Table 6 — Fault Codes

The drive is programmed to automatically restart after a fault and will attempt to restart three times

after a fault (the drive will not restart after CF, cF, GF, F1, F2-F9, or Fo faults). If all three restart attempts

are unsuccessful, the drive will trip into FAULT LOCKOUT (LC), which requires a manual reset. 

                    

     LEGEND

CODE

DESCRIPTION

RESET 

METHOD

PROBABLE CAUSE

CORRECTIVE ACTION

AF

High Temperature Fault 

Automatic

Ambient temperature is too high; 
Cooling fan has failed (if equipped).

Check cooling fan operation.

CF

Control Fault

Manual

A blank EPM, or an EPM with cor-
rupted data has been installed.

Perform a factory reset using Parameter 
48 – PROGRAM SELECTION. See Drive 
Programming section.

cF

Incompatibility Fault

Manual

An EPM with an incompatible param-
eter version has been installed.

Either remove the EPM or perform a fac-
tory reset (Parameter 48) to change the 
parameter version of the EPM to match 
the parameter version of the drive.

F1

EPM Fault

Manual

The EPM is missing or damaged.

Install EPM or replace with new EPM.

F2—F9

Fo

Internal Faults

Manual

The control board has sensed a
problem

Consult factory.

GF

Data Fault

Manual

User data and Carrier defaults in the 
EPM are corrupted.

Restore factory defaults by toggling P48 to 
another mode. Then set P48 to desired 
mode to restore all defaults for that mode. 
See Drive Programming section. If that 
does not work, replace EPM.

HF

High DC Bus Voltage Fault

Automatic

Line voltage is too high; Deceleration 
rate is too fast; Overhauling load.

Check line voltage — set P01
appropriately.

JF

Serial Fault

Automatic

The watchdog timer has timed out, 
indicating that the serial link has been 
lost.

Check serial connection (computer).
Check settings for P15.
Check settings in communication software 
to match P15.

LF

Low DC Bus Voltage Fault

Automatic

Line voltage is too low.

Check line voltage — set P01
appropriately.

OF

Output Transistor Fault

Automatic

Phase to phase or phase to ground 
short circuit on the output; Failed out-
put transistor; Boost settings are too 
high; Acceleration rate is too fast.

Reduce boost or increase acceleration 
values. If unsuccessful, replace drive.

PF

Current Overload Fault

Automatic

VFD is undersized for the application; 
Mechanical problem with the driven 
equipment.

Check line voltage – set P01 appropri-
ately.
Check for dirty coils.
Check for motor bearing failure.

SF

Single-phase Fault

Automatic

Single-phase input power has been 
applied to a three-phase drive.

Check input power phasing.

Drive displays

‘---’ even 

though drive 

should be 

running

Start Contact is Not Closed

Automatic

Start contact is missing or not
functioning.

Check fan relay.

VFD flashes 

“---” 

and LCS

Start Contact is Not Closed

Automatic

Start contact not closed.

Check FR for closed contact.

VFD flashes 

57 (or 47)

and LCS

Speed Signal Lost

Automatic

Speed signal lost. Drive will operate 
at 57 (or 47) Hz until reset or loss of 
start command. Resetting requires 
cycling start command (or power).

Transducer signal lost. Check VDC signal 
between TB5 and TB2. Should be in range 
of 0.5V to 4.5V. 5VDC output should be 
present between TB6 and TB2.

EPM —

Electronic Programming Module

FR

Fan Relay

LCS —

Loss of Control Signal

TB

Terminal Block

VFD —

Variable Frequency Drive

StockCheck.com

Downloaded from StockCheck.com

Summary of Contents for MOTORMASTER CRLOWAMB018A00

Page 1: ...motor speed in response to varying liquid refrigerant pressure A properly applied Motormaster V control extends the operating range of air conditioning systems and permits operation at lower outdoor a...

Page 2: ...Class CC HY10KB200 3 Fuse 30A KTK R Class CC HY10KB300 3 Harness Assembly 48EJ403106 2 Harness Assembly 48EJ402454 Harness Assembly 48EJ402298 Label 48EJ503269 Transducer HK05YZ007 Transducer Harness...

Page 3: ...HR46TN001 2 Controller 460 V 2 Hp HR46TN002 2 Controller 575 V 2 Hp HR46TN003 2 Enclosure 30RA500381 Enclosure Cover 30RA500519 Enclosure Mounting Bracket 50EJ500656 Fan Relay HN61KK035 2 Relay Base...

Page 4: ...LEGEND MCHX Microchannel Heat Exchanger RTPF Round Tube Plate Fin Heat Exchanger UNIT SIZE QUANTITY DIMENSION A in mm 020 035 1 78 125 0 125 1984 3 036 050 2 78 125 0 125 1984 3 051 060 2 118 0 125 29...

Page 5: ...he existing OFM wire harnesses and strip insulation back 1 2 inch Attach 16 gage black red and blue field supplied wires to the corresponding colors of both OFM harnesses with a wire nut Connect black...

Page 6: ...51 060 RTPF 1 MMV 2 3 Shut OFF at 55 F and turn ON at 65 F outdoor air temperature 4 5 6 060 MCHX 1 MMV B 2 Shut OFF at 55 F and turn ON at 65 F outdoor air temperature 3 MMV A 4 Shut OFF at 55 F and...

Page 7: ...OCK Fig 4 Fuse Block and Fan Relay Mounting cont 48 50A2 A3 A4 A5 AJ AK AW AY036 051 AND 060 RTPF 48 50A2 A3 A4 A5 AJ AK AW AY060 MCHX a48 8404 MMV CONTROL ACH550 OR S9 VFD Fig 5 MMV Control Mounting...

Page 8: ...8 E3 VFD MMV CONTROL E3 VFD MMV CONTROL Fig 6 MMV Control Mounting with 25 Hp 575 v E3 VFD Fig 7 MMV Control Mounting with 30 or 40 Hp 575 v E3 VFD StockC heck com Downloaded from StockCheck com...

Page 9: ...MMPT 230 3 60 SHOWN REFER TO TABLE 4 FOR ALTERNATE VOLTAGE CONNECTIONS A B C TB YEL RED BLK RED BLU 11 12 13 22 23 21 Fig 8 Motormaster V Accessory Wiring 48 50A2 A3 A4 A5 AJ AK AW AY020 035 Units Fi...

Page 10: ...he control box and run them through the opening of the cable tray on the back of the control box where existing transducer cables come out Route wires along bottom edge of back of control box and up t...

Page 11: ...230 3 60 SHOWN REFER TO TABLE 4 FOR ALTERNATE VOLTAGE CONNECTIONS FR A OFC3 13 14 C1 C2 ADD FAN RELAY FR A IN PARALLEL WITH OFC3 MMF A BLU YEL A B C TB BLU RED BLK GRN YEL DRAIN RED BLK BLU RED BLK G...

Page 12: ...n ap proximately 200 psig liquid line pressure for R 22 units and 320 psig for R 410A units Above that pressure the fan should operate at full speed The Motormaster V control uses a 0 to 5 vdc signal...

Page 13: ...at low frequencies 0 5 0 5 0 5 P29 Accel boost 0 0 0 0 P30 Slip compensation 0 0 0 0 P31 Preset spd 1 speed if loss of control signal 57 57 47 P32 Preset spd 2 0 0 0 0 P33 Preset spd 3 0 0 0 0 P34 Pr...

Page 14: ...e group is displayed through parameters P50 to P56 and all values are read only These values can be accessed without entering a password Press MODE twice and P50 will appear Press MODE again to displa...

Page 15: ...ltage set P01 appropriately JF Serial Fault Automatic The watchdog timer has timed out indicating that the serial link has been lost Check serial connection computer Check settings for P15 Check setti...

Page 16: ...any time specifications or designs without notice and without incurring obligations Catalog No 04 53480084 01 Printed in U S A Form 48 50A 14SI Pg 16 3 11 Replaces 48 50A 10SI Copyright 2011 Carrier...

Reviews: