background image

Defrost Operation

A unique feature of this thermostat is that a defrost cycle, once
started, will always be completed. This is true even if thermostat is
satisfied during defrost. The result is that a heating cycle never
begins with an uncompleted defrost and its associated "cold blow".

During operation of HP in heating mode, HP itself determines
when a defrost is necessary. It initiates defrost by energizing its O
and W wires. The signal on the O wire switches HP from heating
to cooling mode and W signal starts furnace. Thermostat monitors
this action by sensing the signal (which it did not create) on the O
line. It responds by turning on its W outputs (both if 2-stage
furnace) to hold furnace on high heat. At completion of defrost,
indicated by removal of signal from HP on O wire, thermostat does
1 of 2 things. If it is satisfied, it turns off all Y, G, and W outputs
which results in all equipment off. If not satisfied, it will turn off
Y and G, leaving W on until it becomes satisfied. In this way it
assures that furnace will be used to satisfy a heat demand existing
after a defrost cycle is completed.

Emergency Heat

If EHEAT mode is selected at thermostat, all heating will be done
by furnace.

Continuous Fan

If FAN ON is selected, thermostat energizes G terminal, which
causes fan to operate when both heating and cooling are off.

Staging Sequence—Heating

Depending on whether HP is single or 2 speed and whether furnace
is single or 2 stage, the staging of thermostat outputs with
increasing demand varies. Table 1 shows the heating staging
sequence for all 4 possible combinations of single- and multi-stage
equipment. Note that thermostat itself has a maximum of 3 heating
stages. Note also that at outdoor temperatures below selected
balance point setting no HP operation is allowed. As discussed
earlier, once furnace is turned on, it remains on to satisfy all
demand.

A "freeze protect" feature is built into the dual fuel thermostat. If
indoor temperature sensor fails, and thermostat is in HEAT or
AUTO mode, heat will be cycled when outdoor temperature is
below 50°F. The amount of heat supplied will increase as outdoor
temperature decreases, keeping structure from freezing.

INSTALLATION CONSIDERATIONS

POWER

Note that this control does not require batteries and is not "power
stealing". It does require 24 vac (R and C terminals) of the
low-voltage transformer to be connected to it for proper operation.
It will not operate without these 2 connections.

OUTDOOR TEMPERATURE SENSING

The dual fuel thermostat uses outdoor temperature to determine
whether the furnace or the heat pump is allowed to operate. The
outdoor temperature sensor, Part No. TSTATXXSEN01-B, is
supplied with the unit and must be installed. Plan installation so

that 2 wires can be run from the thermostat to an outdoor location,
preferably on the north side of the house or refer to Installation
Instructions included with the outdoor temperature sensor for
simplified connection. Sensor can be mounted to outdoor unit and
existing control wires may be used for its connection. Details are
provided in the sensor Installation Instructions.

INSTALLATION

Step 1—Thermostat Location

Thermostat should be mounted:

Approximately 5 ft (1.5m) from floor.

Close to or in a frequently used room, preferably on an inside
partitioning wall.

On a section of wall without pipes or duct work.

In a location where the outdoor temperature sensor wires can be
routed to thermostat location. It is acceptable to use 2 separate
wires in thermostat cable to connect outdoor sensor. These
wires may be connected at furnace to another pair continuing to
outdoor heat pump. The outdoor sensor may then be mounted
and connected in vicinity of heat pump, but be sure it is not
located in direct sunlight.

Thermostat should NOT be mounted:

Close to a window, on an outside wall, or next to a door leading
to the outside.

Exposed to direct light and heat from a lamp, sun, fireplace, or
other temperature-radiating object which may cause a false
reading.

Close to or in direct airflow from supply registers and return-air
grilles.

In areas with poor air circulation, such as behind a door or in
an alcove.

Step 2—Set DIP Switches

There is a 4 section DIP switch within the thermostat which must
be properly set by the installer. It is easiest to set these 4 switches
before the thermostat is mounted on the wall, so STOP and
complete the following steps:

1. Open hinged thermostat cover.

2. Remove cover completely by snapping it apart at hinge.

3. Open thermostat by pressing back half of the right end of

plastic case inward while, at the same time, pulling front and
back halves apart at the right end. The 2 halves will swing
apart.

4. Snap hinge apart to completely separate the 2 halves.

5. Switches are located in upper right corner of circuit board. to

change switch position, use corner of a small screwdriver to
slide switch to opposite position.

6. After switches have been set, do not reassemble the 2 halves.

The rear plastic will be first mounted to wall.

Switch A - Not Used in Dual Fuel Thermostats

This switch must be in OFF position in all dual fuel applications.
DO NOT turn ON.

Table 1—Heating Stages

WIRING DIAGRAM

SYSTEM TYPE

BALANCE POINT

SETTING

STAGE 1

STAGE 2

STAGE 3

Fig. 2

1-speed HP

1-stage furnace

Above

HP

Furnace

Below

Furnace

Fig. 4, 6, 8

1-speed HP

2-stage furnace

Above

HP

Furnace Lo

Furnace Hi

Below

Furnace Lo

Furnace Hi

Fig. 3

2-speed HP

1-stage furnace

Above

HP Lo

HP Hi

Furnace

Below

Furnace

Fig. 5, 7, 9

2-speed HP

2-stage furnace

Above

HP Lo

HP Hi

Furnace Lo or Hi

Below

Furnace Lo or Hi

3

Summary of Contents for Programmable Dual Fuel Thermostats

Page 1: ...ettings per 24 hour period for 7 independent days may be programmed Batteries are not required during a power interruption the internal memory stores programs for an unlimited time and the clock continues to run for at least 72 hrs SYSTEM CONSIDERATIONS The dual fuel thermostat is designed to be used only in HP furnace installations It replaces a conventional 2 stage HP thermostat and a HP furnace...

Page 2: ...ing The temperature range is 5 55 F When the outdoor temperature is above the auxiliary heat lockout setting the heat pump will become the primary source and the gas furnace cannot come on except in defrost or emergency heat mode The auxiliary heat lockout setting can never be set below the balance point setting and likewise the balance point can never be set above the auxiliary heat lockout setti...

Page 3: ...lied with the unit and must be installed Plan installation so that 2 wires can be run from the thermostat to an outdoor location preferably on the north side of the house or refer to Installation Instructions included with the outdoor temperature sensor for simplified connection Sensor can be mounted to outdoor unit and existing control wires may be used for its connection Details are provided in ...

Page 4: ...s See Fig 2 through 9 Both R and C must be connected for proper thermostat operation Improper wiring or installation may damage the thermostat Check to make sure wiring is correct before proceeding with installation or turning on unit 9 Push any excess wire into wall and against mounting base Seal hole in wall to prevent air leaks Leaks can affect operation 10 Snap hinge back together 11 Close the...

Page 5: ...gain to flash upper small display for selection of another option or press END to exit the configuration mode Option 8 Auxiliary Heat Lockout Setting This option allows selection of an outdoor temperature of 5 through 55 F in 5 steps or equivalent values in C or OF off Furnace is prevented from operating for outdoor temperatures above the selected temperature If OF off is selected furnace operatio...

Page 6: ...ater due to a staging timer which requires 15 minutes of low before high comes on The UP and FAN buttons cannot be used to defeat this timer This timer can be defeated by reducing the set point to more than 5 below room temperature bringing on a high speed demand within 5 seconds Remember 2 speed units have a 1 minute off time between lo and high speed so the thermostat s demand will not show imme...

Page 7: ... The FAN button may be used to select between AUTO fan on only with equipment and ON fan on continuously fan modes Step 7 Checklist 1 Put away tools and instruments and clean up debris 2 Review Homeowner s Guide with owner 3 Leave literature packet with owner 4 Fill out and return survey card Table 4 Dual Fuel Thermostat Quick Reference THERMOSTAT OUTPUTS Outdoor Unit Set DIP Switch D 24v Hot Comm...

Page 8: ... notes 1 2 3 4 and 9 SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF OFF OFF Fig 5 Two Stage Furnace with 2 Speed Heat Pump A98563 O W2 Y1 W2 W W1 G R R G DUAL FUEL THERMOSTAT TWO STAGE FURNACE TWO SPEED HEAT PUMP W W1 C Y2 W2 O Y1 W3 C B L S1 S2 R Y Y2 C HUM W2 HEAT STAGE 3 FURNACE HEAT COOL STAGE 2 COMPRESSOR HI HEAT COOL STAGE 1 COMPRESSOR LO RVS COOLING FAN 24 VAC HOT 24 VAC COM N A RVS SENSI...

Page 9: ...GS ON A B C D OFF OFF OFF OFF FURNACE BOARD O Y1 VARIABLE SPEED 80 NON CONDENSING FURNACE Fig 9 Variable Speed Furnace with 2 Speed Heat Pump A98446 O W2 Y1 W2 W W1 G R R G DUAL FUEL THERMOSTAT VARIABLE SPEED CONDENSING FURNACE TWO SPEED HEAT PUMP W W1 C Y2 W2 O Y1 W3 C B L S1 S2 R C HUM W2 HEAT STAGE 3 FURNACE HEAT COOL STAGE 2 COMPRESSOR HI HEAT COOL STAGE 1 COMPRESSOR LO RVS COOLING FAN 24 VAC ...

Page 10: ...ot select the FURNACE INTERFACE or BALANCE POINT option on the 2 speed heat pump control board This is controlled internally by the Dual Fuel Thermostat 7 As an option lock the furnace into low fire operation and let Y1 W2 control high fire operation Refer to indoor equipment Installation Instructions for proper setup 8 Furnace must control its own second stage heat operation via furnace control a...

Page 11: ...imum brownout level all outputs are turned off and the display indicates E2 If the AC line voltage disappears completely the display will immediately go blank E3 If thermostat cannot properly read outdoor temperature E3 will alternate with room temperature on the room temperature display and the outdoor temperature will read 2 dashes E6 If defrost timer continues for longer than 15 minutes E6 will...

Page 12: ...ctory default 2 3 Fahrenheit or Celsius F or C factory default F 4 7 N A 8 Auxiliary Heat Lockout Off or 5 55 F factory default Off 9 10 N A 11 Balance Point Temperature Off or 5 55 F factory default 40 12 N A 13 Room Temperature Offset 5 to 5 factory default 0 14 N A 15 Enable Auto Mode Off or On factory default On Mon Tue Wed Thu Fri Sat Sun TIME HEAT COOL TIME HEAT COOL TIME HEAT COOL TIME HEAT...

Reviews: