Table 5 — Program Parameters for the Operating Mode

LEGEND

PARAMETERS

DESCRIPTION

MODE 1

MODE 2

MODE 4

P01

Line Voltage: 01 = low line, 02 = high line 

01

02

02

P02

Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz

01

01

01

P03

Startup mode: flying restart

06

06

06

P04

Stop mode: coast to stop

01

01

01

P05

Standard Speed source: 01 = keypad, 04 = 4-20mA (NO PI), 05 = R22 or R410A,
06 = R134a

05

05

05

P06

TB-14 output: 01 = none

01

01

01

P08

TB-30 output: 01 = none

01

01

01

P09

TB-31 Output: 01 = none

01

01

01

P10

TB-13A function sel: 01 = none

01

01

01

P11

TB-13B function sel: 01 = none

01

01

01

P12

TB-13C function sel: 01 = none

01

01

01

P13

TB-15 output: 01 = none

01

01

01

P14

Control: 01 = Terminal strip 

01

01

01

P15

Serial link: 02 = enabled 9600,8,N,2 with timer

02

02

02

P16

Units editing: 02 = whole units

02

02

02

P17

Rotation: 01 = forward only, 03 = reverse only 

01

01

01

P19

Acceleration time: 20 sec

20

20

20

P20

Deceleration time: 10 sec

10

10

10

P21

DC brake time: 0

0

0

0

P22

DC BRAKE VOLTAGE 0%

0

0

0

P23

Min freq = 8 Hz ~ 100 – 160 rpm

8

8

8

P24

Max freq

60

60

50

P25

Current limit: (%)

125

110

110

P26

Motor overload: 100

100

100

100

P27

Base freq: 60 or 50 Hz

60

60

50

P28

Fixed boost: 0.5% at low frequencies

0.5

0.5

0.5

P29

Accel boost: 0%

0

0

0

P30

Slip compensation: 0%

0

0

0

P31

Preset spd #1: speed if loss of control signal

57

57

47

P32

Preset spd #2: 0

0

0

0

P33

Preset spd #3: 0 

0

0

0

P34

Preset spd 4 default — R22 setpoint. TB12-2 open

24.0

24.0

24.0

P35

Preset spd 5 default — R134a setpoint. TB12-2 closed

12.6

12.6

12.6

P36

Preset spd 6 default

0

0

0

P37

Preset spd 7 default

0

0

0

P38

Skip bandwidth

0

0

0

P39

Speed scaling

0

0

0

P40

Frequency scaling 50 or 60 Hz

60

60

50

P41

Load scaling: default (not used so NA)

200

200

200

P42

Accel/decel #2: default (not used so NA)

60

60

60

P43

Serial address

1

1

1

P44

Password:111 

111

111

111

P45

Speed at min signal: 8 Hz; used when PID mode is disabled and 4-20 mA input is
at 4 mA

8

8

8

P46

Speed at max feedback: 60 or 50 Hz. Used when PID disabled and 4-20 mA input is
at 20 mA

60

60

50

P47

Clear history? 01 = maintain. (set to 02 to clear)

01

01

01

P48

Program selection: Program 1 – 12

01

02

04

P61

PI Mode: 05 = reverse, 0-5V, 01 = no PID

05

05

05

P62

Min feedback = 0 (0V *10)

0

0

0

P63

Max feedback = 50 (5V * 10)

50

50

50

P64

Proportional gain = 3.5%

3.5

3.5

3.5

P65

Integral gain = .2

.2

.2

.2

P66

PI accel/decel (setpoint change filter) = 10

10

10

10

P67

Min alarm

0

0

0

P68

Max alarm

0

0

0

NA

Not Applicable

PI

Proportional Integral

PID —

Proportional Integral Derivative

StockCheck.com

Downloaded from StockCheck.com

Summary of Contents for MOTORMASTER CRLOWAMB018A00

Page 1: ...motor speed in response to varying liquid refrigerant pressure A properly applied Motormaster V control extends the operating range of air conditioning systems and permits operation at lower outdoor a...

Page 2: ...Class CC HY10KB200 3 Fuse 30A KTK R Class CC HY10KB300 3 Harness Assembly 48EJ403106 2 Harness Assembly 48EJ402454 Harness Assembly 48EJ402298 Label 48EJ503269 Transducer HK05YZ007 Transducer Harness...

Page 3: ...HR46TN001 2 Controller 460 V 2 Hp HR46TN002 2 Controller 575 V 2 Hp HR46TN003 2 Enclosure 30RA500381 Enclosure Cover 30RA500519 Enclosure Mounting Bracket 50EJ500656 Fan Relay HN61KK035 2 Relay Base...

Page 4: ...LEGEND MCHX Microchannel Heat Exchanger RTPF Round Tube Plate Fin Heat Exchanger UNIT SIZE QUANTITY DIMENSION A in mm 020 035 1 78 125 0 125 1984 3 036 050 2 78 125 0 125 1984 3 051 060 2 118 0 125 29...

Page 5: ...he existing OFM wire harnesses and strip insulation back 1 2 inch Attach 16 gage black red and blue field supplied wires to the corresponding colors of both OFM harnesses with a wire nut Connect black...

Page 6: ...51 060 RTPF 1 MMV 2 3 Shut OFF at 55 F and turn ON at 65 F outdoor air temperature 4 5 6 060 MCHX 1 MMV B 2 Shut OFF at 55 F and turn ON at 65 F outdoor air temperature 3 MMV A 4 Shut OFF at 55 F and...

Page 7: ...OCK Fig 4 Fuse Block and Fan Relay Mounting cont 48 50A2 A3 A4 A5 AJ AK AW AY036 051 AND 060 RTPF 48 50A2 A3 A4 A5 AJ AK AW AY060 MCHX a48 8404 MMV CONTROL ACH550 OR S9 VFD Fig 5 MMV Control Mounting...

Page 8: ...8 E3 VFD MMV CONTROL E3 VFD MMV CONTROL Fig 6 MMV Control Mounting with 25 Hp 575 v E3 VFD Fig 7 MMV Control Mounting with 30 or 40 Hp 575 v E3 VFD StockC heck com Downloaded from StockCheck com...

Page 9: ...MMPT 230 3 60 SHOWN REFER TO TABLE 4 FOR ALTERNATE VOLTAGE CONNECTIONS A B C TB YEL RED BLK RED BLU 11 12 13 22 23 21 Fig 8 Motormaster V Accessory Wiring 48 50A2 A3 A4 A5 AJ AK AW AY020 035 Units Fi...

Page 10: ...he control box and run them through the opening of the cable tray on the back of the control box where existing transducer cables come out Route wires along bottom edge of back of control box and up t...

Page 11: ...230 3 60 SHOWN REFER TO TABLE 4 FOR ALTERNATE VOLTAGE CONNECTIONS FR A OFC3 13 14 C1 C2 ADD FAN RELAY FR A IN PARALLEL WITH OFC3 MMF A BLU YEL A B C TB BLU RED BLK GRN YEL DRAIN RED BLK BLU RED BLK G...

Page 12: ...n ap proximately 200 psig liquid line pressure for R 22 units and 320 psig for R 410A units Above that pressure the fan should operate at full speed The Motormaster V control uses a 0 to 5 vdc signal...

Page 13: ...at low frequencies 0 5 0 5 0 5 P29 Accel boost 0 0 0 0 P30 Slip compensation 0 0 0 0 P31 Preset spd 1 speed if loss of control signal 57 57 47 P32 Preset spd 2 0 0 0 0 P33 Preset spd 3 0 0 0 0 P34 Pr...