background image

APPLICATION

The dual fuel thermostat is designed for the following applications:

1-stage cool, 2-stage heat: 1-speed HP with 1-stage furnace
1-stage cool, 3-stage heat: 1-speed HP with 2-stage furnace
2-stage cool, 3-stage heat: 2-speed HP with 1-stage furnace
2-stage cool, 4-stage heat: 2-speed HP with 2-stage furnace*

*This combination must use furnace algorithm to control furnace
staging.

Balance Point Temperature

The "balance point" temperature is a setting which affects the
operation of the heating mode. This is a field-selected input
temperature (range 5-55°F) where the dual fuel thermostat will
monitor outdoor air temperature and decide whether to enable or
disable the heat pump.

If the outdoor temperature is above the "balance point," the heat
pump will energize first to try to satisfy the indoor temperature
demand. If the heat pump does not make a sufficient improvement
within a reasonable time period (i.e. 15 minutes), then the gas
furnace will come on to satisfy the indoor temperature demand. If
the outdoor temperature is below the "balance point," the heat
pump will not be allowed to operate (i.e. locked out), and the gas
furnace will be used to satisfy the indoor temperature.

There are three separate concepts which are related to selecting the
final "balance point" temperature. Read each of the following
carefully to determine the best "balance point" in a dual fuel
installation:

Capacity Balance Temperature:

This is the point where the heat pump cannot provide sufficient
capacity to keep up with the indoor temperature demand because
of declining outdoor temperature. At or below this point, the
furnace is needed to maintain proper indoor temperature.

Economic Balance Temperature:

Above this point, the heat pump is the most cost efficient to
operate, and below this point, the furnace is the most cost efficient
to operate. This can be somewhat complicated to determine and it
involves knowing the cost of gas and electricity, as well as the
efficiency of the furnace and heat pump. For the most economical
operation, the heat pump should operate above this temperature
(assuming it has sufficient capacity), and the furnace should
operate below this temperature.

Comfort Balance Temperature:

When the heat pump is operating below this point, the indoor
supply air feels uncomfortable (i.e. too cool). This is purely
subjective and will depend on the homeowner’s idea of comfort.
Below this temperature, the gas furnace should operate in order to
satisfy the desire for indoor comfort.

Auxiliary Heat Lockout Setting

The "auxiliary heat lockout" setting is an optional lockout feature.
This is in addition to the "balance point." The purpose of this
feature is to lock out the gas furnace whenever the outdoor
temperature is above the selected setting. The temperature range is
5-55°F. When the outdoor temperature is above the "auxiliary heat
lockout" setting, the heat pump will become the primary source,
and the gas furnace cannot come on (except in defrost or
emergency heat mode).

The "auxiliary heat lockout" setting can never be set below the
"balance point" setting, and likewise, the "balance point" can never
be set above the "auxiliary heat lockout" setting. The range of each
of these is from 5-55°F (or equivalent values in Celsius), or they
can be turned off. When off, they do not limit the equipment
operation. If the "auxiliary heat lockout" setting is moved down, it

will "push" the "balance point" so the two settings do not overlap.
Likewise, moving up the "balance point" will push the "auxiliary
heat lockout" setting.

When the two settings are the same, the system views this as a
single outdoor "balance point" temperature, and the heat pump is
used for above (warmer outdoor temperatures) and the furnace for
below (colder outdoor temperatures.)

DESCRIPTION OF OPERATION

Cooling Operation—Single Speed

HP cooling:
O/W2 energizes reversing valve to select cooling operation.
G energizes furnace blower.
Y/Y2 energizes compressor and selects high blower speed at
furnace.
When cooling demand is satisfied, G and Y/Y2 are de-energized.
O/W2 will remain on to minimize cycling of reversing valve. It
will turn off only when a call for heat occurs.

Cooling Operation—Two Speed

Low-speed HP cooling:
O/W2 energizes reversing valve to select cooling operation.
G energizes furnace blower.
Y1/W2 energizes compressor at low speed and may determine
furnace blower speed.

High-speed HP cooling:
Y/Y2 is added to low-speed cooling call to operate compressor at
high speed and increase blower speed.

Heating Operation—Single-Speed HP

HP heating:
O/W2 remains off to select heating operation.
G turns on furnace blower.
Y/Y2 energizes compressor and increases furnace blower speed.

Heating Operation—Two-Speed HP

Low-Speed HP heating:
O/W2 remains off to select heating operation.
G turns on furnace blower.
Y1/W2 turns on compressor at low speed and may also adjust
blower speed for low-speed HP operation.

High-Speed HP heating:
Y/Y2 is added to low-speed HP heating call to operate compressor
at high speed and adjust blower for high-speed HP operation.

Heating Operation—Single-Stage Furnace

W/W1 causes furnace to operate. Furnace controls its own blower
at heating speed.

Heating Operation—Two-Stage Furnace—Thermostat Control

Low heat:
W/W1 causes furnace to operate at low heat. Furnace controls its
own blower at low heating speed.

High heat:
Y1/W2 is added to low-heat heating call to operate furnace in
high-heat mode. Furnace controls its own blower at high heating
speed.

Heating Operation—Two-Stage Furnace—Algorithm Control

W/W1 causes furnace to operate. Based on amount of time it is
required to be on, it determines when to operate at low heat and
when to operate at high heat. It controls its own blower at proper
speed.

2

Summary of Contents for Programmable Dual Fuel Thermostats

Page 1: ...ettings per 24 hour period for 7 independent days may be programmed Batteries are not required during a power interruption the internal memory stores programs for an unlimited time and the clock continues to run for at least 72 hrs SYSTEM CONSIDERATIONS The dual fuel thermostat is designed to be used only in HP furnace installations It replaces a conventional 2 stage HP thermostat and a HP furnace...

Page 2: ...ing The temperature range is 5 55 F When the outdoor temperature is above the auxiliary heat lockout setting the heat pump will become the primary source and the gas furnace cannot come on except in defrost or emergency heat mode The auxiliary heat lockout setting can never be set below the balance point setting and likewise the balance point can never be set above the auxiliary heat lockout setti...

Page 3: ...lied with the unit and must be installed Plan installation so that 2 wires can be run from the thermostat to an outdoor location preferably on the north side of the house or refer to Installation Instructions included with the outdoor temperature sensor for simplified connection Sensor can be mounted to outdoor unit and existing control wires may be used for its connection Details are provided in ...

Page 4: ...s See Fig 2 through 9 Both R and C must be connected for proper thermostat operation Improper wiring or installation may damage the thermostat Check to make sure wiring is correct before proceeding with installation or turning on unit 9 Push any excess wire into wall and against mounting base Seal hole in wall to prevent air leaks Leaks can affect operation 10 Snap hinge back together 11 Close the...

Page 5: ...gain to flash upper small display for selection of another option or press END to exit the configuration mode Option 8 Auxiliary Heat Lockout Setting This option allows selection of an outdoor temperature of 5 through 55 F in 5 steps or equivalent values in C or OF off Furnace is prevented from operating for outdoor temperatures above the selected temperature If OF off is selected furnace operatio...

Page 6: ...ater due to a staging timer which requires 15 minutes of low before high comes on The UP and FAN buttons cannot be used to defeat this timer This timer can be defeated by reducing the set point to more than 5 below room temperature bringing on a high speed demand within 5 seconds Remember 2 speed units have a 1 minute off time between lo and high speed so the thermostat s demand will not show imme...

Page 7: ... The FAN button may be used to select between AUTO fan on only with equipment and ON fan on continuously fan modes Step 7 Checklist 1 Put away tools and instruments and clean up debris 2 Review Homeowner s Guide with owner 3 Leave literature packet with owner 4 Fill out and return survey card Table 4 Dual Fuel Thermostat Quick Reference THERMOSTAT OUTPUTS Outdoor Unit Set DIP Switch D 24v Hot Comm...

Page 8: ... notes 1 2 3 4 and 9 SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF OFF OFF Fig 5 Two Stage Furnace with 2 Speed Heat Pump A98563 O W2 Y1 W2 W W1 G R R G DUAL FUEL THERMOSTAT TWO STAGE FURNACE TWO SPEED HEAT PUMP W W1 C Y2 W2 O Y1 W3 C B L S1 S2 R Y Y2 C HUM W2 HEAT STAGE 3 FURNACE HEAT COOL STAGE 2 COMPRESSOR HI HEAT COOL STAGE 1 COMPRESSOR LO RVS COOLING FAN 24 VAC HOT 24 VAC COM N A RVS SENSI...

Page 9: ...GS ON A B C D OFF OFF OFF OFF FURNACE BOARD O Y1 VARIABLE SPEED 80 NON CONDENSING FURNACE Fig 9 Variable Speed Furnace with 2 Speed Heat Pump A98446 O W2 Y1 W2 W W1 G R R G DUAL FUEL THERMOSTAT VARIABLE SPEED CONDENSING FURNACE TWO SPEED HEAT PUMP W W1 C Y2 W2 O Y1 W3 C B L S1 S2 R C HUM W2 HEAT STAGE 3 FURNACE HEAT COOL STAGE 2 COMPRESSOR HI HEAT COOL STAGE 1 COMPRESSOR LO RVS COOLING FAN 24 VAC ...

Page 10: ...ot select the FURNACE INTERFACE or BALANCE POINT option on the 2 speed heat pump control board This is controlled internally by the Dual Fuel Thermostat 7 As an option lock the furnace into low fire operation and let Y1 W2 control high fire operation Refer to indoor equipment Installation Instructions for proper setup 8 Furnace must control its own second stage heat operation via furnace control a...

Page 11: ...imum brownout level all outputs are turned off and the display indicates E2 If the AC line voltage disappears completely the display will immediately go blank E3 If thermostat cannot properly read outdoor temperature E3 will alternate with room temperature on the room temperature display and the outdoor temperature will read 2 dashes E6 If defrost timer continues for longer than 15 minutes E6 will...

Page 12: ...ctory default 2 3 Fahrenheit or Celsius F or C factory default F 4 7 N A 8 Auxiliary Heat Lockout Off or 5 55 F factory default Off 9 10 N A 11 Balance Point Temperature Off or 5 55 F factory default 40 12 N A 13 Room Temperature Offset 5 to 5 factory default 0 14 N A 15 Enable Auto Mode Off or On factory default On Mon Tue Wed Thu Fri Sat Sun TIME HEAT COOL TIME HEAT COOL TIME HEAT COOL TIME HEAT...

Reviews: