background image

3

Table 2C — Motormaster® V Control Package Contents — 48/50A2,A3,A4,A5060 MCHX Units (R-410A)

Table 3 — Motormaster V Control Package Usage

            LEGEND
MCHX — Microchannel Heat Exchanger
RTPF  — Round Tube Plate Fin Heat Exchanger

Pre-Installation — 

Inspect the contents of this accessory

package before installing. File a claim with the shipper if there

is shipping damage or if a part is missing.

INSTALLATION

Step 1 — Install Field-Fabricated Wind Baffles

In areas with prevailing winds of more than 5 mph and

where temperatures drop below 32 F, wind baffles must be field

fabricated to ensure proper cooling cycle operation at

low-ambient temperatures with Motormaster V controls, not

needed on size 060 units with MCHX (Microchannel heat ex-

changers). See Fig. 2 for baffle details. Use 20-gage (1 mm) gal-

vanized sheet metal, or similar corrosion-resistant material for

the baffles. Use field-supplied screws to attach baffles to unit.

Screws should be 

1

/

4

-in. (6.3 mm) diameter or larger. Screws

should not be more than 

1

/

inch in length. Drill required screw

holes for mounting baffles.

ITEM

CRLOWAMB024A00

CRLOWAMB025A00

CRLOWAMB026A00

Controller, 230 V 2 Hp

HR46TN001 (2)

Controller, 460 V 2 Hp

HR46TN002 (2)

Controller, 575 V 2 Hp

HR46TN003 (2)

Enclosure

30RA500381

Enclosure Cover

30RA500519

Enclosure Mounting Bracket

50EJ500656

Fan Relay

HN61KK035 (2)

Relay Base

HN79KK035 (2)

Fuse Block

HY11UT035 (2)

Fuse 15A, KTK-R, Class CC

HY10KB151 (6)

HY10KB151 (6)

Fuse 20A, KTK-R, Class CC

HY10KB200 (6)

Harness Assembly

48EJ400657 (2)

Harness Assembly

48EJ402454 (2)

Harness Assembly

48EJ400658 (2)

Label

48EJ500564

Transducer

HK05ZZ001 (2)

Transducer Harness

48EJ403240 (2)

Wire Tie

HY76TB123 (5)

Wire Tie

HY76TB171 (2)

Wire, 16 Gage 72 in. Long

WHT (2), GRY (2)

1/2-in. Connector

HW60EA001 (2)

1-in. Connector

HW60HH006 (2)

Small Varnish Cloth

38C24601 (2)

Large Varnish Cloth

48DA510141 (2)

UNIT

VOLTAGE

ITEM DESCRIPTION

48/50AJ,AK,AW,AY020-060

208/230

CRLOWAMB018A00

380, 400, 460

CRLOWAMB019A00

575

CRLOWAMB020A00

48/50A2,A3,A4,A5020-050

 and 48/50A2,A3,A4,A5060 RTPF

208/230

CRLOWAMB021A00

380, 460

CRLOWAMB022A00

575

CRLOWAMB023A00

48/50A2,A3,A4,A5060 MCHX

208/230

CRLOWAMB024A00

380, 460

CRLOWAMB025A00

575

CRLOWAMB026A00

WARNING

To avoid the possibility of electrical shock, open all discon-

nects before installing or servicing this accessory.

CAUTION

To avoid damage to refrigerant coils, electrical compo-

nents, and wiring use extreme care when drilling screw

holes and screwing in fasteners.

StockCheck.com

Downloaded from StockCheck.com

Summary of Contents for MOTORMASTER CRLOWAMB018A00

Page 1: ...motor speed in response to varying liquid refrigerant pressure A properly applied Motormaster V control extends the operating range of air conditioning systems and permits operation at lower outdoor a...

Page 2: ...Class CC HY10KB200 3 Fuse 30A KTK R Class CC HY10KB300 3 Harness Assembly 48EJ403106 2 Harness Assembly 48EJ402454 Harness Assembly 48EJ402298 Label 48EJ503269 Transducer HK05YZ007 Transducer Harness...

Page 3: ...HR46TN001 2 Controller 460 V 2 Hp HR46TN002 2 Controller 575 V 2 Hp HR46TN003 2 Enclosure 30RA500381 Enclosure Cover 30RA500519 Enclosure Mounting Bracket 50EJ500656 Fan Relay HN61KK035 2 Relay Base...

Page 4: ...LEGEND MCHX Microchannel Heat Exchanger RTPF Round Tube Plate Fin Heat Exchanger UNIT SIZE QUANTITY DIMENSION A in mm 020 035 1 78 125 0 125 1984 3 036 050 2 78 125 0 125 1984 3 051 060 2 118 0 125 29...

Page 5: ...he existing OFM wire harnesses and strip insulation back 1 2 inch Attach 16 gage black red and blue field supplied wires to the corresponding colors of both OFM harnesses with a wire nut Connect black...

Page 6: ...51 060 RTPF 1 MMV 2 3 Shut OFF at 55 F and turn ON at 65 F outdoor air temperature 4 5 6 060 MCHX 1 MMV B 2 Shut OFF at 55 F and turn ON at 65 F outdoor air temperature 3 MMV A 4 Shut OFF at 55 F and...

Page 7: ...OCK Fig 4 Fuse Block and Fan Relay Mounting cont 48 50A2 A3 A4 A5 AJ AK AW AY036 051 AND 060 RTPF 48 50A2 A3 A4 A5 AJ AK AW AY060 MCHX a48 8404 MMV CONTROL ACH550 OR S9 VFD Fig 5 MMV Control Mounting...

Page 8: ...8 E3 VFD MMV CONTROL E3 VFD MMV CONTROL Fig 6 MMV Control Mounting with 25 Hp 575 v E3 VFD Fig 7 MMV Control Mounting with 30 or 40 Hp 575 v E3 VFD StockC heck com Downloaded from StockCheck com...

Page 9: ...MMPT 230 3 60 SHOWN REFER TO TABLE 4 FOR ALTERNATE VOLTAGE CONNECTIONS A B C TB YEL RED BLK RED BLU 11 12 13 22 23 21 Fig 8 Motormaster V Accessory Wiring 48 50A2 A3 A4 A5 AJ AK AW AY020 035 Units Fi...

Page 10: ...he control box and run them through the opening of the cable tray on the back of the control box where existing transducer cables come out Route wires along bottom edge of back of control box and up t...

Page 11: ...230 3 60 SHOWN REFER TO TABLE 4 FOR ALTERNATE VOLTAGE CONNECTIONS FR A OFC3 13 14 C1 C2 ADD FAN RELAY FR A IN PARALLEL WITH OFC3 MMF A BLU YEL A B C TB BLU RED BLK GRN YEL DRAIN RED BLK BLU RED BLK G...

Page 12: ...n ap proximately 200 psig liquid line pressure for R 22 units and 320 psig for R 410A units Above that pressure the fan should operate at full speed The Motormaster V control uses a 0 to 5 vdc signal...

Page 13: ...at low frequencies 0 5 0 5 0 5 P29 Accel boost 0 0 0 0 P30 Slip compensation 0 0 0 0 P31 Preset spd 1 speed if loss of control signal 57 57 47 P32 Preset spd 2 0 0 0 0 P33 Preset spd 3 0 0 0 0 P34 Pr...

Page 14: ...e group is displayed through parameters P50 to P56 and all values are read only These values can be accessed without entering a password Press MODE twice and P50 will appear Press MODE again to displa...

Page 15: ...ltage set P01 appropriately JF Serial Fault Automatic The watchdog timer has timed out indicating that the serial link has been lost Check serial connection computer Check settings for P15 Check setti...

Page 16: ...any time specifications or designs without notice and without incurring obligations Catalog No 04 53480084 01 Printed in U S A Form 48 50A 14SI Pg 16 3 11 Replaces 48 50A 10SI Copyright 2011 Carrier...