background image

2

Wiring Diagram

A diagram noting all components and their proper wiring is
provided. (See Fig. 11)

Installation Report

An Installation Report is provided at the end of this document,

where you should record installation notes for each Gateway
(Coordinator), and issues encountered.

Recommended Order of Operation To Install the

Gateway (Coordinator):

1. Determine where to mount each component.
2. Mount the components.
3. Wire all components.
4. Power up and test the Gateway (Coordinator).
5. Fill out the required RTU Installation Checklist.
6. Fill out the Installation Report.
7. Scan and email “RTU Checklist” and “Installation Report”

to [email protected] within 48 hours of complet-
ing device setup.

Equipment Location:

The first step is to decide which rooftop unit should have the
Gateway (Coordinator). This device should be mounted preferably

in the middle of the rooftop or on a rooftop unit where other

controllers have line of sight access to this rooftop unit. (See Fig.
1.)

Overview Schematic

The components listed below must be installed. Refer to the
diagram in Fig. 2. when deciding where to mount each component

in relation to the rooftop unit.

Component

Installation Location

Energy Demand Gateway

(Coordinator)

Inside cabinet

Transformer

Inside cabinet

4--Pole Relay

Inside cabinet

Modem Enclosure

Exterior of cabinet

Antenna and Mounting Base

Exterior of cabinet, on top

Preferred Location

(Please note the central location on the rooftop)

C13332

Fig. 1 -- Preferred Equipment Installation Locations

Supplied

4-Pole Relay

Supplied 

Transformer

C13333

Fig. 2 -- Component Installation Schematic

Summary of Contents for CRDMNDGW001A00

Page 1: ...ergy Demand System uses wireless devices incorporating patented Swarm Energy Management algorithms to create a network of coordinated rooftop units to reduce and optimize their energy usage This syste...

Page 2: ...Equipment Location The first step is to decide which rooftop unit should have the Gateway Coordinator This device should be mounted preferably in the middle of the rooftop or on a rooftop unit where...

Page 3: ...ny available panel Ensure the selected mounting loca tion does not cause damage to coils or existing compo nents S Antenna Mounting Base Mounted on top of the cabi net S Relay Located inside the cabin...

Page 4: ...Modem Enclosure to the 3 wire Molex connector from the Gateway Coordinator wires 3 4 11 12 C13339 Fig 7 Data Cable Connection Install Antenna and Mounting Base Magnetic mount with extension wire pass...

Page 5: ...Wait until you see the indicators on the left of the display light up in a vertical row C13342 5 Press the unlock sequence Y B ENTER Confirm that the OVERRIDE indicator flashes and the screen displays...

Page 6: ...turns on and at least two bars of signal strength are visible Contact REGEN En ergy s Operation Center 949 258 4415 Option No 2 for assistance if fewer than two signal strength bars are dis played C13...

Page 7: ...e 5 2 Current Transformers 6 4 Pole Relay pre wired with extension wires 7 Mounting screws supplied in a plastic bag not displayed below 1 Gateway Coordinator Controller 2 Magnetic antenna base 3 Ante...

Page 8: ...d Controllers Shipped Installed Qty of 4 Pole Relays Shipped Installed Qty of Transformers Shipped Installed Qty of Antennas Shipped Installed Section 3 Installation Issues Facility Roof Access Delays...

Page 9: ...s of cooling are energized note any startup delays Blower Delay 1st stage Delay 2nd stage Delay 9 Once all stages of cooling energized measure amperage on lines where CTs are clamped measure incoming...

Page 10: ...orp S 7310 W Morris St S Indianapolis IN 46231 Edition Date 05 13 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No CRD...

Reviews: