All rights reserved
Notification Class tab
A BACnet alarm's Notification Class defines:
•
Alarm priority for Alarm, Fault, and Return to Normal states
•
Options for BACnet alarm acknowledgment
•
Where alarms should be sent (recipients)
Alarms in the i-Vu® application use Notification Class #1. The i-Vu® application is automatically a recipient of
these alarms.
Notification Class Recipients
The first row in this list is from the i-Vu® application. Do not delete this row. Click
Add
if you want other BACnet devices to receive alarms associated with this
Notification Class.
NOTE
Additional entries in this table may be lost after a download.
Recipient Type
Select
Recipient Device
for device recipients that support dynamic binding.
Complete the
Recipient Device
field if you are using this recipient type.
Select
Recipient
Address
(static binding) for either of the following:
•
Third-party BACnet device recipients that do not support dynamic binding
•
When you want alarms to be broadcast (you must uncheck
Issue Confirmed
Notifications
). This use is rare.
Complete the
Network Number
and
MAC Address
fields if you are using this
recipient type.
Recipient Device
Type the
Device Instance
from SiteBuilder (or from the network administrator for
third-party devices) in the
#
field.
Network Number
Specify a number for the BACnet network or set to 0 if the port is not used.
MAC Address
A factory-assigned Ethernet MAC Address or IP Address
Issue Confirmed
Notifications
Select to have a device continue sending an alarm message until it receives
delivery confirmation from the recipient.
Transitions to Send
Uncheck the types of alarms you do not want the recipient to get.
Off Normal
BACnet priority for Alarms.
Fault
BACnet priority for Fault messages.
Normal
BACnet priority for Return-to-normal messages.
Days and Times to Send
Monday to Sunday
From Time
To Time
Select days and times during which the recipient will receive alarms.
Process Identifier
Change for third-party devices that use a BACnet Process Identifier other than 1.