i-Vu® XT Router (drv_gen5)
CARRIER CORPORATION ©2022
Installation and Start-up Guide
15
All rights reserved
To set the Port S1 address and baud rate
The address should be in one of the following ranges based on the port's use.
•
For ARCNET, the range is 1 to 254.
•
For MS/TP, the range is 0 to 127.
On the
Connections
>
Port S1
tab, type the address in the
MAC Address
field.
NOTE
ARCNET is not supported on Port S2.
For MS/TP, set up the port's baud rate
1
On the
Connections
>
Port S1
tab, select the
Baud Rate
. The default is 76,800 bps.
2
Click
.
To set the Port S2 address and baud rate
1
On the
Connections
>
Port S2
tab, type the address in the
MAC Address
field. The address must be in the
range of 0 to 127.
2
Select the
MSTP Baud Rate
. The default is 76,800 bps.
NOTE
Enter the same baud rate for all devices on the MS/TP network.
3
Click
.
Summary of Contents for i-Vu XT