background image

Warnings(for using R290/R32 refrigerant only)

Extreme care shall be taken not to overfill the refrigeration 

system. Prior to recharging the system it shall be pressure 

tested with OFN. The system shall be leak tested on 

completion of charging but prior to commissioning. A follow 

up leak test shall be carried out prior to leaving the site.

14.Decommissioning

Before carrying out this procedure, it is essential that the 

technician is completely familiar with the equipment and all 

its detail. It is recommended good practice that all 

refrigerants are recovered safely. Prior to the task being 

carried out, an oil and refrigerant sample shall be taken in 

case analysis is required prior to re-use of reclaimed 

refrigerant. It is essential that electrical power is available 

before the task is commenced. 

a) Become familiar with the equipment and its operation.  

b) Isolate system electrically. 

c) Before attempting the procedure ensure that:

 Mechanical handling equipment is available, if required, for 

 handling refrigerant cylinders; 

 All personal protective equipment is available and being 

 used correctly; The recovery process is supervised at all 

 times by a competent person; 

 Recovery equipment and cylinders conform to the 

 appropriate standards. 

d) Pump down refrigerant system, if possible. 

e) If a vacuum is not possible, make a manifold so that 

  refrigerant can be removed from various parts of the 

 system. 

f)  Make sure that cylinder is situated on the scales before 

 recovery takes place. 

g) Start the recovery machine and operate in accordance 

 with manufacturer's instructions. 

h) Do not overfill cylinders. (No more than 80 % volume 

 liquid charge). 

i)  Do not exceed the maximum working pressure of the 

 cylinder, even temporarily. 

j)  When the cylinders have been filled correctly and the 

 process completed, make sure that the cylinders and the 

 equipment are removed from site promptly and all 

 isolation valves on the equipment are closed off. 

k) Recovered refrigerant shall not be charged into another 

 refrigeration  system unless it has been cleaned and 

 checked.

15.Labelling

Equipment shall be labelled stating that it has been 

de-commissioned and emptied of refrigerant. The label 

shall be dated and signed. Ensure that there are labels 

on the equipment stating the equipment contains 

flammable refrigerant.

16.Recovery

When removing refrigerant from a system, either for 

servicing or decommissioning, it is recommended good 

practice that all refrigerants are removed safely. 

When transferring refrigerant into cylinders, ensure that only 

appropriate refrigerant recovery cylinders are employed. 

Ensure that the correct number of cylinders for holding the 

total system charge is available. All cylinders to be used are 

designated for the recovered refrigerant and labelled for that 

refrigerant (i.e. special cylinders for the recovery of 

refrigerant). Cylinders shall be complete with pressure relief 

valve and associated shut-off valves in good working order. 

Empty recovery cylinders are evacuated and, if possible, 

cooled before recovery occurs. 

The recovery equipment shall be in good working order with 

a set of instructions concerning the equipment that is at hand 

and shall be suitable for the recovery of flammable 

refrigerants. In addition, a set of calibrated weighing scales 

shall be available and in good working order. Hoses shall 

be complete with leak-free disconnect couplings and in good 

condition. Before using the recovery machine, check that it 

is in satisfactory working order, has been properly 

maintained and that any associated electrical components 

are sealed to prevent ignition in the event of a refrigerant 

release. Consult manufacturer if in doubt.

The recovered refrigerant shall be returned to the refrigerant 

supplier in the correct recovery cylinder, and the relevant 

Waste Transfer Note arranged. Do not mix refrigerants in 

recovery units and especially not in cylinders. If compressors 

or compressor oils are to be removed, ensure that they 

have been evacuated to an acceptable level to make 

certain that flammable refrigerant does not remain within 

the lubricant. The evacuation process shall be carried out 

prior to returning the compressor to the suppliers. Only 

electric heating to the compressor body shall be employed 

to accelerate this process. When oil is drained from a 

system, it shall be carried out safely.

Note About Fluorinated Gasses

-Fluorinated greenhouse gases are contained in 

 hermetically sealed equipment. For specific information 

 on the type, the amount and the CO

2

 equivalent in tonnes 

 of the fluorinated greenhouse gas(on some models), 

 please refer to the relevant label on the unit itself. 

-Installation, service, maintenance and repair of this unit 

 must be performed by a certified technician.

-Product uninstallation and recycling must be performed 

 by a certified technician.

  

7

Summary of Contents for MPPD-10CRN7-QC1G1

Page 1: ...unit Make sure to save this manual for future reference This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installation manual of indoor unit Ple...

Page 2: ...fety Precauti ons Cautions Warnings for using R290 R32 refrigerant only Preparations Install ation Operati on Maintenance Faults Diagnosis Design and Compliance Notes Sociabl e Remark 2 3 4 8 9 12 15...

Page 3: ...ause electrical components to short circuit DO NOT install the unit in a location that may be exposed to combustible gas as this could cause re The unit has wheels to facilitate moving Make sure not t...

Page 4: ...raffic area and where it will not be tripped over Do not operate unit with a damaged cord plug power fuse or circuit breaker Discard unit or return to an authorized service facility for examination an...

Page 5: ...ce or burn Be aware that the refrigerants may not contain an odour Appliance MPPDB 12CRN7 QB6G1 should be installed operated and stored in a room with a floor area larger than 11 m Appliance MPPDB 10C...

Page 6: ...ll possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which flammable refrigerant can possi...

Page 7: ...may not be adequate or Warnings for using R290 R32 refrigerant only 6 may need re calibration Detection equipment shall be calibrated in a refrigerant free area Ensure that the detector is not a pote...

Page 8: ...When removing refrigerant from a system either for servicing or decommissioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders e...

Page 9: ...outlet lower air filter lower air intake drain outlet 8 f ro n t rear control panel handle both sides horizontal louver blade swing automatically Caster power plug socket power cord buckle vent contro...

Page 10: ...on location should meet the following requirements Make sure that you install your unit on an even surface to minimize noise and vibration The unit must be installed near a grounded plug and the Colle...

Page 11: ...use the bolt to fasten the window sliders once they are adjusted to the proper length 3 For some models if the length of the window requires three window sliders optional use two bolts to fasten the...

Page 12: ...the exhaust system works properly All the illustrations in this manual are for explanation purpose only Your air conditioner may be slightly different The actual shape shall prevail max 120cm or 47 in...

Page 13: ...COOL mode light FAN mode light DRY mode light AUTO mode light WIRELESS light NOTE Some features ION FOLLOW ME HEAT WIRELESS etc are optional ION is not applicable for R32 R290 units Operation 12 NOTE...

Page 14: ...tion press and hold the swing button for 3 seconds to initiate the Wireless connection mode The LED DISPLAY shows AP to indicate you can set Wireless connection If connection router is successful with...

Page 15: ...the UP or DOWN button to change the Auto time by 0 5 hour increments up to 10 hours then at 1 hour increments up to 24 hours The control will count down the time remaining until start The system will...

Page 16: ...flow smoothly See Figs with Do never let it up See Figs with When the continuous drain hose is not used ensure that the corresponding drain plug and knob are installed firmly to prevent leakage X Mai...

Page 17: ...ter according to instructions This sound is caused by the ow of refrigerant inside the unit This is normal Maintenance Tips Clean the Unit Store the unit when not in use Be sure to clean the air lter...

Page 18: ...wall exhaust adaptor A as shown in the Installation section of this manual Unit Temperature Range NOTE To be in compliance EN 61000 3 11 the product MPPDB 12HRN7 QB6G1 shall be connected only to a su...

Page 19: ...cipality has established collection systems where electronic waste can be disposed of at least free of charge to the user B When buying a new product the retailer will take back the old product at lea...

Reviews: