background image

press of SET TIME/TEMP button switches between the available
option (small display) and the available selections within each
option (large display).

CONFIGURATION OPTIONS—SELECTION:

Option 1—Anticipator Adjustment

This adjustment controls the sensitivity and cycle rate of the
thermostat. Higher numbers decrease the sensitivity and slow the
cycle rate. Lower numbers increase the sensitivity and cycle rate.
However, a limiting feature will not allow more than 4 cycles per
hour, regardless of setting. Anticipator values can range from 1 to
9. Factory default is 3. This default setting will provide optimum
performance in nearly all installations. Try it first. Do not change
setting unless there is evidence of need to do so.

Unlike conventional anticipators, this setting is not to be deter-
mined by current draw. There is not need to measure, know, or
compensate for current. There is also no droop with this thermo-
stat. Regardless of setting and the number of stages, both heating
and cooling will control to their respective set points.

TO ADJUST:

1. Enter configuration mode (if not already there). See above.

The upper small (COOL set point) display will be flashing 01.
If not, use up and down buttons to move it to 01.

2. Press SET TIME/TEMP button once to flash the current

selection of 1 through 9 on the large display. Factory default
is 3.

3. Use up and down buttons to move between the available

choices.

4. Press SET TIME/TEMP button again to flash the upper small

disply for selection of another option, or press END to exit the
configuration mode.

Option 2—Clean Filter Timer

Select hours of blower operation (heating, cooling, or fan) before
CLEAN FILTER icon is displayed. With OFF selected, icon will
never come on, disabling this feature. Time selection can be from
400 to 3600 hrs by selecting numbers 1 through 9. (Time is 400X
number selected.) Factory default is 2 (800 hrs). Recommended
selections

are:

disposable

filter—400

to

800

hrs,

media

filter—1200 to 1600 hrs, or electronic air cleaner—1600 to 2400
hrs of blower operation.

TO SELECT OR ADJUST:

1. Enter configuration mode if not already there. See above. Use

up and down buttons to make small (now flashing) display
indicate 02.

2. Press SET TIME/TEMP button once to flash current selection

of OF, or 1 through 9 on large display. Factory default is 2.

3. Use up and down buttons to move between the available

choices.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to exit
configuration mode.

Option 3—Fahrenheit or Celsius Operation

Select between Fahrenheit and Celsius operation. Factory default
is Fahrenheit.

TO SELECT:

1. Enter configuration mode if not already there. See above. Use

up and down buttons to make small (now flashing) display
indicate 03.

2. Press SET TIME/TEMP button once to flash current selection

of F or C. Factory default is F.

3. Use up and down buttons to move between C and F on large

display.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to exit
the configuration mode.

Option 8—Auxiliary Heat Lockout Setting

This option allows selection of an outdoor temperature of 5°
through 55°F in 5° steps (or equivalent values in C), or OF (off).
Furnace is prevented from operating for outdoor temperatures
above the selected temperature. If OF (off) is selected, furnace
operation is allowed at all outdoor temperatures. If selected,
emergency heat (EHEAT) overrides this feature. Factory default is
OF. This setting can only be equal to or above the setting choice
made for Option 11. Moving this setting lower may "push" Option
11 setting downward.

TO SELECT:

1. Enter configuration mode if not already there. See above. Use

up and down buttons to make small (now flashing) display
indicate 08.

2. Press SET TIME/TEMP button once to flash large display.

3. Use up and down buttons to move between 5, 10, 15, 20, 25,

30, 35, 40, 45, 50, 55, or OF on large display. Factory default
is OF. Remember, this may change setting for Option 11.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to exit
the configuration mode.

Option 11—Balance Point Setting

This option allows selection of an outdoor temperature of 5°
through 55°F in 5° steps (or equivalent values in C), or OF (off).
Heat pump is prevented from operating for outdoor temperatures
below selected temperature. If OF (off) is selected, heat pump
operation is allowed at all outdoor temperatures. Factory default is
OF. This setting can only be equal to or below the setting choice
made for Option 8. Moving this setting higher may "push" Option
8 setting upward.

TO SELECT:

1. Enter configuration mode if not already there. See above. Use

up and down buttons to make small (now flashing) display
indicate 11.

2. Press SET TIME/TEMP button once to flash large display.

3. Use up and down buttons to move between 5, 10, 15, 20, 25,

30, 35, 40, 45, 50, 55, or OF on large display. Factory default
is OF. Remember, this may change setting for Option 8.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to exit
configuration mode.

Option 13—Room Temperature Offset Adjustment

This option allows calibration (or deliberate miscalibration) of the
room temperature sensor. There are various reasons why home-
owners may want to have the displayed temperature adjusted to a
higher or lower value. The selected number is the number of
degrees, plus or minus, which will be added to the actual
temperature. The numbers can range between -5 and +5. Factory
default is 0. This adjusted value will be used as the actual
temperature for both the display and the control action. For
example, if 2 is selected. 72° actual will read 74°. If set point is 72°
then the room will control to an actual temperature of 70° which
will be displayed and acted upon as if it were 72°. The effect is that
a positive number selection will make the room temperature lower
and vice versa. The thermostat is calibrated within an accuracy of
plus or minus 1° when shipped from the factory, so this adjustment
will provide the best accuracy when set to 0.

5

Summary of Contents for Programmable Dual Fuel Thermostats

Page 1: ...ettings per 24 hour period for 7 independent days may be programmed Batteries are not required during a power interruption the internal memory stores programs for an unlimited time and the clock continues to run for at least 72 hrs SYSTEM CONSIDERATIONS The dual fuel thermostat is designed to be used only in HP furnace installations It replaces a conventional 2 stage HP thermostat and a HP furnace...

Page 2: ...ing The temperature range is 5 55 F When the outdoor temperature is above the auxiliary heat lockout setting the heat pump will become the primary source and the gas furnace cannot come on except in defrost or emergency heat mode The auxiliary heat lockout setting can never be set below the balance point setting and likewise the balance point can never be set above the auxiliary heat lockout setti...

Page 3: ...lied with the unit and must be installed Plan installation so that 2 wires can be run from the thermostat to an outdoor location preferably on the north side of the house or refer to Installation Instructions included with the outdoor temperature sensor for simplified connection Sensor can be mounted to outdoor unit and existing control wires may be used for its connection Details are provided in ...

Page 4: ...s See Fig 2 through 9 Both R and C must be connected for proper thermostat operation Improper wiring or installation may damage the thermostat Check to make sure wiring is correct before proceeding with installation or turning on unit 9 Push any excess wire into wall and against mounting base Seal hole in wall to prevent air leaks Leaks can affect operation 10 Snap hinge back together 11 Close the...

Page 5: ...gain to flash upper small display for selection of another option or press END to exit the configuration mode Option 8 Auxiliary Heat Lockout Setting This option allows selection of an outdoor temperature of 5 through 55 F in 5 steps or equivalent values in C or OF off Furnace is prevented from operating for outdoor temperatures above the selected temperature If OF off is selected furnace operatio...

Page 6: ...ater due to a staging timer which requires 15 minutes of low before high comes on The UP and FAN buttons cannot be used to defeat this timer This timer can be defeated by reducing the set point to more than 5 below room temperature bringing on a high speed demand within 5 seconds Remember 2 speed units have a 1 minute off time between lo and high speed so the thermostat s demand will not show imme...

Page 7: ... The FAN button may be used to select between AUTO fan on only with equipment and ON fan on continuously fan modes Step 7 Checklist 1 Put away tools and instruments and clean up debris 2 Review Homeowner s Guide with owner 3 Leave literature packet with owner 4 Fill out and return survey card Table 4 Dual Fuel Thermostat Quick Reference THERMOSTAT OUTPUTS Outdoor Unit Set DIP Switch D 24v Hot Comm...

Page 8: ... notes 1 2 3 4 and 9 SUGGESTED DIP SWITCH SETTINGS ON A B C D OFF OFF OFF OFF Fig 5 Two Stage Furnace with 2 Speed Heat Pump A98563 O W2 Y1 W2 W W1 G R R G DUAL FUEL THERMOSTAT TWO STAGE FURNACE TWO SPEED HEAT PUMP W W1 C Y2 W2 O Y1 W3 C B L S1 S2 R Y Y2 C HUM W2 HEAT STAGE 3 FURNACE HEAT COOL STAGE 2 COMPRESSOR HI HEAT COOL STAGE 1 COMPRESSOR LO RVS COOLING FAN 24 VAC HOT 24 VAC COM N A RVS SENSI...

Page 9: ...GS ON A B C D OFF OFF OFF OFF FURNACE BOARD O Y1 VARIABLE SPEED 80 NON CONDENSING FURNACE Fig 9 Variable Speed Furnace with 2 Speed Heat Pump A98446 O W2 Y1 W2 W W1 G R R G DUAL FUEL THERMOSTAT VARIABLE SPEED CONDENSING FURNACE TWO SPEED HEAT PUMP W W1 C Y2 W2 O Y1 W3 C B L S1 S2 R C HUM W2 HEAT STAGE 3 FURNACE HEAT COOL STAGE 2 COMPRESSOR HI HEAT COOL STAGE 1 COMPRESSOR LO RVS COOLING FAN 24 VAC ...

Page 10: ...ot select the FURNACE INTERFACE or BALANCE POINT option on the 2 speed heat pump control board This is controlled internally by the Dual Fuel Thermostat 7 As an option lock the furnace into low fire operation and let Y1 W2 control high fire operation Refer to indoor equipment Installation Instructions for proper setup 8 Furnace must control its own second stage heat operation via furnace control a...

Page 11: ...imum brownout level all outputs are turned off and the display indicates E2 If the AC line voltage disappears completely the display will immediately go blank E3 If thermostat cannot properly read outdoor temperature E3 will alternate with room temperature on the room temperature display and the outdoor temperature will read 2 dashes E6 If defrost timer continues for longer than 15 minutes E6 will...

Page 12: ...ctory default 2 3 Fahrenheit or Celsius F or C factory default F 4 7 N A 8 Auxiliary Heat Lockout Off or 5 55 F factory default Off 9 10 N A 11 Balance Point Temperature Off or 5 55 F factory default 40 12 N A 13 Room Temperature Offset 5 to 5 factory default 0 14 N A 15 Enable Auto Mode Off or On factory default On Mon Tue Wed Thu Fri Sat Sun TIME HEAT COOL TIME HEAT COOL TIME HEAT COOL TIME HEAT...

Reviews: