Carrier Infinity 15 SEER 50XT-A Installation Instructions Manual Download Page 6

6

Step 3 — Provide Clearances

The required minimum service clearances are shown in Fig. 5 and
6. Adequate ventilation and outdoor air must be provided. The

outdoor fan draws air through the outdoor coil and discharges it

through the top fan grille. Be sure that the fan discharge does not
recirculate to the outdoor coil. Do not locate the unit in either a

corner or under an overhead obstruction. The minimum clearance
under a partial overhang (such as a normal house overhang) is 48

in. (1219 mm) above the unit top. The maximum horizontal
extension of a partial overhang must not exceed 48 in. (1219 mm).

IMPORTANT

: Do not restrict outdoor airflow. An air restriction

at either the outdoor--air inlet or the fan discharge may be
detrimental to compressor life.
Do not place the unit where water, ice, or snow from an overhang

or roof will damage or flood the unit. Do not install the unit on
carpeting or other combustible materials. Slab--mounted units

should be at least 4 in. (102 mm) above the highest expected water
and runoff levels. Do not use unit if it has been under water.

Step 4 — Rig and Place Unit

Rigging and handling of this equipment can be hazardous for
many reasons due to the installation location (roofs, elevated

structures, etc.).
Only trained, qualified crane operators and ground support staff

should handle and install this equipment.
When working with this equipment, observe precautions in the

literature, on tags, stickers, and labels attached to the equipment,

and any other safety precautions that might apply.
Training for operators of the lifting equipment should include, but

not be limited to, the following:

1. Application of the lifter to the load, and adjustment of the

lifts to adapt to various sizes or kinds of loads.

2. Instruction in any special operation or precaution.
3. Condition of the load as it relates to operation of the lifting

kit, such as balance, temperature, etc.

Follow all applicable safety codes. Wear safety shoes and work

gloves.
INSPECTION
Prior to initial use, and at monthly intervals, all rigging shackles,
clevis pins, and straps should be visually inspected for any damage,

evidence of wear, structural deformation, or cracks. Particular

attention should be paid to excessive wear at hoist hooking points
and load support areas. Materials showing any kind of wear in

these areas must not be used and should be discarded.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing or servicing system, always turn off main

power to system. There may be more than one disconnect

switch. Turn off accessory heater power switch if

applicable. Tag disconnect switch with a suitable warning

label.

!

WARNING

UNIT FALLING HAZARD

Failure to follow this warning could result in personal

injury or death.
Never stand beneath rigged units or lift over people.

!

WARNING

Rigging/Lifting of Unit

UNIT FALLING HAZARD

Failure to follow this warning could result in personal

injury or death.
Large base units must be secured to common curb before

allowing full weight of unit to rest on curb. Install screws

through curb into unit base rails while rigging crane is still

supporting unit.

!

WARNING

Lifting holes are provided in base rails as shown in Fig. 5 and 6.

1. Leave top shipping skid on the unit for use as a spreader bar

to prevent the rigging straps from damaging the unit. If the

skid is not available, use a spreader bar of sufficient length
to protect the unit from damage.

2. Attach shackles, clevis pins, and straps to the base rails of

the unit. Be sure materials are rated to hold the weight of the
unit (See Fig. 7).

3. Attach a clevis of sufficient strength in the middle of the

straps. Adjust the clevis location to ensure unit is lifted level

with the ground.

4. After unit is placed on the roof curb or mounting pad,

remove the top skid.

UNIT FALLING HAZARD

Failure to follow this warning could result in personal

injury/death or property damage.
When straps are taut, the clevis should be a minimum of 36

in. (914 mm) above the unit top cover.

!

WARNING

After the unit is placed on the roof curb or mounting pad, remove
the top crating.

50X

T

--

A

Summary of Contents for Infinity 15 SEER 50XT-A

Page 1: ...round Lead to Ground Screw 9 Routing Control Power Wires 11 Accessory Installation 11 Special Procedures for 208 v Operation 12 PRE START UP 13 START UP 13 20 Unit Start Up 13 Sequence of Operation 17...

Page 2: ...ckaged heat pump is fully self contained and designed for outdoor installation See Fig 1 Standard units are shipped in a horizontal discharge configuration for installation on a rooftop or a cement sl...

Page 3: ...it basepan Anchor screw A09090 A09095 A09096 A09094 A09097 UNIT SIZE CATALOG NUMBER A IN mm B small base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm Small or Large CPRFCURB010A00 11 279 1...

Page 4: ...4 A09128 Fig 5 50XT A24 30 Unit Dimensions 50XT A...

Page 5: ...5 A09129 Fig 6 50XT A36 60 Unit Dimensions 50XT A...

Page 6: ...es INSPECTION Prior to initial use and at monthly intervals all rigging shackles clevis pins and straps should be visually inspected for any damage evidence of wear structural deformation or cracks Pa...

Page 7: ...tween the unit and the conditioned space If a 90 degree elbow cannot be installed then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditio...

Page 8: ...sposal methods comply with local codes restrictions and practices The units dispose of condensate through a 3 4 in NPT female fitting that exits on the compressor end of the unit Condensate water can...

Page 9: ...age that could affect warranty UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the unit being installed 1 Make all electrical connections in accordance with NEC NFP...

Page 10: ...Cfm Comfort Variable based on Comfort Settings see User Interface instructions for more information Efficiency 700 875 1050 1225 1400 1750 Max 800 1000 1200 1400 1600 2000 Size in mm 10x10 254x254 10x...

Page 11: ...e F1 on Fig 15 The C circuit of transformer circuit is referenced to chassis ground through a printed circuit run at SEC2 and metal control board mounting eyelets Check to be sure control board is mou...

Page 12: ...Fig 14 SPECIAL PROCEDURES FOR 208 V OPERATION Be sure unit disconnect switch is open Disconnect the yellow primary lead from the transformer See unit wiring label See Fig 17 Connect the yellow primary...

Page 13: ...ng conditions a Make sure that outdoor fan blade is correctly positioned in fan orifice See Fig 20 b Make sure that condensate drain pan and trap are filled with water to ensure proper drainage c Make...

Page 14: ...ment fuse If COMM LED does not light within proper time period and status code is displayed 1 Check system wiring to be sure UI is powered and connections are made A to A B to B etc and wiring is not...

Page 15: ...15 A09092 Fig 17 Wiring Schematic 50XT A Single Phase 50XT A...

Page 16: ...ed off The MOTOR LED will not flash to indicate communications when it is turned off Fan coil control is constantly communicating with the motor even when the motor and MOTOR LED are off If motor does...

Page 17: ...but may cause the low voltage fuse to open STATUS CODE 46 BROWNOUT CONDITION If the secondary voltage of the transformer falls below 15 vac for a period exceeding 4 seconds Status Code 46 will be dis...

Page 18: ...trip or start relay not releasing if installed Contactor Shorted 73 Compressor voltage sensed when no demand for compressor op eration exists Contactor may be stuck closed or there is a wiring error...

Page 19: ...when outdoor coil temp is outdoor air temperature plus 3_F 1 6 C or outdoor fan has been ON for 30 minutes Fan is turned off to allow refrigerant system to stabilize S In low stage fan is off when out...

Page 20: ...d adjustment to the specified factory charge must always be very minimal If a substantial adjustment is indicated an abnormal condition exists somewhere in the cooling system such as insufficient airf...

Page 21: ...21 A06297 Fig 18 Non Communicating Emergency Cooling Heating Wiring Connections A09109 Fig 19 Cooling Charging Table Subcooling 50XT A...

Page 22: ...To ensure continuing high performance and to minimize the possibility of premature equipment failure periodic maintenance must be performed on this equipment This packaged air conditioner unit should...

Page 23: ...ll obstructions to ensure proper cooling operation Never place articles on top of the unit CAUTION 1 Remove 4 screws holding outdoor grille and motor to top cover 2 Turn motor grille assembly upside d...

Page 24: ...land scroll compressor uses Mobil 3MA POE oil This is the only oil allowed for oil recharge Step 11 Refrigerant System This step covers the refrigerant system of the 50XT A including the compressor oi...

Page 25: ...Table 2 The control board should be replaced BROWN OUT PROTECTION If the line voltage is less than 187v for at least 4 seconds the appropriate compressor contactor and fan relay are de energized Compr...

Page 26: ...e sensors are out of range If the sensors are out of range the control will flash the appropriate fault code as shown in Table 2 The thermistor comparison is not performed during low ambient cooling o...

Page 27: ...psig low side retard S Use hoses with minimum 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oil...

Page 28: ...r Unit undersized for load Decrease load or increase unit size UI temperature set too low too high Reset UI setting Low refrigerant charge Locate leak repair and recharge Air in system Recover refrige...

Page 29: ...TIGHTNESS MAKE SURE THAT If Applicable ON 60 SIZE PURON HEAT PUMP ONLY THE TWO WIRE TIES FASTEN TO THE OUTDOOR COILS AND REVERSING VALVE ACCUMULATOR HAVE BEEN REMOVED III START UP ELECTRICAL SUPPLY V...

Page 30: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 03 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Reviews: