LEDs
NET (Network Status) Tricolor LED
Color
Pattern
Condition
Message in Module
Status
Possible Solutions
Red
On
Ethernet connection problem
No Ethernet Link
•
Connect Ethernet Cable
•
Check other network
components
Red
1 blink
One of the following BACnet/IP
(Ethernet) DLL reporting issue:
•
Unable to create tasks
•
Unable to open socket for BACnet
port
BACnet/IP error
Cycle power
Red
2 blink
Current default IP address does not
match the current rotary switch setting
Default IP address
mismatch
•
Use the controller setup
Ports
tab to set the IP
address
•
Cycle power to accept new
IP address
•
Change rotary switches to
match current default IP
address