COMPRESSOR INTERNAL RELIEF
The compressor is protected by an internal pressure relief (IPR)

which relieves discharge gas into compressor shell when
differential between suction and discharge pressures exceeds 550 --

625 psi. The compressor is also protected by an internal overload

attached to motor windings.
TEMPERATURE THERMISTORS
Thermistors are electronic devices which sense temperature. As the
temperature increases, the resistance decreases. Thermistors are

used to sense outdoor ambient (OAT) and coil temperature (OCT).

Refer to Fig. 21 for resistance values versus temperature. See Fig.
22 for OCT location.
If the outdoor ambient or coil thermistor should fail, the HP/AC
control will flash the appropriate fault code (See Table 2).

IMPORTANT

: Coil thermistor is factory mounted. Check to

insure thermistor is mounted properly. Outdoor air thermistor
(OAT) is field mounted and connected. Verify that the OAT has
been properly installed.

0

10

20

30

40

50

60

70

80

90

0

20

40

60

80

100

120

TEMPERATURE (DEG. F)

RESISTANCE (KOHMS)

THERMISTOR CURVE

A91431

Fig. 21 -- Resistance Values Versus Temperature

THERMISTOR SENSOR COMPARISON
The control continuously monitors and compares the outdoor air
temperature sensor and outdoor coil temperature sensor to ensure

proper operating conditions. The comparison is:

S

In cooling mode, if the outdoor air sensor indicates

10

_

F

(--12

°

C) warmer than the coil sensor (or) the outdoor air sensor

indicates

20

_

F (--7

°

C) cooler than the coil sensor, the sensors are

out of range.

S

In heating

i

f the outdoor air sensor indicates

35

_

F (2

°

C)

warmer than the coil sensor (or) the outdoor air sensor indicates

10

_

F (--12

°

C) cooler than the coil sensor, the sensors are out of

range.

If the sensors are out of range, the control will flash the appropriate
fault code as shown in Table 2.
The thermistor comparison is not performed during low ambient

cooling operation.
FAILED THERMISTOR DEFAULT OPERATION
Factory defaults have been provided in the event of failure of
outdoor air thermistor and/or coil thermistor.

If the OAT sensor should fail, low ambient cooling will not be
allowed and the one--minute outdoor fan off delay will not occur.

Defrost will be initiated based on coil temperature and time.
If the OCT sensor should fail, low ambient cooling will not be

allowed. Defrost will occur at each time interval during heating

operation, but will terminate after 5 minutes.
If there is a thermistor out of range error, defrost will occur at each

time interval during heating operation, but will terminate after 5
minutes.
Refer to the Troubleshooting Chart (Table 7) for additional

troubleshooting information.

A06311

Fig. 22 -- Outdoor Coil Thermistor (OCT) Attachment

FINAL CHECKS

IMPORTANT

: Before leaving job, be sure to do the following:

1. Ensure that all wiring is routed away from tubing and sheet

metal edges to prevent rub--through or wire pinching.

2. Ensure that all wiring and tubing is secure in unit before

adding panels and covers. Securely fasten all panels and
covers.

3. Tighten service valve stem caps to 1/2--turn past finger

tight.

4. Leave Users Manual with owner. Explain system operation

and periodic maintenance requirements outlined in manual.

5. Fill out Dealer Installation Checklist and place in customer

file.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible

equipment failure, periodic maintenance must be performed on this
equipment.
Frequency of maintenance may vary depending upon geographic

areas, such as coastal applications. See Users Manual for
information.

50X

T

--

A

Summary of Contents for Infinity 15 SEER 50XT-A

Page 1: ...round Lead to Ground Screw 9 Routing Control Power Wires 11 Accessory Installation 11 Special Procedures for 208 v Operation 12 PRE START UP 13 START UP 13 20 Unit Start Up 13 Sequence of Operation 17...

Page 2: ...ckaged heat pump is fully self contained and designed for outdoor installation See Fig 1 Standard units are shipped in a horizontal discharge configuration for installation on a rooftop or a cement sl...

Page 3: ...it basepan Anchor screw A09090 A09095 A09096 A09094 A09097 UNIT SIZE CATALOG NUMBER A IN mm B small base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm Small or Large CPRFCURB010A00 11 279 1...

Page 4: ...4 A09128 Fig 5 50XT A24 30 Unit Dimensions 50XT A...

Page 5: ...5 A09129 Fig 6 50XT A36 60 Unit Dimensions 50XT A...

Page 6: ...es INSPECTION Prior to initial use and at monthly intervals all rigging shackles clevis pins and straps should be visually inspected for any damage evidence of wear structural deformation or cracks Pa...

Page 7: ...tween the unit and the conditioned space If a 90 degree elbow cannot be installed then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditio...

Page 8: ...sposal methods comply with local codes restrictions and practices The units dispose of condensate through a 3 4 in NPT female fitting that exits on the compressor end of the unit Condensate water can...

Page 9: ...age that could affect warranty UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the unit being installed 1 Make all electrical connections in accordance with NEC NFP...

Page 10: ...Cfm Comfort Variable based on Comfort Settings see User Interface instructions for more information Efficiency 700 875 1050 1225 1400 1750 Max 800 1000 1200 1400 1600 2000 Size in mm 10x10 254x254 10x...

Page 11: ...e F1 on Fig 15 The C circuit of transformer circuit is referenced to chassis ground through a printed circuit run at SEC2 and metal control board mounting eyelets Check to be sure control board is mou...

Page 12: ...Fig 14 SPECIAL PROCEDURES FOR 208 V OPERATION Be sure unit disconnect switch is open Disconnect the yellow primary lead from the transformer See unit wiring label See Fig 17 Connect the yellow primary...

Page 13: ...ng conditions a Make sure that outdoor fan blade is correctly positioned in fan orifice See Fig 20 b Make sure that condensate drain pan and trap are filled with water to ensure proper drainage c Make...

Page 14: ...ment fuse If COMM LED does not light within proper time period and status code is displayed 1 Check system wiring to be sure UI is powered and connections are made A to A B to B etc and wiring is not...

Page 15: ...15 A09092 Fig 17 Wiring Schematic 50XT A Single Phase 50XT A...

Page 16: ...ed off The MOTOR LED will not flash to indicate communications when it is turned off Fan coil control is constantly communicating with the motor even when the motor and MOTOR LED are off If motor does...

Page 17: ...but may cause the low voltage fuse to open STATUS CODE 46 BROWNOUT CONDITION If the secondary voltage of the transformer falls below 15 vac for a period exceeding 4 seconds Status Code 46 will be dis...

Page 18: ...trip or start relay not releasing if installed Contactor Shorted 73 Compressor voltage sensed when no demand for compressor op eration exists Contactor may be stuck closed or there is a wiring error...

Page 19: ...when outdoor coil temp is outdoor air temperature plus 3_F 1 6 C or outdoor fan has been ON for 30 minutes Fan is turned off to allow refrigerant system to stabilize S In low stage fan is off when out...

Page 20: ...d adjustment to the specified factory charge must always be very minimal If a substantial adjustment is indicated an abnormal condition exists somewhere in the cooling system such as insufficient airf...

Page 21: ...21 A06297 Fig 18 Non Communicating Emergency Cooling Heating Wiring Connections A09109 Fig 19 Cooling Charging Table Subcooling 50XT A...

Page 22: ...To ensure continuing high performance and to minimize the possibility of premature equipment failure periodic maintenance must be performed on this equipment This packaged air conditioner unit should...

Page 23: ...ll obstructions to ensure proper cooling operation Never place articles on top of the unit CAUTION 1 Remove 4 screws holding outdoor grille and motor to top cover 2 Turn motor grille assembly upside d...

Page 24: ...land scroll compressor uses Mobil 3MA POE oil This is the only oil allowed for oil recharge Step 11 Refrigerant System This step covers the refrigerant system of the 50XT A including the compressor oi...

Page 25: ...Table 2 The control board should be replaced BROWN OUT PROTECTION If the line voltage is less than 187v for at least 4 seconds the appropriate compressor contactor and fan relay are de energized Compr...

Page 26: ...e sensors are out of range If the sensors are out of range the control will flash the appropriate fault code as shown in Table 2 The thermistor comparison is not performed during low ambient cooling o...

Page 27: ...psig low side retard S Use hoses with minimum 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oil...

Page 28: ...r Unit undersized for load Decrease load or increase unit size UI temperature set too low too high Reset UI setting Low refrigerant charge Locate leak repair and recharge Air in system Recover refrige...

Page 29: ...TIGHTNESS MAKE SURE THAT If Applicable ON 60 SIZE PURON HEAT PUMP ONLY THE TWO WIRE TIES FASTEN TO THE OUTDOOR COILS AND REVERSING VALVE ACCUMULATOR HAVE BEEN REMOVED III START UP ELECTRICAL SUPPLY V...

Page 30: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 03 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Reviews: