i-Vu® XT Router (drv_gen5)
CARRIER CORPORATION ©2022
Installation and Start-up Guide
37
All rights reserved
NET (Network Status) Tricolor LED
Color
Pattern
Condition
Message in Module
Status
Possible Solutions
White
1 blink
Unable to connect to BACnet/SC Hub
BACnet/SC Not
Connected
•
Configuration issue
–
ex:
no URL for hub
•
Certificate issue
•
No hub connection
White
On
Unable to connect to BACnet/SC Hub,
but connection to failover hub was
successful
BACnet/SC Connected to
failover hub
Fix any issues present with the
primary hub connection
Blue
On
One of the following issues:
•
Port communication firmware did
not load properly
•
Port communication firmware is
not running
•
Invalid protocol selected
ARCNET/MSTP firmware
error
•
Change rotary switch to
select valid protocol
•
Cycle power
Blue
1 blink
Invalid address selected for protocol
Invalid address selection
for ARCNET/MSTP
Change rotary switch to valid
address
Blue
2 blink
Router has same MAC address as
another connected device
Duplicate address on
ARCNET/MSTP
Change rotary switch to unique
address
Blue
3 blink
Router is the only device on the
network
No other devices
detected on
ARCNET/MSTP
•
Check that network cable
is connected properly
•
Check that baud rate is
correct
Blue
4 blink
Excessive errors detected over 3
second period
Excessive
communication errors
on ARCNET/MSTP
•
Check that network cable
is connected properly
•
Check that baud rate is
correct
Blue
5 blink
ARCNET traffic overload possibly due
to circular router or excessive COVs
(change of values)
Event System Error -
FPGA RX FIFO full
•
Check the network
configuration for a circular
route
•
Increase the time
between COVs to reduce
excessive COV traffic
Green
On
All enabled networks are functioning
properly
No errors
No action required