background image

16

MOTOR TURNS SLOWLY

1. Low static pressure loading of blower while access panel is

removed will cause blower to run slowly. Particularly at low
airflow requests. This is normal, do not assume a fault

exists.

2. Recheck airflow and system static pressure using UI service

screens with access panel in place.

NOTE

: Blower motor faults will not cause a lockout of blower

operation. The fan coil control will attempt to run the blower motor
as long as UI maintains a demand for airflow. The control will not
operate electric heaters while a fault condition exists. The control
communicates with the motor at least once every five seconds,
even when the motor is idle. If, during operation, the control does
not communicate with the motor for more than 25 seconds, the
motor will shut itself down and wait for communications to be
reestablished.

D. Using Fan Coil Control Motor LED in Troubleshooting

The MOTOR LED is connected to the blower motor

communication line and works with the fan coil control
microprocessor and the STATUS LED to provide unit operation

and troubleshooting information. When the motor is commanded

to operate, the MOTOR LED will be turned on and will flash each
time instructions are sent to the motor. When the motor is

commanded to stop, the MOTOR LED will be turned off.
If the MOTOR LED is lit, flashing, and the motor is running, or if

the MOTOR LED is off and the motor is stopped, operation is

normal and no motor fault exists.
If the MOTOR LED is lit, flashing, and the motor does not run, or

if the MOTOR LED is off and the motor is running, check the
STATUS LED for the Status Code. Refer to the troubleshooting

instructions for the indicated Status Code in Section E, Fan Coil
Control Troubleshooting.

E. Fan Coil Control Troubleshooting

Fan coil control faults indicated by flashing codes on the amber

system STATUS LED can be resolved using troubleshooting

information provided below. Codes are listed in order of their
priority, highest to lowest. Though multiple faults can exist at any

time, only the highest priority code will be displayed on STATUS
LED. Clearing the indicated fault when multiple faults exist will

cause the next highest priority Status Code to be flashed. All

existing faults, as well as a fault history, can be viewed at UI.
STATUS CODE 45, CONTROL BOARD TEST FAULT
Fan coil control has failed internal start--up tests and must be
replaced. No other service procedure will correct.
STATUS CODE 37, HEATER OUTPUT SENSED “ON” WHEN

NOT ENERGIZED:
Fan coil control is provided with circuitry to detect presence of a

24--vac signal on electric heater stage 1 and stage 2 outputs.
If fan coil control detects a 24--vac signal on either heater stage

output and it is not supplying signal, Status Code 37 will be
displayed on STATUS LED. Control will turn off output and

command blower motor to supply an airflow determined to be safe

for current operation mode with electric heaters energized.
To find the fault:

1. Stop all system operations at UI and check heater stage

24--vac outputs.

2. Disconnect electric heater at power and check heater wiring

for faults. See Status Code 36 for more information.

STATUS CODE 44, MOTOR COMMUNICATION FAULT
When motor is commanded to operate, the MOTOR LED will be

turned on and will flash each time instructions are sent to the
motor.
When the motor is commanded to stop, the MOTOR LED will be
turned off. The MOTOR LED will not flash to indicate

communications when it is turned off.

Fan coil control is constantly communicating with the motor, even
when the motor and MOTOR LED are off. If motor does not

acknowledge receipt of communications, the fan coil control will
display Status Code 44 on STATUS LED and continue to try to

communicate

with

the

motor.

If

motor

acknowledges

communication, status code will be cleared.
If MOTOR LED is lit and flashing and motor does not run:

1. Check the STATUS LED. If STATUS LED is indicating a

Status 44 code, check the motor wiring harness for proper

connection to control and motor receptacles.

2. Check motor wiring harness to be sure all wiring complies

with wiring diagram description, makes a complete circuit

from connector to connector, and is not shorted.

3. Check 12--vdc low voltage supply to motor at pins 1 (+)

and 2 (--) of motor header connection to fan coil control.

If all checks are normal, fan coil control is good and control

module on motor may need replacement. Check motor and Motor
Control Module following the instructions in Section C, Indoor

Fan Motor Troubleshooting.
If the MOTOR LED is off, STATUS LED is indicating a Status

Code 44 and motor is running:

1. Disconnect the motor harness at the fan coil control. If

motor continues to run, fan coil control is good and control
module on motor may need replacement.

STATUS CODE 25, INVALID MOTOR / MODEL SELECTION
On initial start--up, the fan coil control shall poll motor for its size

data and check unit size data stored in the control memory.

1. If motor size is incorrect for unit size or size data is invalid,

Status Code 25 will be displayed on STATUS LED.

2. If model size data is missing (as is the case when a

replacement fan coil control board is installed), system UI
will prompt installer to enter correct model size from a list

of valid sizes.

3. If motor size is incorrect for model size, motor must be

replaced with proper size motor. Fan coil control will not
respond to operation requests until this fault condition is
resolved.

STATUS CODE 26, INVALID HEATER SIZE
On initial power--up, fan coil control will write into memory

electric heater size as read from heater if heater is provided with

Identifier Resistor (IDR). Heater size must be valid for the installed
unit. Fan coil control will read IDR value connected to pins 1 and 2

of heater harness connector. If no resistor is found, system UI will
prompt installer to verify that no heater is installed. Verifying that

this is correct will establish that the unit is operating without an
electric heater accessory. Upon choosing negative option, installer

will be prompted to select heater size installed from a list of valid

heater sizes for unit size installed.
If heater ID resistor value read is invalid, Status Code 26 will be

displayed on STATUS LED.
If heater installed is equipped with a resistor connected to pins 1

and 2 of heater harness connector and status code 26 is displayed

on STATUS LED:

1. Check wiring harness connections to be sure connections

are secure.

2. If symptoms persist, disconnect wiring harness at fan coil

control board and check for a resistance value greater than

5000 ohms.

3. Check for proper wiring of resistor assembly.
4. Make sure heater size installed is an approved size for unit

and size installed.

NOTE

: Fan coil control will not operate electric heater until this

Status Code is resolved. If the heater size is set through the UI, the
heater will be operated as a single stage heater. If staging is desired,
the IDR value must be read in by the unit control.

50X

T

--

A

Summary of Contents for Infinity 15 SEER 50XT-A

Page 1: ...round Lead to Ground Screw 9 Routing Control Power Wires 11 Accessory Installation 11 Special Procedures for 208 v Operation 12 PRE START UP 13 START UP 13 20 Unit Start Up 13 Sequence of Operation 17...

Page 2: ...ckaged heat pump is fully self contained and designed for outdoor installation See Fig 1 Standard units are shipped in a horizontal discharge configuration for installation on a rooftop or a cement sl...

Page 3: ...it basepan Anchor screw A09090 A09095 A09096 A09094 A09097 UNIT SIZE CATALOG NUMBER A IN mm B small base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm Small or Large CPRFCURB010A00 11 279 1...

Page 4: ...4 A09128 Fig 5 50XT A24 30 Unit Dimensions 50XT A...

Page 5: ...5 A09129 Fig 6 50XT A36 60 Unit Dimensions 50XT A...

Page 6: ...es INSPECTION Prior to initial use and at monthly intervals all rigging shackles clevis pins and straps should be visually inspected for any damage evidence of wear structural deformation or cracks Pa...

Page 7: ...tween the unit and the conditioned space If a 90 degree elbow cannot be installed then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditio...

Page 8: ...sposal methods comply with local codes restrictions and practices The units dispose of condensate through a 3 4 in NPT female fitting that exits on the compressor end of the unit Condensate water can...

Page 9: ...age that could affect warranty UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the unit being installed 1 Make all electrical connections in accordance with NEC NFP...

Page 10: ...Cfm Comfort Variable based on Comfort Settings see User Interface instructions for more information Efficiency 700 875 1050 1225 1400 1750 Max 800 1000 1200 1400 1600 2000 Size in mm 10x10 254x254 10x...

Page 11: ...e F1 on Fig 15 The C circuit of transformer circuit is referenced to chassis ground through a printed circuit run at SEC2 and metal control board mounting eyelets Check to be sure control board is mou...

Page 12: ...Fig 14 SPECIAL PROCEDURES FOR 208 V OPERATION Be sure unit disconnect switch is open Disconnect the yellow primary lead from the transformer See unit wiring label See Fig 17 Connect the yellow primary...

Page 13: ...ng conditions a Make sure that outdoor fan blade is correctly positioned in fan orifice See Fig 20 b Make sure that condensate drain pan and trap are filled with water to ensure proper drainage c Make...

Page 14: ...ment fuse If COMM LED does not light within proper time period and status code is displayed 1 Check system wiring to be sure UI is powered and connections are made A to A B to B etc and wiring is not...

Page 15: ...15 A09092 Fig 17 Wiring Schematic 50XT A Single Phase 50XT A...

Page 16: ...ed off The MOTOR LED will not flash to indicate communications when it is turned off Fan coil control is constantly communicating with the motor even when the motor and MOTOR LED are off If motor does...

Page 17: ...but may cause the low voltage fuse to open STATUS CODE 46 BROWNOUT CONDITION If the secondary voltage of the transformer falls below 15 vac for a period exceeding 4 seconds Status Code 46 will be dis...

Page 18: ...trip or start relay not releasing if installed Contactor Shorted 73 Compressor voltage sensed when no demand for compressor op eration exists Contactor may be stuck closed or there is a wiring error...

Page 19: ...when outdoor coil temp is outdoor air temperature plus 3_F 1 6 C or outdoor fan has been ON for 30 minutes Fan is turned off to allow refrigerant system to stabilize S In low stage fan is off when out...

Page 20: ...d adjustment to the specified factory charge must always be very minimal If a substantial adjustment is indicated an abnormal condition exists somewhere in the cooling system such as insufficient airf...

Page 21: ...21 A06297 Fig 18 Non Communicating Emergency Cooling Heating Wiring Connections A09109 Fig 19 Cooling Charging Table Subcooling 50XT A...

Page 22: ...To ensure continuing high performance and to minimize the possibility of premature equipment failure periodic maintenance must be performed on this equipment This packaged air conditioner unit should...

Page 23: ...ll obstructions to ensure proper cooling operation Never place articles on top of the unit CAUTION 1 Remove 4 screws holding outdoor grille and motor to top cover 2 Turn motor grille assembly upside d...

Page 24: ...land scroll compressor uses Mobil 3MA POE oil This is the only oil allowed for oil recharge Step 11 Refrigerant System This step covers the refrigerant system of the 50XT A including the compressor oi...

Page 25: ...Table 2 The control board should be replaced BROWN OUT PROTECTION If the line voltage is less than 187v for at least 4 seconds the appropriate compressor contactor and fan relay are de energized Compr...

Page 26: ...e sensors are out of range If the sensors are out of range the control will flash the appropriate fault code as shown in Table 2 The thermistor comparison is not performed during low ambient cooling o...

Page 27: ...psig low side retard S Use hoses with minimum 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oil...

Page 28: ...r Unit undersized for load Decrease load or increase unit size UI temperature set too low too high Reset UI setting Low refrigerant charge Locate leak repair and recharge Air in system Recover refrige...

Page 29: ...TIGHTNESS MAKE SURE THAT If Applicable ON 60 SIZE PURON HEAT PUMP ONLY THE TWO WIRE TIES FASTEN TO THE OUTDOOR COILS AND REVERSING VALVE ACCUMULATOR HAVE BEEN REMOVED III START UP ELECTRICAL SUPPLY V...

Page 30: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 03 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Reviews: