background image

17

STATUS CODE 36, HEATER OUTPUT NOT SENSED WHEN
ENERGIZED
Fan coil control is provided with circuitry to detect presence of a
24--vac signal on electric heater stage 1 and stage 2 outputs.
If fan coil control energizes either heater stage and does not detect

the 24--vac signal on output, Status Code 36 will be displayed on
the STATUS LED, control will continue to energize heater

output(s) and adjust blower operation to a safe airflow level for
energized electric heat stage(s).
To find the fault:

1. Check for 24--vac on heater stage outputs. Fan coil control

or sensing circuit may be bad.

NOTE

:

It may be useful as an electric heater troubleshooting

procedure to disconnect the system communications to force Status
Code 16 enabling of emergency heat mode. It is difficult to know
which heater output is energized or not energized in normal
operation. When unit is operated in emergency heat mode using
electric heaters, both outputs are energized and de--energized
together. Terminal strip inputs to fan coil control can then be
connected R to W to turn on both electric heat outputs. Heater
output sensing circuits can then be checked to resolve Status Code
36 or 37 problems.
STATUS CODE 41, BLOWER MOTOR FAULT
If MOTOR LED is lit and flashing and motor does not run:

1. Check STATUS LED. If STATUS LED is indicating Status

Code 41, motor control has detected that the motor will not

come up to speed within 30 seconds of being commanded
to run or that the motor has been slowed to below 250 rpm

for more than 10 seconds after coming up to speed. Motor
wiring harness and fan coil control are operating properly,
do not replace.

2. Check to be sure that the blower wheel is not rubbing the

housing.

3. Check motor to be sure that the motor shaft is not seized

(motor control module must be removed and electronics

disconnected from windings to perform this check
properly).

4. Check motor windings section following instructions in

Section C, Indoor Fan Motor Troubleshooting.

If all these checks are normal, the motor control module may need

replacement.
STATUS CODE 16, SYSTEM COMMUNICATION FAULT
If, at any time, system communications are not successful for a

period exceeding 2 minutes, the fan coil control will only allow
emergency heating or cooling operation using a common

thermostat, and the terminal strip connections and will display
Status

code

16

on

the

amber

STATUS

LED

(see

Non--Communicating Emergency Cooling/Heating Mode). No
further unit troubleshooting information will be available at the UI

until communications are re--established.
Check system wiring to be sure the UI is powered and connections
are made A to A, B to B, etc., and wiring is not shorted.

Mis--wiring or shorting of the ABCD communications wiring will
not allow successful communications. Correcting wiring faults will

clear the code and re--establish communications.
Shorting or mis--wiring the low voltage system wiring will not
cause damage to unit control or to UI but may cause the low

voltage fuse to open.
STATUS CODE 46, BROWNOUT CONDITION
If the secondary voltage of the transformer falls below 15--vac for a

period exceeding 4 seconds, Status Code 46 will be displayed on
STATUS LED and the UI will command the control board to turn

off compressor.
When secondary voltage rises above 17--vac for more than 4

seconds, the brownout condition is cleared and normal system

operation will resume subject to any minimum compressor
off--delay function which may be in effect. Brownout does not

affect blower or electric heater operation.
STATUS CODE 53, OUTDOOR AIR TEMPERATURE

SENSOR FAULT
If an OAT sensor is found at power--up, input is constantly checked
to be within a valid temperature range. If sensor is found to be

open or shorted at any time after initial validation, Status Code 53
will be displayed at amber STATUS LED.
Check for faults in wiring connecting sensor to OAT terminals.

Using an Ohm meter, check resistance of thermistor for a short or
open condition.
If thermistor is shorted or open, replace it to return the system to
normal operation. If fault is in the wiring connections, correcting

the fault will clear the code and return the system to normal

operation.
NOTE: If fault condition is an open thermistor or a wiring problem

that appears to be an open thermistor and the power to the unit is
cycled off, the fault code will be cleared on the next power--up but

the fault will remain and system operation will not be as expected.

This is because on power--up, the unit control cannot discern

the difference between an open sensor or if a sensor is not

installed.

F. HP/AC Control Troubleshooting

See Table 2 for HP/AC control board status codes and
troubleshooting information.

Step 2 — Sequence of Operation

The 50XT--A packaged heat pump is designed for installation with
a communicating UI. This unit will not respond to commands

provided by a common thermostat except under certain emergency

situations described in Step 1—Start--Up.
The UI uses temperature, humidity and other data supplied from

indoor and outdoor system components to control heating or
cooling system for optimum comfort. The unit will be commanded

by UI to supply airflow. The unit will operate the indoor fan at

requested airflow for most modes.
The nominal requested airflow will be 350 cfm per ton of nominal

cooling capacity as defined by unit size. Actual airflow request will
be adjusted from nominal using indoor and outdoor temperature

and indoor humidity data to optimize the system operation for

occupant comfort and system efficiency. Refer to UI literature for
further system control details.
Airflow during electric heater operation must be greater than a
minimum level for safe operation. If UI instructs unit to turn on

electric heat and the requested airflow is less than the minimum
level the fan coil control will override requested value.

NOTE

: Once the compressor has started and then has stopped, it

should not be started again until 4 minutes have elapsed. The
cooling cycle remains “on” until the room temperature drops to
point that is slightly below the cooling control setting of the UI.

50X

T

--

A

Summary of Contents for Infinity 15 SEER 50XT-A

Page 1: ...round Lead to Ground Screw 9 Routing Control Power Wires 11 Accessory Installation 11 Special Procedures for 208 v Operation 12 PRE START UP 13 START UP 13 20 Unit Start Up 13 Sequence of Operation 17...

Page 2: ...ckaged heat pump is fully self contained and designed for outdoor installation See Fig 1 Standard units are shipped in a horizontal discharge configuration for installation on a rooftop or a cement sl...

Page 3: ...it basepan Anchor screw A09090 A09095 A09096 A09094 A09097 UNIT SIZE CATALOG NUMBER A IN mm B small base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm Small or Large CPRFCURB010A00 11 279 1...

Page 4: ...4 A09128 Fig 5 50XT A24 30 Unit Dimensions 50XT A...

Page 5: ...5 A09129 Fig 6 50XT A36 60 Unit Dimensions 50XT A...

Page 6: ...es INSPECTION Prior to initial use and at monthly intervals all rigging shackles clevis pins and straps should be visually inspected for any damage evidence of wear structural deformation or cracks Pa...

Page 7: ...tween the unit and the conditioned space If a 90 degree elbow cannot be installed then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditio...

Page 8: ...sposal methods comply with local codes restrictions and practices The units dispose of condensate through a 3 4 in NPT female fitting that exits on the compressor end of the unit Condensate water can...

Page 9: ...age that could affect warranty UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the unit being installed 1 Make all electrical connections in accordance with NEC NFP...

Page 10: ...Cfm Comfort Variable based on Comfort Settings see User Interface instructions for more information Efficiency 700 875 1050 1225 1400 1750 Max 800 1000 1200 1400 1600 2000 Size in mm 10x10 254x254 10x...

Page 11: ...e F1 on Fig 15 The C circuit of transformer circuit is referenced to chassis ground through a printed circuit run at SEC2 and metal control board mounting eyelets Check to be sure control board is mou...

Page 12: ...Fig 14 SPECIAL PROCEDURES FOR 208 V OPERATION Be sure unit disconnect switch is open Disconnect the yellow primary lead from the transformer See unit wiring label See Fig 17 Connect the yellow primary...

Page 13: ...ng conditions a Make sure that outdoor fan blade is correctly positioned in fan orifice See Fig 20 b Make sure that condensate drain pan and trap are filled with water to ensure proper drainage c Make...

Page 14: ...ment fuse If COMM LED does not light within proper time period and status code is displayed 1 Check system wiring to be sure UI is powered and connections are made A to A B to B etc and wiring is not...

Page 15: ...15 A09092 Fig 17 Wiring Schematic 50XT A Single Phase 50XT A...

Page 16: ...ed off The MOTOR LED will not flash to indicate communications when it is turned off Fan coil control is constantly communicating with the motor even when the motor and MOTOR LED are off If motor does...

Page 17: ...but may cause the low voltage fuse to open STATUS CODE 46 BROWNOUT CONDITION If the secondary voltage of the transformer falls below 15 vac for a period exceeding 4 seconds Status Code 46 will be dis...

Page 18: ...trip or start relay not releasing if installed Contactor Shorted 73 Compressor voltage sensed when no demand for compressor op eration exists Contactor may be stuck closed or there is a wiring error...

Page 19: ...when outdoor coil temp is outdoor air temperature plus 3_F 1 6 C or outdoor fan has been ON for 30 minutes Fan is turned off to allow refrigerant system to stabilize S In low stage fan is off when out...

Page 20: ...d adjustment to the specified factory charge must always be very minimal If a substantial adjustment is indicated an abnormal condition exists somewhere in the cooling system such as insufficient airf...

Page 21: ...21 A06297 Fig 18 Non Communicating Emergency Cooling Heating Wiring Connections A09109 Fig 19 Cooling Charging Table Subcooling 50XT A...

Page 22: ...To ensure continuing high performance and to minimize the possibility of premature equipment failure periodic maintenance must be performed on this equipment This packaged air conditioner unit should...

Page 23: ...ll obstructions to ensure proper cooling operation Never place articles on top of the unit CAUTION 1 Remove 4 screws holding outdoor grille and motor to top cover 2 Turn motor grille assembly upside d...

Page 24: ...land scroll compressor uses Mobil 3MA POE oil This is the only oil allowed for oil recharge Step 11 Refrigerant System This step covers the refrigerant system of the 50XT A including the compressor oi...

Page 25: ...Table 2 The control board should be replaced BROWN OUT PROTECTION If the line voltage is less than 187v for at least 4 seconds the appropriate compressor contactor and fan relay are de energized Compr...

Page 26: ...e sensors are out of range If the sensors are out of range the control will flash the appropriate fault code as shown in Table 2 The thermistor comparison is not performed during low ambient cooling o...

Page 27: ...psig low side retard S Use hoses with minimum 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oil...

Page 28: ...r Unit undersized for load Decrease load or increase unit size UI temperature set too low too high Reset UI setting Low refrigerant charge Locate leak repair and recharge Air in system Recover refrige...

Page 29: ...TIGHTNESS MAKE SURE THAT If Applicable ON 60 SIZE PURON HEAT PUMP ONLY THE TWO WIRE TIES FASTEN TO THE OUTDOOR COILS AND REVERSING VALVE ACCUMULATOR HAVE BEEN REMOVED III START UP ELECTRICAL SUPPLY V...

Page 30: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 03 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Reviews: