIME HEAT COOL TIME HEAT...

Reviews: