background image

20

QUIET SHIFT
Quiet Shift is a field--selectable defrost mode which may eliminate

occasional noise that could be heard at the start of the defrost cycle
and restarting of the heating cycle. This feature must be enabled at

the UI. When activated, the following sequence of operation will

occur. Reversing valve will energize and compressor will turn off
for 30 seconds, then turn back on to complete defrost. At the end

of the defrost cycle, the reversing valve de--energizes, compressor
will turn off for another 30 seconds, and the fan will turn off for 40

seconds, before starting in the heating mode.

Step 3 — Check for Refrigerant Leaks

Locate and repair refrigerant leaks and charge the unit as follows:

1. Use both high-- and low--pressure ports to relieve system

pressure and reclaim remaining refrigerant.

2. Repair leak following accepted practices.

NOTE

: Install a filter drier whenever the system has been opened

for repair.

3. Check system for leaks using an approved method.
4. Evacuate refrigerant system and reclaim refrigerant if no

additional leaks are found.

5. Charge unit with Puron (R--410A) refrigerant, using an

accurate scale. Refer to unit rating plate for required charge.

Step 4 — Start--Up Adjustments

Complete the required procedures given in the Pre--Start--Up

section before starting the unit. Do not jumper any safety devices
when operating the unit. Do not operate the unit in cooling mode

when the outdoor temperature is below 40

°

F (4

_

C) (unless

low--ambient operation is enabled in the UI). Do not rapid cycle
the compressor. Allow 5 min. between “on” cycles to prevent

compressor damage.
CHECKING

COOLING

AND

HEATING

CONTROL

OPERATION
See UI Installation Instructions for detailed system CHECKOUT.
CHECKING AND ADJUSTING REFRIGERANT CHARGE
The refrigerant system is fully charged with Puron (R--410A)
refrigerant and is tested and factory sealed.

NOTE

: Any adjustment to refrigerant charge must be done with

unit operating in HIGH stage.

NOTE

:

Adjustment of the refrigerant charge is not required

unless the unit is suspected of not having the proper R--410A
charge. The charging label and the tables shown refer to system
temperatures and pressures in cooling mode only. A refrigerant
charging label is attached to the outside of the unit. If charge level
is suspect in heating mode, reclaim all refrigerant and charge to
rating plate amount. (This information may be obtained from the
physical data table also.)

IMPORTANT

:

When evaluating the refrigerant charge, an

indicated adjustment to the specified factory charge must always be
very minimal. If a substantial adjustment is indicated, an abnormal

condition exists somewhere in the cooling system, such as
insufficient airflow across either coil or both coils.
REFRIGERANT CHARGE
The amount of refrigerant charge is listed on the unit rating plate

and/or the physical data table. Refer to the Refrigeration Service
Techniques Manual, Refrigerants Section.
NO CHARGE
Check for leak. Use standard evacuating techniques. After

evacuating system, weigh in the specified amount of refrigerant

(refer to system rating plate).
LOW CHARGE COOLING
Use Cooling Charging Chart (Fig. 19). Vary refrigerant until the
conditions of the chart are met. Note that charging charts are

different from type normally used. Charts are based on charging
the units to correct subcooling for the various operating conditions.

Accurate pressure gauge and temperature sensing devices are

required. Connect the pressure gauge to the service port on the
suction line. Mount the temperature sensing device on the suction

line and insulate it so that the outdoor ambient does not affect the
reading. Indoor air CFM must be within the normal operating

range of the unit.
TO USE COOLING CHARGING CHARTS
Take the liquid line temperature and read the manifold pressure

gauges.
Refer to the chart to determine what the liquid line temperature

should be.

NOTE

:

If the problem causing the inaccurate readings is a

refrigerant leak, refer to Check for Refrigerant Leaks section.
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS

NOTE

: Be sure that all supply-- and return--air grilles are open,

free from obstructions, and adjusted properly.
The 50XT--A unit utilizes state of the art ECM (Electronic

Computated Motor) ID Blower Motors. See UI instructions for

detailed information on adjusting airflow.
NON--COMMUNICATING

EMERGENCY

COOLING

/

HEATING MODE
This mode of operation is provided only in the case where the UI

has failed or is otherwise unavailable. If communications cannot be

established with the UI, the Infinity fan coil board will enable the
R, C, Y, O, and W input terminals to allow simple thermostatic

control of the 50XT--A unit.
For control with a standard thermostat, disconnect the ABCD

connectors from both control boards and using No. 18 AWG

color--coded, insulated type 90

°

C minimum or equivalent wire,

make the connections between the standard thermostat, the fan coil

board, and the HP/AC board per Fig. 18. Recommend the use of
interconnecting wire with 105C, 600V, 2/64” insulation.
The Infinity control will respond to cooling and heating demands
with the maximum safe airflow based on electric heat size (if

applicable) and unit capacity.

50X

T

--

A

Summary of Contents for Infinity 15 SEER 50XT-A

Page 1: ...round Lead to Ground Screw 9 Routing Control Power Wires 11 Accessory Installation 11 Special Procedures for 208 v Operation 12 PRE START UP 13 START UP 13 20 Unit Start Up 13 Sequence of Operation 17...

Page 2: ...ckaged heat pump is fully self contained and designed for outdoor installation See Fig 1 Standard units are shipped in a horizontal discharge configuration for installation on a rooftop or a cement sl...

Page 3: ...it basepan Anchor screw A09090 A09095 A09096 A09094 A09097 UNIT SIZE CATALOG NUMBER A IN mm B small base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm Small or Large CPRFCURB010A00 11 279 1...

Page 4: ...4 A09128 Fig 5 50XT A24 30 Unit Dimensions 50XT A...

Page 5: ...5 A09129 Fig 6 50XT A36 60 Unit Dimensions 50XT A...

Page 6: ...es INSPECTION Prior to initial use and at monthly intervals all rigging shackles clevis pins and straps should be visually inspected for any damage evidence of wear structural deformation or cracks Pa...

Page 7: ...tween the unit and the conditioned space If a 90 degree elbow cannot be installed then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditio...

Page 8: ...sposal methods comply with local codes restrictions and practices The units dispose of condensate through a 3 4 in NPT female fitting that exits on the compressor end of the unit Condensate water can...

Page 9: ...age that could affect warranty UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the unit being installed 1 Make all electrical connections in accordance with NEC NFP...

Page 10: ...Cfm Comfort Variable based on Comfort Settings see User Interface instructions for more information Efficiency 700 875 1050 1225 1400 1750 Max 800 1000 1200 1400 1600 2000 Size in mm 10x10 254x254 10x...

Page 11: ...e F1 on Fig 15 The C circuit of transformer circuit is referenced to chassis ground through a printed circuit run at SEC2 and metal control board mounting eyelets Check to be sure control board is mou...

Page 12: ...Fig 14 SPECIAL PROCEDURES FOR 208 V OPERATION Be sure unit disconnect switch is open Disconnect the yellow primary lead from the transformer See unit wiring label See Fig 17 Connect the yellow primary...

Page 13: ...ng conditions a Make sure that outdoor fan blade is correctly positioned in fan orifice See Fig 20 b Make sure that condensate drain pan and trap are filled with water to ensure proper drainage c Make...

Page 14: ...ment fuse If COMM LED does not light within proper time period and status code is displayed 1 Check system wiring to be sure UI is powered and connections are made A to A B to B etc and wiring is not...

Page 15: ...15 A09092 Fig 17 Wiring Schematic 50XT A Single Phase 50XT A...

Page 16: ...ed off The MOTOR LED will not flash to indicate communications when it is turned off Fan coil control is constantly communicating with the motor even when the motor and MOTOR LED are off If motor does...

Page 17: ...but may cause the low voltage fuse to open STATUS CODE 46 BROWNOUT CONDITION If the secondary voltage of the transformer falls below 15 vac for a period exceeding 4 seconds Status Code 46 will be dis...

Page 18: ...trip or start relay not releasing if installed Contactor Shorted 73 Compressor voltage sensed when no demand for compressor op eration exists Contactor may be stuck closed or there is a wiring error...

Page 19: ...when outdoor coil temp is outdoor air temperature plus 3_F 1 6 C or outdoor fan has been ON for 30 minutes Fan is turned off to allow refrigerant system to stabilize S In low stage fan is off when out...

Page 20: ...d adjustment to the specified factory charge must always be very minimal If a substantial adjustment is indicated an abnormal condition exists somewhere in the cooling system such as insufficient airf...

Page 21: ...21 A06297 Fig 18 Non Communicating Emergency Cooling Heating Wiring Connections A09109 Fig 19 Cooling Charging Table Subcooling 50XT A...

Page 22: ...To ensure continuing high performance and to minimize the possibility of premature equipment failure periodic maintenance must be performed on this equipment This packaged air conditioner unit should...

Page 23: ...ll obstructions to ensure proper cooling operation Never place articles on top of the unit CAUTION 1 Remove 4 screws holding outdoor grille and motor to top cover 2 Turn motor grille assembly upside d...

Page 24: ...land scroll compressor uses Mobil 3MA POE oil This is the only oil allowed for oil recharge Step 11 Refrigerant System This step covers the refrigerant system of the 50XT A including the compressor oi...

Page 25: ...Table 2 The control board should be replaced BROWN OUT PROTECTION If the line voltage is less than 187v for at least 4 seconds the appropriate compressor contactor and fan relay are de energized Compr...

Page 26: ...e sensors are out of range If the sensors are out of range the control will flash the appropriate fault code as shown in Table 2 The thermistor comparison is not performed during low ambient cooling o...

Page 27: ...psig low side retard S Use hoses with minimum 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oil...

Page 28: ...r Unit undersized for load Decrease load or increase unit size UI temperature set too low too high Reset UI setting Low refrigerant charge Locate leak repair and recharge Air in system Recover refrige...

Page 29: ...TIGHTNESS MAKE SURE THAT If Applicable ON 60 SIZE PURON HEAT PUMP ONLY THE TWO WIRE TIES FASTEN TO THE OUTDOOR COILS AND REVERSING VALVE ACCUMULATOR HAVE BEEN REMOVED III START UP ELECTRICAL SUPPLY V...

Page 30: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 03 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Reviews: