background image

14

4. Press MODE to display present parameter setting. The

upper right decimal point blinks. Use UP and DOWN

buttons to scroll to the desired parameter number.

5. Once the desired parameter number is found, press the

MODE button to display the present parameter setting.

The upper right-hand decimal point will begin blinking,

indicating that the present parameter setting is being dis-

played. Use the UP and DOWN buttons to change set-

ting. Press MODE to store new setting.

6. Press MODE to store the new setting and also exit the

PROGRAM mode. To change another parameter, press

the MODE button again to re-enter the PROGRAM

mode (the parameter menu will be accessed at the param-

eter that was last viewed or changed before exiting). If the

MODE button is pressed within two minutes of exiting

the PROGRAM mode, the password is not required to ac-

cess the parameters.

7. After two minutes, the password must be entered in order

to access the parameters again.

TO CHANGE PASSWORD  — Enter  the  current  password

then change P44 to the desired password.
TO RESET FACTORY DEFAULTS  — To recognize a fac-

tory reset, the MMV controller must see a change in P48.

1. Cycle power from Motormaster

®

 V control.

2. Enter PROGRAM mode by entering password.
3. Scroll to P48 by using UP and DOWN buttons and then

press MODE. One of the 12 mode numbers will appear.

(Modes 1, 2 and 4 are used for these units.)

4. Restore factory defaults by changing the value in P48 us-

ing UP and DOWN buttons and then storing the value by

pressing MODE.

5. Press MODE again to re-display the value of P48.
6. Change the value of P48 to the desired factory default

mode (see Table 5) using UP and DOWN buttons then

press MODE. The Motormaster V control is now restored

to factory settings.

TROUBLESHOOTING

Troubleshooting the Motormaster V control requires a com-

bination of observing system operation and VFD display

information.

If the liquid line pressure is above the set point and the VFD

is running at full speed, this is a normal condition. The fan

CANNOT

 go any faster to maintain set point.

If the VFD is not slowing down even though liquid line

pressure is below set point, the VFD could be set for manual

control or the control may be receiving faulty pressure trans-

ducer output. Corrective action would include:
• Check that VDC signal between TB5 and TB2 is

between 0.5 v and 4.5 v.

• Restore VFD to automatic control.

• Change parameter P05 back to correct value shown in

Table 5.
The MMV control also provides real time monitoring of

key inputs and outputs. The collective group is displayed

through parameters P50 to P56 and all values are read only.

These values can be accessed without entering a password.

Press MODE twice and P50 will appear.
Press MODE again to display value.
To scroll to P51-P56 from P50, use UP and DOWN buttons

then press MODE to display the value.

P50: FAULT HISTORY —

 Last 8 faults

• P51: SOFTWARE version

P52: DC BUS VOLTAGE —

 in percent of nominal.

Usually rated input voltage x 1.4

P53: MOTOR VOLTAGE —

 in percent of rated output

voltage

P54: LOAD —

 in percent of drives rated output current

P55: VDC INPUT —

 in percent of maximum input:

100% will indicate full scale which is 5 v

P56: 4-20 mA INPUT —

 in percent of maximum input.

20% = 4 mA, 100% = 20 mA

NOTE:

 

The Motormaster V transducer is attached to circuit A.

If circuit A compressor power is interrupted (overload, high

pressure cutout, etc.) the outdoor fans will operate at a reduced

speed resulting from erroneous low pressure readings. This

process may cause a high pressure safety cutout on circuit B

compressor. If only circuit B is capable of operating for a tem-

porary period of time because of a circuit A problem, the trans-

ducer will have to be moved to the circuit B service port until

circuit A can be repaired. Once the problem is repaired, move

the transducer back to circuit A for proper unit operation.

Fault Lockout — 

If a fault lockout (LC) has occurred,

view the fault history in P50 to find the last fault. Once P50 is

displayed, use the arrow buttons to scroll through the last

8 faults. Any current faults or fault codes from the fault history

can be analyzed using Table 6.
TO DISABLE AUTOMATIC CONTROL MODE AND

ENTER MANUAL SPEED CONTROL:

1. Change P05 to ‘01- keypad’.
2. Push UP and DOWN arrow button to set manual speed.
3. Set P05 to proper value to restore automatic control

according to Table 5.

TO PROVIDE MANUAL START/STOP CONTROL — With

power removed from VFD, remove start command jumper and

install a switch between the appropriate start terminals as

required in Table 4.

EPM Chip — 

The drive uses a electronic programming

module (EPM) chip to store the program parameters. This is an

EEPROM memory chip and is accessible from the front of the

VFD. It should not be removed with power applied to the

VFD.

Loss of CCN Communications — 

Carrier Comfort

Network® (CCN) communications with external control

systems can be affected by high frequency electrical noise gen-

erated by the Motormaster V control. Ensure unit is well

grounded to eliminate ground currents along communication

lines.

If communications are lost only while Motormaster V con-

trol is in operation, order a signal isolator (CEAS420876-2)

and power supplies (CEAS221045-01, 2 required) for the CCN

communication line.

StockCheck.com

Downloaded from StockCheck.com

Summary of Contents for MOTORMASTER CRLOWAMB018A00

Page 1: ...motor speed in response to varying liquid refrigerant pressure A properly applied Motormaster V control extends the operating range of air conditioning systems and permits operation at lower outdoor a...

Page 2: ...Class CC HY10KB200 3 Fuse 30A KTK R Class CC HY10KB300 3 Harness Assembly 48EJ403106 2 Harness Assembly 48EJ402454 Harness Assembly 48EJ402298 Label 48EJ503269 Transducer HK05YZ007 Transducer Harness...

Page 3: ...HR46TN001 2 Controller 460 V 2 Hp HR46TN002 2 Controller 575 V 2 Hp HR46TN003 2 Enclosure 30RA500381 Enclosure Cover 30RA500519 Enclosure Mounting Bracket 50EJ500656 Fan Relay HN61KK035 2 Relay Base...

Page 4: ...LEGEND MCHX Microchannel Heat Exchanger RTPF Round Tube Plate Fin Heat Exchanger UNIT SIZE QUANTITY DIMENSION A in mm 020 035 1 78 125 0 125 1984 3 036 050 2 78 125 0 125 1984 3 051 060 2 118 0 125 29...

Page 5: ...he existing OFM wire harnesses and strip insulation back 1 2 inch Attach 16 gage black red and blue field supplied wires to the corresponding colors of both OFM harnesses with a wire nut Connect black...

Page 6: ...51 060 RTPF 1 MMV 2 3 Shut OFF at 55 F and turn ON at 65 F outdoor air temperature 4 5 6 060 MCHX 1 MMV B 2 Shut OFF at 55 F and turn ON at 65 F outdoor air temperature 3 MMV A 4 Shut OFF at 55 F and...

Page 7: ...OCK Fig 4 Fuse Block and Fan Relay Mounting cont 48 50A2 A3 A4 A5 AJ AK AW AY036 051 AND 060 RTPF 48 50A2 A3 A4 A5 AJ AK AW AY060 MCHX a48 8404 MMV CONTROL ACH550 OR S9 VFD Fig 5 MMV Control Mounting...

Page 8: ...8 E3 VFD MMV CONTROL E3 VFD MMV CONTROL Fig 6 MMV Control Mounting with 25 Hp 575 v E3 VFD Fig 7 MMV Control Mounting with 30 or 40 Hp 575 v E3 VFD StockC heck com Downloaded from StockCheck com...

Page 9: ...MMPT 230 3 60 SHOWN REFER TO TABLE 4 FOR ALTERNATE VOLTAGE CONNECTIONS A B C TB YEL RED BLK RED BLU 11 12 13 22 23 21 Fig 8 Motormaster V Accessory Wiring 48 50A2 A3 A4 A5 AJ AK AW AY020 035 Units Fi...

Page 10: ...he control box and run them through the opening of the cable tray on the back of the control box where existing transducer cables come out Route wires along bottom edge of back of control box and up t...

Page 11: ...230 3 60 SHOWN REFER TO TABLE 4 FOR ALTERNATE VOLTAGE CONNECTIONS FR A OFC3 13 14 C1 C2 ADD FAN RELAY FR A IN PARALLEL WITH OFC3 MMF A BLU YEL A B C TB BLU RED BLK GRN YEL DRAIN RED BLK BLU RED BLK G...

Page 12: ...n ap proximately 200 psig liquid line pressure for R 22 units and 320 psig for R 410A units Above that pressure the fan should operate at full speed The Motormaster V control uses a 0 to 5 vdc signal...

Page 13: ...at low frequencies 0 5 0 5 0 5 P29 Accel boost 0 0 0 0 P30 Slip compensation 0 0 0 0 P31 Preset spd 1 speed if loss of control signal 57 57 47 P32 Preset spd 2 0 0 0 0 P33 Preset spd 3 0 0 0 0 P34 Pr...

Page 14: ...e group is displayed through parameters P50 to P56 and all values are read only These values can be accessed without entering a password Press MODE twice and P50 will appear Press MODE again to displa...

Page 15: ...ltage set P01 appropriately JF Serial Fault Automatic The watchdog timer has timed out indicating that the serial link has been lost Check serial connection computer Check settings for P15 Check setti...

Page 16: ...any time specifications or designs without notice and without incurring obligations Catalog No 04 53480084 01 Printed in U S A Form 48 50A 14SI Pg 16 3 11 Replaces 48 50A 10SI Copyright 2011 Carrier...

Reviews: