2

SAFETY CONSIDERATIONS

Improper installation adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other

conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your

distributor or branch for information or assistance. The qualified

installer or agency must use factory--authorized kits or accessories
when modifying this product Refer to the individual instructions

packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,

and work gloves. Use quenching cloth for brazing operations.
Have a fire extinguisher available. Read these instructions

thoroughly and follow all warnings or cautions included in

literature and attached to the unit. Consult local building codes, the
current editions of the National Electrical Code (NEC) NFPA 70.
In Canada refer to the current editions of the Canadian electrical

Code CSA C22.1.

Recognize safety information. This is the safety--alert symbol

.

When you see this symbol on the unit and in instructions or

manuals, be alert to the potential for personal injury. Understand

these signal words; DANGER, WARNING, and CAUTION. These
words are used with the safety--alert symbol. DANGER identifies

the most serious hazards which

will

result in severe personal injury

or death. WARNING signifies hazards which

could

result in

personal injury or death. CAUTION is used to identify unsafe
practices which

may

result in minor personal injury or product and

property damage. NOTE is used to highlight suggestions which

will

result in enhanced installation, reliability, or operation.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing or servicing system, always turn off main

power and tag disconnect to system. There may be more

than one disconnect switch. Turn off accessory heater power

switch if applicable.

!

WARNING

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could result in personal

injury or equipment damage.
Puron (R--410A) systems operate at higher pressures than

standard R--22 systems. DO NOT use R--22 service

equipment or components on Puron (R--410A) equipment.

Ensure service equipment is rated for Puron (R--410A).

WARNING

!

CUT HAZARD

Failure to follow this caution may result in personal injury.
When removing access panels or performing maintenance

functions inside your unit, be aware of sharp sheet metal parts

and screws. Although special care is taken to reduce sharp

edges to a minimum, be extremely careful when handling

parts or reaching into the unit.

!

CAUTION

INTRODUCTION

The 50XT--A packaged heat pump is fully self--contained and

designed for outdoor installation (See Fig. 1). Standard units are
shipped in a horizontal--discharge configuration for installation on

a rooftop, or a cement slab (see Fig. 4 for roof curb details).

Standard units can be converted to downflow (vertical) discharge
configurations for rooftop applications.

RECEIVING AND INSTALLATION

Step 1 — Check Equipment

IDENTIFY UNIT
The unit model number and serial number are printed on the unit

informative plate. Check this information against shipping papers.
INSPECT SHIPMENT
Inspect for shipping damage before removing packaging material.

If unit appears to be damaged or is torn loose from its anchorage,
have it examined by transportation inspectors before removal.

Forward claim papers directly to transportation company.
Manufacturer is not responsible for any damage incurred in transit.

Check all items against shipping list. Immediately notify the

nearest Carrier office if any item is missing. To prevent loss or
damage, leave all parts in original packages until installation.

Step 2 — Provide Unit Support

IMPORTANT

: The unit must be secured to the curb by installing

screws through the bottom of the curb flange and into the unit base
rails. When installing large base units onto the common curb, the
screws must be installed before allowing the full weight of the unit
to rest on the curb. A minimum of six screws are required for large
base units. Failure to secure unit properly could result in an
unstable unit. See Warning near Rigging/Lifting information and
accessory curb instructions for more details.
For hurricane tie downs, contact distributor for details and PE

(Professional Engineering) Certificate, if required.
ROOF CURB
Install accessory roof curb in accordance with instructions shipped

with curb (See Fig. 4). Install insulation, cant strips, roofing, and
flashing. Ductwork must be attached to curb.

IMPORTANT

: The gasketing of the unit to the roof curb is

critical for a water tight seal. Install gasketing material supplied
with the roof curb. Improperly applied gasketing also can result in
air leaks and poor unit performance.
Curb should be level to within 1/4 in. (6.4 mm) (See Fig. 2). This

is necessary for unit drain to function properly. Refer to accessory
roof curb installation instructions for additional information as

required.

A

B

C

MAXIMUM ALLOWABLE

DIFFERENCE in. (mm)

A-C

1/4

1/4

1/4

(6.35)

(6.35)

(6.35)

A-B

B-C

A07925

Fig. 2 -- Unit Leveling Tolerances

SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of 4

in. thick with 2 in. (51 mm) above grade. The slab should extend
approximately 2 in. (51 mm) beyond the casing on all 4 sides of

the unit (See Fig. 3). Do not secure the unit to the slab

except

when

required by local codes.

OPTIONAL

RETURN

AIR

OPENING

OPTIONAL

SUPPLY

AIR

OPENING

EVAP. COIL

COND. COIL

(50.8mm)

A07926

Fig. 3 -- Slab Mounting Detail

50X

T

--

A

Summary of Contents for Infinity 15 SEER 50XT-A

Page 1: ...round Lead to Ground Screw 9 Routing Control Power Wires 11 Accessory Installation 11 Special Procedures for 208 v Operation 12 PRE START UP 13 START UP 13 20 Unit Start Up 13 Sequence of Operation 17...

Page 2: ...ckaged heat pump is fully self contained and designed for outdoor installation See Fig 1 Standard units are shipped in a horizontal discharge configuration for installation on a rooftop or a cement sl...

Page 3: ...it basepan Anchor screw A09090 A09095 A09096 A09094 A09097 UNIT SIZE CATALOG NUMBER A IN mm B small base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm Small or Large CPRFCURB010A00 11 279 1...

Page 4: ...4 A09128 Fig 5 50XT A24 30 Unit Dimensions 50XT A...

Page 5: ...5 A09129 Fig 6 50XT A36 60 Unit Dimensions 50XT A...

Page 6: ...es INSPECTION Prior to initial use and at monthly intervals all rigging shackles clevis pins and straps should be visually inspected for any damage evidence of wear structural deformation or cracks Pa...

Page 7: ...tween the unit and the conditioned space If a 90 degree elbow cannot be installed then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditio...

Page 8: ...sposal methods comply with local codes restrictions and practices The units dispose of condensate through a 3 4 in NPT female fitting that exits on the compressor end of the unit Condensate water can...

Page 9: ...age that could affect warranty UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the unit being installed 1 Make all electrical connections in accordance with NEC NFP...

Page 10: ...Cfm Comfort Variable based on Comfort Settings see User Interface instructions for more information Efficiency 700 875 1050 1225 1400 1750 Max 800 1000 1200 1400 1600 2000 Size in mm 10x10 254x254 10x...

Page 11: ...e F1 on Fig 15 The C circuit of transformer circuit is referenced to chassis ground through a printed circuit run at SEC2 and metal control board mounting eyelets Check to be sure control board is mou...

Page 12: ...Fig 14 SPECIAL PROCEDURES FOR 208 V OPERATION Be sure unit disconnect switch is open Disconnect the yellow primary lead from the transformer See unit wiring label See Fig 17 Connect the yellow primary...

Page 13: ...ng conditions a Make sure that outdoor fan blade is correctly positioned in fan orifice See Fig 20 b Make sure that condensate drain pan and trap are filled with water to ensure proper drainage c Make...

Page 14: ...ment fuse If COMM LED does not light within proper time period and status code is displayed 1 Check system wiring to be sure UI is powered and connections are made A to A B to B etc and wiring is not...

Page 15: ...15 A09092 Fig 17 Wiring Schematic 50XT A Single Phase 50XT A...

Page 16: ...ed off The MOTOR LED will not flash to indicate communications when it is turned off Fan coil control is constantly communicating with the motor even when the motor and MOTOR LED are off If motor does...

Page 17: ...but may cause the low voltage fuse to open STATUS CODE 46 BROWNOUT CONDITION If the secondary voltage of the transformer falls below 15 vac for a period exceeding 4 seconds Status Code 46 will be dis...

Page 18: ...trip or start relay not releasing if installed Contactor Shorted 73 Compressor voltage sensed when no demand for compressor op eration exists Contactor may be stuck closed or there is a wiring error...

Page 19: ...when outdoor coil temp is outdoor air temperature plus 3_F 1 6 C or outdoor fan has been ON for 30 minutes Fan is turned off to allow refrigerant system to stabilize S In low stage fan is off when out...

Page 20: ...d adjustment to the specified factory charge must always be very minimal If a substantial adjustment is indicated an abnormal condition exists somewhere in the cooling system such as insufficient airf...

Page 21: ...21 A06297 Fig 18 Non Communicating Emergency Cooling Heating Wiring Connections A09109 Fig 19 Cooling Charging Table Subcooling 50XT A...

Page 22: ...To ensure continuing high performance and to minimize the possibility of premature equipment failure periodic maintenance must be performed on this equipment This packaged air conditioner unit should...

Page 23: ...ll obstructions to ensure proper cooling operation Never place articles on top of the unit CAUTION 1 Remove 4 screws holding outdoor grille and motor to top cover 2 Turn motor grille assembly upside d...

Page 24: ...land scroll compressor uses Mobil 3MA POE oil This is the only oil allowed for oil recharge Step 11 Refrigerant System This step covers the refrigerant system of the 50XT A including the compressor oi...

Page 25: ...Table 2 The control board should be replaced BROWN OUT PROTECTION If the line voltage is less than 187v for at least 4 seconds the appropriate compressor contactor and fan relay are de energized Compr...

Page 26: ...e sensors are out of range If the sensors are out of range the control will flash the appropriate fault code as shown in Table 2 The thermistor comparison is not performed during low ambient cooling o...

Page 27: ...psig low side retard S Use hoses with minimum 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oil...

Page 28: ...r Unit undersized for load Decrease load or increase unit size UI temperature set too low too high Reset UI setting Low refrigerant charge Locate leak repair and recharge Air in system Recover refrige...

Page 29: ...TIGHTNESS MAKE SURE THAT If Applicable ON 60 SIZE PURON HEAT PUMP ONLY THE TWO WIRE TIES FASTEN TO THE OUTDOOR COILS AND REVERSING VALVE ACCUMULATOR HAVE BEEN REMOVED III START UP ELECTRICAL SUPPLY V...

Page 30: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 03 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Reviews: