i-Vu® XT Router (drv_gen5)
CARRIER CORPORATION ©2022
Installation and Start-up Guide
22
All rights reserved
Gig-E Port using BACnet/IPv4
Primary BACnet/IP
Home network
or
Set as home
This is typically the network that is communicating with the building automation
system's application. This sets the BACnet Address of the Device Object. If the
port is
Enabled
, the user can set this port as the home network to identify it as
the connection to the i-Vu® application.
Click
Disable
if you want to disable the port from use.
Auto Generate Network
Number
If checked, network number is autogenerated, which then automatically sets to
((IP network rotary switch address) x 10) + 0.
Uncheck to use
Custom Static
Address Mode
.
Network Number
Specify a number for the BACnet/IP network or set to 0 if the port is not used.
The network number is 0 by default. Filled in automatically if
Autogenerate
Network Number
is checked.
NOTE
When downloaded from the i-Vu® application, these numbers match those
set using SiteBuilder.
Address Mode
Select the type of addressing the router is to use. See Addressing the i-Vu® XT
Router.
Select
Default IP Address
to automatically assign the following to the router:
•
IP address = 192.168.168.
x
where
x
is the setting on the rotary switches in the range from 1 to 253
•
Subnet Mask = 255.255.255.0
•
Default Gateway = 192.168.168.254
Select
Custom Static
if you have a permanent IP address which does not change
and is usually obtained from the network administrator.
Address
Displays the unique address of the device, if assigned. Editable only if using
Custom Static
addressing.
Subnet Mask
Displays the Subnet Mask of the device, if assigned. Editable only if using
Custom
Static
addressing.
Default Gateway
Displays the Default Gateway of the device, if assigned. Editable only if using
Custom Static
addressing.
UDP Port
The port that the i-Vu® XT Router will use for BACnet communication.
If the i-Vu® XT Router has two BACnet/IP networks communicating on the Gig-E
port, confirm that the home network interface has the port number set to what
the i-Vu® application will use for BACnet communication.