i. Run the FR-B cable through the 1/2-in. connector

of the MMV-B enclosure (do not tighten connector

screws at this time). Connect black wire to MMV-

B terminal 2 and red wire to MMV-B terminal 1,

13A, or 13C (see Table 4). Place the other small

varnish cloth 38C24601 around both cables at the

point they enter the 1/2-in. connector. Tighten

down connector screws being careful not to dam-

age the cables.

9. Bundle excess wire and dress harnesses with wire ties.

10. Reattach control box, MMV enclosure, and cable tray

covers.

Step 3 — Configure Motormaster

®

 V Con-

trol — 

The Motormaster V control is configured for an oper-

ation mode of internal PI (pressure independent) control and 0

to 5V feedback by installing the start contactor according to

Table 4. No additional programming is required. Note that the

pressure transducer must be attached for proper configuration.

Table 4 — Configuration Table

Step 4 — Test Motormaster V Control — 

To test the

control and motor in the test mode, run compressor no. 1.

The Motormaster V electronic control adjusts the fan speed

based on the liquid pressure input. Ensure that fans are rotating

clockwise (as viewed from above). If rotation is back-

ward, lock out all power then swap 2 leads AFTER the

Motormaster V control.

START-UP

The Motormaster V electronic control will be powered up

as long as unit voltage is present. When the system calls for

cooling, the fan relay will be energized to initiate the start-up

sequence for the Motormaster V electronic control. The LED

(light-emitting diode) will display the speed of the motor. The

display range will be 8 to 60 Hz. The Motormaster V electronic

control will start the condenser fan when the compressor en-

gages. The control will adjust the fan speed to maintain ap-

proximately 200 psig liquid line pressure for R-22 units and

320 psig for R-410A units. Above that pressure, the fan should

operate at full speed.

The Motormaster V control uses a 0 to 5 vdc signal input

from a pressure transducer attached to the liquid line service

valve gage port on circuit A. The pressure transducer is con-

nected to terminals 2, 5 and 6 on the controller. The controller

is configured by jumper wires and sensor input types. No field

programming is required. If controller does not function prop-

erly, the information provided below can be used to program

and troubleshoot the drive.

Drive Programming — 

Table 5 shows all program pa-

rameters for each of the operating modes. Refer to Trouble-

shooting section before attempting to change programming in

the Motormaster V control.

TO ENTER PASSWORD AND CHANGE PROGRAM

VALUES:

1. Press MODE.
2. The display will read “00” and the upper right-hand deci-

mal point will be blinking. This will activate the PASS-

WORD prompt (if the password has not been disabled).

3. Use the UP and DOWN buttons to scroll to the password

value (the factory default password is “111”) and press

the MODE button. Once the correct password value is en-

tered, the display will read “P01”, which indicates that the

PROGRAM mode has been accessed at the beginning of

the parameter menu (P01 is the first parameter).

NOTE: If the display flashes “Er”, the password was incorrect,

and the process to enter the password must be repeated.

Fig. 11 — MMV Control Mounting with 48/50A2,A3,A4,A5060 MCHX Units

a48-8405

NOMINAL

VOLTAGE

(V-Ph-Hz)

MODE

CONTROL INPUT

(Pin 5)

START

CONTACTS

230-3-60
460-3-60
575-3-60

1

Internal PI control,

 0-5V feedback

TB 1,2

208-3-60
380-3-60

2

TB 13A,2

400-3-50

4

TB 13C,2

CAUTION

It is strongly recommended that the user NOT change any

programming without consulting Carrier service personnel.

Unit damage may occur from improper programming.

StockCheck.com

Downloaded from StockCheck.com

Summary of Contents for MOTORMASTER CRLOWAMB018A00

Page 1: ...motor speed in response to varying liquid refrigerant pressure A properly applied Motormaster V control extends the operating range of air conditioning systems and permits operation at lower outdoor a...

Page 2: ...Class CC HY10KB200 3 Fuse 30A KTK R Class CC HY10KB300 3 Harness Assembly 48EJ403106 2 Harness Assembly 48EJ402454 Harness Assembly 48EJ402298 Label 48EJ503269 Transducer HK05YZ007 Transducer Harness...

Page 3: ...HR46TN001 2 Controller 460 V 2 Hp HR46TN002 2 Controller 575 V 2 Hp HR46TN003 2 Enclosure 30RA500381 Enclosure Cover 30RA500519 Enclosure Mounting Bracket 50EJ500656 Fan Relay HN61KK035 2 Relay Base...

Page 4: ...LEGEND MCHX Microchannel Heat Exchanger RTPF Round Tube Plate Fin Heat Exchanger UNIT SIZE QUANTITY DIMENSION A in mm 020 035 1 78 125 0 125 1984 3 036 050 2 78 125 0 125 1984 3 051 060 2 118 0 125 29...

Page 5: ...he existing OFM wire harnesses and strip insulation back 1 2 inch Attach 16 gage black red and blue field supplied wires to the corresponding colors of both OFM harnesses with a wire nut Connect black...

Page 6: ...51 060 RTPF 1 MMV 2 3 Shut OFF at 55 F and turn ON at 65 F outdoor air temperature 4 5 6 060 MCHX 1 MMV B 2 Shut OFF at 55 F and turn ON at 65 F outdoor air temperature 3 MMV A 4 Shut OFF at 55 F and...

Page 7: ...OCK Fig 4 Fuse Block and Fan Relay Mounting cont 48 50A2 A3 A4 A5 AJ AK AW AY036 051 AND 060 RTPF 48 50A2 A3 A4 A5 AJ AK AW AY060 MCHX a48 8404 MMV CONTROL ACH550 OR S9 VFD Fig 5 MMV Control Mounting...

Page 8: ...8 E3 VFD MMV CONTROL E3 VFD MMV CONTROL Fig 6 MMV Control Mounting with 25 Hp 575 v E3 VFD Fig 7 MMV Control Mounting with 30 or 40 Hp 575 v E3 VFD StockC heck com Downloaded from StockCheck com...

Page 9: ...MMPT 230 3 60 SHOWN REFER TO TABLE 4 FOR ALTERNATE VOLTAGE CONNECTIONS A B C TB YEL RED BLK RED BLU 11 12 13 22 23 21 Fig 8 Motormaster V Accessory Wiring 48 50A2 A3 A4 A5 AJ AK AW AY020 035 Units Fi...

Page 10: ...he control box and run them through the opening of the cable tray on the back of the control box where existing transducer cables come out Route wires along bottom edge of back of control box and up t...

Page 11: ...230 3 60 SHOWN REFER TO TABLE 4 FOR ALTERNATE VOLTAGE CONNECTIONS FR A OFC3 13 14 C1 C2 ADD FAN RELAY FR A IN PARALLEL WITH OFC3 MMF A BLU YEL A B C TB BLU RED BLK GRN YEL DRAIN RED BLK BLU RED BLK G...

Page 12: ...n ap proximately 200 psig liquid line pressure for R 22 units and 320 psig for R 410A units Above that pressure the fan should operate at full speed The Motormaster V control uses a 0 to 5 vdc signal...

Page 13: ...at low frequencies 0 5 0 5 0 5 P29 Accel boost 0 0 0 0 P30 Slip compensation 0 0 0 0 P31 Preset spd 1 speed if loss of control signal 57 57 47 P32 Preset spd 2 0 0 0 0 P33 Preset spd 3 0 0 0 0 P34 Pr...

Page 14: ...e group is displayed through parameters P50 to P56 and all values are read only These values can be accessed without entering a password Press MODE twice and P50 will appear Press MODE again to displa...

Page 15: ...ltage set P01 appropriately JF Serial Fault Automatic The watchdog timer has timed out indicating that the serial link has been lost Check serial connection computer Check settings for P15 Check setti...

Page 16: ...any time specifications or designs without notice and without incurring obligations Catalog No 04 53480084 01 Printed in U S A Form 48 50A 14SI Pg 16 3 11 Replaces 48 50A 10SI Copyright 2011 Carrier...

Reviews: