48/50A2,A3,A4,A5060 MCHX UNITS — Two  Motormas-

ter

®

 controls are used to control two independent outdoor-fan

motors. The refrigerant circuit A Motormaster controlled OFM

is the no. 3 OFM. The refrigerant circuit B Motormaster con-

trolled OFM is the no. 1 OFM (see Fig. 3). The no. 2 and 4

OFMs are controlled to shutoff at 55 F and on at 65 F outdoor-

air temperature. All OFMs in this unit are compatible with the

Motormaster control and do NOT need to be changed out. 

Use the following procedure to mount and connect the

MMV controllers to this unit:

1. Disconnect power to the unit. Lockout and tag power dis-

connect.

2. Remove control box covers.
3. Mount accessory fuse blocks HY11UT035 (label 1 as

MMF-A and the other as MMF-B) and fan relay bases

HN79KK035 (label 1 as FR-A and the other as FR-B) in-

side control box as shown in Fig. 4. Secure components

with ½-in. sheet metal screws.

a. Insert fuses into fuse blocks and relays into relay

bases.

b. Install harnesses 48EJ402454 from load side of

CCB (control circuit breaker terminals 21, 22, 23)

to line side of MMF-A and MMF-B fuse blocks as

shown in Fig. 10. Note that it may be easier to pick

up the load side of CCB (control circuit breaker)

from the ¼-in. male quick connect terminals on the

line side (terminals 11, 12, 13) of the OFCs (out-

door fan contactors). See power schematic on con-

trol box door.

c. Connect FR-A coil to OFC3 coil and FR-B coil to

OFC1 coil using the 72 in. long 16 gage white and

gray wires (stripped end goes to FR) as shown in

Fig. 10.

4. Mount the MMV controller enclosures 30RA500381on

the inside of the unit corner post, as shown in Fig. 11, us-

ing the mounting brackets 50EJ500656 installed on the

enclosures (label 1 as MMV-A and the other as MMV-B).

Remove the enclosure covers and install the ½-in.

HW60EA001 and 1-in. HW60HH006 connectors in the

holes in the lower right hand side of the enclosures. 

5. Connect transducers HK05ZZ001 to the liquid line ser-

vice Schrader ports, located under the V-coil of the con-

denser fan sections, of refrigerant circuit A and B. Circuit

A is the one closest to the indoor fan motor section, and

circuit B is the one closest to the control box, (label cir-

cuit A transducer as MMPT-A and circuit B transducer as

MMPT-B).

6. Plug transducer cables 48EJ403240 into transducers (la-

bel stripped end of circuit A cable as MMPT-A and the

stripped end of circuit B cable as MMPT-B). Run cables

along inside of unit base rail and up the corner post to the

MMV enclosures.

7. Run MMPT-A cable through ½-in. connector of MMV-A

enclosure, and MMPT-B cable through ½-in. connector

of MMV-B enclosure (do not tighten connector screws at

this time). Connect red, green, and black wires to MMV-

A and MMV-B terminals 6, 5, and 2 as shown in Fig. 10.

Terminate drain wire of transducer cables under one of

the lower MMV mounting screws. 

8. Make remaining electrical connections to MMV-A and

MMV-B (see Fig. 10).

a. In main control box, disconnect black, red, blue,

and green wires from load side (terminals 21, 22,

23) of OFC1 and OFC3 contactors (label cable

from OFC1 as OFM1 and cable from OFC3 as

OFM3). Pull wires out through the hole in the bot-

tom of the control box and run them through the

opening of the cable tray on the back of the control

box (where existing transducer cables come out).

Route wires along bottom edge of back of control

box and up the corner post to the MMV enclosures.

b. Run the OFM1 cable through the 1-in. connector

of the MMV-B enclosure (do not tighten connector

screws at this time). Remove ring terminals from

black, red, and blue wires and strip insulation back

3/8-inch. Connect black, red, and blue wires to

MMV-B terminals T1, T2, and T3. Connect green

ground wire to MMV-B ground screw.

c. Run OFM3 cable through 1-in. connector of

MMV-A enclosure (do not tighten connector

screws at this time). Remove ring terminals from

black, red, and blue wires and strip insulation back

3/8-inch. Connect black, red, and blue wires to

MMV-A terminals T1, T2, and T3. Connect green

ground wire to MMV-B ground screw.

d. In main control box connect 1 Motormaster® VFD

harness 50EJ400657 to the load side of MMF-A

(label the opposite end of this harness as MMF-A)

and the other Motormaster VFD harnesses

50EJ400657 to the load side of MMF-B (label the

opposite end of this harness as MMF-B). Run the

harnesses along the bottom of the control box and

out through the hole that the OFM harnesses were

in. Pull the harnesses out through the hole in the

bottom of the control box and run them through the

opening of the cable tray on the back of the control

box (in the same manner as the OFM harnesses). 

e. Run the MMF-A cable through 1-in connector of

MMV-A enclosure (do not tighten connector

screws at this time). Connect L1, L2, and L3 wires

to MMV-A terminals L1, L2, and L3. Connect

green ground wire to MMV-A ground screw. Place

one large varnish cloth 48DA510141 around both

cables at the point they enter the 1-in. connector.

Tighten down connector screws being careful not

to damage the cables.

f. Run the MMF-B cable through 1-in. connector of

MMV-B enclosure (do not tighten connector

screws at this time). Connect L1, L2, and L3 wires

to MMV-B terminals L1, L2, and L3. Connect

green ground wire to MMV-B ground screw. Place

the other large varnish cloth 48DA510141 around

both cables at the point they enter the 1-in. connec-

tor. Tighten down connector screws being careful

not to damage the cables.

g. In main control box connect 1 Motormaster VFD

(variable frequency drive) harness 50EJ400658 to

the N.O. (normally open) contact of FR-A (see

Fig. 11) (label the opposite end of this harness as

FR-A) and the other Motormaster VFD harness

50EJ400658 to the N.O. contact of FR-B (label the

opposite end of this harness as FR-B) Run the har-

nesses along the bottom of the control box and out

through the hole that the OFM harnesses were in.

Pull the harnesses out through the hole in the bot-

tom of the control box and run them through the

opening of the cable tray on the back of the control

box (in the same manner as the OFM harnesses). 

h. Run the FR-A cable through the 1/2-in. connector

of the MMV-A enclosure (do not tighten connector

screws at this time). Connect black wire to MMV-

A terminal 2 and red wire to MMV-A terminal 1,

13A, or 13C (see Table 4). Place 1 small varnish

cloth 38C24601 around both cables at the point

they enter the 1/2-in. connector. Tighten down con-

nector screws being careful not to damage the

cables.

StockCheck.com

Downloaded from StockCheck.com

Summary of Contents for MOTORMASTER CRLOWAMB018A00

Page 1: ...motor speed in response to varying liquid refrigerant pressure A properly applied Motormaster V control extends the operating range of air conditioning systems and permits operation at lower outdoor a...

Page 2: ...Class CC HY10KB200 3 Fuse 30A KTK R Class CC HY10KB300 3 Harness Assembly 48EJ403106 2 Harness Assembly 48EJ402454 Harness Assembly 48EJ402298 Label 48EJ503269 Transducer HK05YZ007 Transducer Harness...

Page 3: ...HR46TN001 2 Controller 460 V 2 Hp HR46TN002 2 Controller 575 V 2 Hp HR46TN003 2 Enclosure 30RA500381 Enclosure Cover 30RA500519 Enclosure Mounting Bracket 50EJ500656 Fan Relay HN61KK035 2 Relay Base...

Page 4: ...LEGEND MCHX Microchannel Heat Exchanger RTPF Round Tube Plate Fin Heat Exchanger UNIT SIZE QUANTITY DIMENSION A in mm 020 035 1 78 125 0 125 1984 3 036 050 2 78 125 0 125 1984 3 051 060 2 118 0 125 29...

Page 5: ...he existing OFM wire harnesses and strip insulation back 1 2 inch Attach 16 gage black red and blue field supplied wires to the corresponding colors of both OFM harnesses with a wire nut Connect black...

Page 6: ...51 060 RTPF 1 MMV 2 3 Shut OFF at 55 F and turn ON at 65 F outdoor air temperature 4 5 6 060 MCHX 1 MMV B 2 Shut OFF at 55 F and turn ON at 65 F outdoor air temperature 3 MMV A 4 Shut OFF at 55 F and...

Page 7: ...OCK Fig 4 Fuse Block and Fan Relay Mounting cont 48 50A2 A3 A4 A5 AJ AK AW AY036 051 AND 060 RTPF 48 50A2 A3 A4 A5 AJ AK AW AY060 MCHX a48 8404 MMV CONTROL ACH550 OR S9 VFD Fig 5 MMV Control Mounting...

Page 8: ...8 E3 VFD MMV CONTROL E3 VFD MMV CONTROL Fig 6 MMV Control Mounting with 25 Hp 575 v E3 VFD Fig 7 MMV Control Mounting with 30 or 40 Hp 575 v E3 VFD StockC heck com Downloaded from StockCheck com...

Page 9: ...MMPT 230 3 60 SHOWN REFER TO TABLE 4 FOR ALTERNATE VOLTAGE CONNECTIONS A B C TB YEL RED BLK RED BLU 11 12 13 22 23 21 Fig 8 Motormaster V Accessory Wiring 48 50A2 A3 A4 A5 AJ AK AW AY020 035 Units Fi...

Page 10: ...he control box and run them through the opening of the cable tray on the back of the control box where existing transducer cables come out Route wires along bottom edge of back of control box and up t...

Page 11: ...230 3 60 SHOWN REFER TO TABLE 4 FOR ALTERNATE VOLTAGE CONNECTIONS FR A OFC3 13 14 C1 C2 ADD FAN RELAY FR A IN PARALLEL WITH OFC3 MMF A BLU YEL A B C TB BLU RED BLK GRN YEL DRAIN RED BLK BLU RED BLK G...

Page 12: ...n ap proximately 200 psig liquid line pressure for R 22 units and 320 psig for R 410A units Above that pressure the fan should operate at full speed The Motormaster V control uses a 0 to 5 vdc signal...

Page 13: ...at low frequencies 0 5 0 5 0 5 P29 Accel boost 0 0 0 0 P30 Slip compensation 0 0 0 0 P31 Preset spd 1 speed if loss of control signal 57 57 47 P32 Preset spd 2 0 0 0 0 P33 Preset spd 3 0 0 0 0 P34 Pr...

Page 14: ...e group is displayed through parameters P50 to P56 and all values are read only These values can be accessed without entering a password Press MODE twice and P50 will appear Press MODE again to displa...

Page 15: ...ltage set P01 appropriately JF Serial Fault Automatic The watchdog timer has timed out indicating that the serial link has been lost Check serial connection computer Check settings for P15 Check setti...

Page 16: ...any time specifications or designs without notice and without incurring obligations Catalog No 04 53480084 01 Printed in U S A Form 48 50A 14SI Pg 16 3 11 Replaces 48 50A 10SI Copyright 2011 Carrier...

Reviews: