automatically exits the Relay Test Mode and commences regular
operation.
After finished the relay test, leave the jumpers connected for at

least five more minutes in order to capture the readings for the

maximum load of the unit.

Do not proceed to the next step until the Relay Test completes

successfully.

The Gateway (Coordinator) can be restarted in Test

mode as many times as desired.

Test Gateway (Coordinator) Signal Strength

1. Disconnect all power to the rooftop unit.
2. Remove jumper wires from control lines.
3. Restore all power to the rooftop unit.
4. Turn the Gateway (Coordinator) on, and wait approximate-

ly 20 seconds until the TRAFFIC indicator turns on, indi-
cating that the Gateway (Coordinator) is attempting to boot
up in regular operation mode

C13359

5. Confirm that the READY indicator turns on, and at least

two bars of signal strength are visible. Contact REGEN En-

ergy’s Operation Center (949--258--4415, Option No. 2) for
assistance if fewer than two signal strength bars are dis-
played.

C13360

6. Close the rooftop unit’s control panel and all cabinet doors.
7. Contact

REGEN

Energy’s

Operation

Center

(949--258--4415, Option No. 2) to notify that the Gateway
(Coordinator) has been successfully commissioned (This
step does not need to be repeated for each Energy Demand

Load Controller).

GATEWAY

(COORDINATOR)

Y1

575V 
480V

24V

Y2

Y1

5

2

Load-Side Power

Stepdown 

Trasformer

Controls

Terminal Board

From 

Thermostat

10

CT Clamp 

Sensor 1

CT 

Clamp 

Sensor 2

Omron LY4

Four pole Relay

Y1

W2

W1

W2

W1

13

14

12

11

10

9

8

7

6

5

FIELD INSTALLED WIRE

6

3

4

14

15

16

17

18

19

20

21

11

12

9

Modem 

Enclosure

GND PWR

RS232

24VAC-

12VDC 

Transformer

Molex 

connector

25

1

24

8

7

FIELD INSTALLED WIRE

WIRE NUT CONNECTION

Molex 

connector

C13361

Fig. 11 -- Standard Wiring Schematic for Thermostat Controls (2--Stage Unit)

Summary of Contents for CRDMNDGW001A00

Page 1: ...ergy Demand System uses wireless devices incorporating patented Swarm Energy Management algorithms to create a network of coordinated rooftop units to reduce and optimize their energy usage This syste...

Page 2: ...Equipment Location The first step is to decide which rooftop unit should have the Gateway Coordinator This device should be mounted preferably in the middle of the rooftop or on a rooftop unit where...

Page 3: ...ny available panel Ensure the selected mounting loca tion does not cause damage to coils or existing compo nents S Antenna Mounting Base Mounted on top of the cabi net S Relay Located inside the cabin...

Page 4: ...Modem Enclosure to the 3 wire Molex connector from the Gateway Coordinator wires 3 4 11 12 C13339 Fig 7 Data Cable Connection Install Antenna and Mounting Base Magnetic mount with extension wire pass...

Page 5: ...Wait until you see the indicators on the left of the display light up in a vertical row C13342 5 Press the unlock sequence Y B ENTER Confirm that the OVERRIDE indicator flashes and the screen displays...

Page 6: ...turns on and at least two bars of signal strength are visible Contact REGEN En ergy s Operation Center 949 258 4415 Option No 2 for assistance if fewer than two signal strength bars are dis played C13...

Page 7: ...e 5 2 Current Transformers 6 4 Pole Relay pre wired with extension wires 7 Mounting screws supplied in a plastic bag not displayed below 1 Gateway Coordinator Controller 2 Magnetic antenna base 3 Ante...

Page 8: ...d Controllers Shipped Installed Qty of 4 Pole Relays Shipped Installed Qty of Transformers Shipped Installed Qty of Antennas Shipped Installed Section 3 Installation Issues Facility Roof Access Delays...

Page 9: ...s of cooling are energized note any startup delays Blower Delay 1st stage Delay 2nd stage Delay 9 Once all stages of cooling energized measure amperage on lines where CTs are clamped measure incoming...

Page 10: ...orp S 7310 W Morris St S Indianapolis IN 46231 Edition Date 05 13 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No CRD...

Reviews: