i-Vu® XT Router (drv_gen5)
CARRIER CORPORATION ©2022
Installation and Start-up Guide
3
All rights reserved
Protection
Device is protected by a replaceable, fast acting, 250 Vac, 2A, 5mm x 20mm glass
fuse.
The power and network ports comply with the EMC requirements EN50491-5-2.
CAUTION
To protect against large electrical surges on serial EIA-485
networks, place a PROT485 at each place wire enters or exits the building.
LED status indicators
•
Tricolor
NET
LED to show network status
•
Tricolor
SYS
LED to show system status
•
A
TX
(Transmit) and
RX
(Receive) LED for the following ports:
Gig-E
Port S1
Port S2
See
LEDs
(page 36).
Environmental operating
range
-40 to 158°F (-40 to 70°C), 10-95% relative humidity, non-condensing
Physical
Fire-retardant plastic ABS, UL94-5VA
Terminal blocks and
connectors
Screw-type terminal blocks.
0.2 in (5.08 mm) pitch connectors
Mounting
35mm DIN rail mounting or screw mounting
Overall dimensions
A:
B:
Depth:
7.1 in. (18.03 cm)
6.95 in. (17.65 cm)
2.09 in. (5.31 cm)
Screw mounting dimensions C:
D:
6.45 in (16.38 cm)
4.1 in. (10.4 cm)
Weight
1 lb. 1 oz. (0.482 kg)
BACnet Support
Conforms to the BACnet Router (B-R-TR) Standard Device Profile as defined in
ANSI/ASHRAE Standard 135-2012 (BACnet) Annex L, Protocol Revision 14