background image

 

 

C

C

a

a

r

r

r

r

i

i

e

e

r

r

 

 

C

C

o

o

n

n

n

n

e

e

c

c

t

t

 

 

W

W

i

i

-

-

F

F

i

i

 

 

T

T

h

h

e

e

r

r

m

m

o

o

s

s

t

t

a

a

t

t

 

 

3

3

3

3

C

C

O

O

N

N

N

N

E

E

C

C

T

T

S

S

T

T

A

A

T

T

4

4

3

3

F

F

X

X

 

 

I

I

n

n

s

s

t

t

a

a

l

l

l

l

a

a

t

t

i

i

o

o

n

n

 

 

G

G

u

u

i

i

d

d

e

e

 

 

 

                                    

 

 

 

 
               Carrier ©2021 ·  Catalog No. 11-808-872-01 · 12/3/2021 

 

Summary of Contents for Connect 33CONNECTSTAT43FX

Page 1: ...r C Co on nn ne ec ct t W Wi i F Fi i T Th he er rm mo os st ta at t 3 33 3C CO ON NN NE EC CT TS ST TA AT T4 43 3F FX X I In ns st ta al ll la at ti io on n G Gu ui id de e Carrier 2021 Catalog No 11 808 872 01 12 3 2021 ...

Page 2: ...t version of this document from www hvacpartners com the Carrier Partner Community website or your local Carrier office Important changes are listed in Document revision history at the end of this document Carrier 2021 All rights reserved ...

Page 3: ...ace 16 Dormant screen 16 Home screen 16 Occupancy Enter PIN screen 17 Changing the setpoints 18 Changing the fan 19 Changing the mode 19 Using the menu for advanced features 20 To adjust date and time 21 To adjust occupancy settings 22 To adjust the display settings 24 To adjust the banner text 26 Using installer settings 28 To set up BACnet 40 To test the HVAC system 45 To restore factory default...

Page 4: ......

Page 5: ...e type II thermistor connected to T and C terminals or Wi Fi outdoor temperature available by GPS location services determined when the thermostat is installed Humidity sensing and control Remote humidity sensing from a 33ZCSENDRH 02 Humidity Duct Sensor or 33ZCSENSRH 02 wall sensor Wi Fi connectivity supports 802 11 a b g n standards and utilizes a Broadcom chipset Cloud Connectivity using the Ca...

Page 6: ...ndensing Connections Connectors P104 and P105 2 banks of finger friendly spring type terminal blocks intended to be wired by the end user or installer Inputs C connection R connection H 0 10 Volt input T remote thermistor Outputs Connections Y3 O B Y2 Y1 G W1 and W2 Communications 485 signal A and B Mounting Standard 4 x 2 in electrical box using the 6 32 x 1 2 in mounting screws and plastic wall ...

Page 7: ...st stage cooling Y2 second stage cooling Y3 third stage cooling Heat only with gas heat up to 2 stages of heating Heating W1 first stage heat W1 W2 second stage heat Heat only with electric heat up to 3 stages of heating Heating W1 first stage heat W2 second stage heat W1 W2 third stage heat AC with gas heat up to 3 stages of cooling and 2 stages heating Cooling Y1 first stage cooling Y2 second st...

Page 8: ...ng and 4 stages of heating with 2 stages auxiliary This system is known as a dual fuel system When gas heat turns on the HP heat turns off unless defrost is active Once the gas is turned on the heating demand is satisfied with gas heat The thermostat does not stage down from gas to heat pump heat Cooling Y1 O B first stage cooling Y1 Y2 O B second stage cooling Heating Y1 first stage HP heating Y1...

Page 9: ...emperature sensor Remote temperature sensor The remote temperature measurement is supplied by a NTC J curve type II thermistor connected between T and C This thermistor is supplied by the installer to use for Space Outdoor Supply Air or an average with the space air temperature When used for the space temperature sensor up to 9 remote space sensors can be averaged 1 or multiples of 4 or 9 The T in...

Page 10: ...energized when the thermostat has a G Fan fan demand W1 First Stage Heat or AUX Heat first stage heat or aux heat demand W2 Second stage heat or AUX heat second stage heat or aux heat demand Y1 First stage cooling or HP heating output first stage cooling or HP heating output Y2 Second Stage Cooling or HP Heating Output second stage cooling or HP heating demand O Reversing Valve Output reversing va...

Page 11: ...Carrier Connect Wi Fi Thermostat 33CONNECTSTAT43FX CARRIER CORPORATION 2021 Installation Guide All rights reserved 7 To wire duel fuel systems and furnace AC systems Dual fuel systems Furnace AC systems Wiring the Carrier Connect Wi Fi Thermostat ...

Page 12: ...Wiring the Carrier Connect Wi Fi Thermostat Carrier Connect Wi Fi Thermostat 33CONNECTSTAT43FX CARRIER CORPORATION 2021 Installation Guide All rights reserved 8 Dual fuel systems Furnace AC systems ...

Page 13: ...Fi Thermostat Carrier Connect Wi Fi Thermostat 33CONNECTSTAT43FX CARRIER CORPORATION 2021 Installation Guide All rights reserved 9 To wire an air handler with heat pump or with AC Air handler heat pump systems Air handler AC systems ...

Page 14: ... the Carrier Connect Wi Fi Thermostat Carrier Connect Wi Fi Thermostat 33CONNECTSTAT43FX CARRIER CORPORATION 2021 Installation Guide All rights reserved 10 Air handler heat pump systems Air handler AC systems ...

Page 15: ...f wire and cable for maximum signal integrity Cable 22 or 24 AWG low capacitance twisted stranded shielded copper wire Maximum length 2000 feet 610 meters per segment Baud rate 9600 bps 19 2 kbps 38 4 kpbs or 76 8 kbps 115 2 kbps Connect communication wiring to terminals A and B Do not terminate shield at the thermostat CAUTION Maintain the same polarity NOTE For more networking details see the Op...

Page 16: ... later 1 After downloading Connect App select USER SETUP and Register New Account NOTE You can also register new accounts using the website connectstat carrier com 2 Enter an email address that you can access on your mobile device and receive the confirmation email to complete the registration process 3 Select SETUP NEW THERMOSTAT and follow the Connect App instructions 4 After registering the the...

Page 17: ... Create groups of thermostats that you have registered Create groups of thermostats that other owners have shared with you Get online product information Find local dealer support To navigate On a touchscreen device use any of the following swipe the screen tap the arrow on the side tap a dot on the bottom of the screen on either side of the HOME button On a non touchscreen device click on the gra...

Page 18: ...ed periods When operating in AUTO MODE the fan only runs when there is an active heating or cooling demand When you select ON the fan runs continuously except during the Blower On Delay when a heat cycle is starting There is a 30 second minimum on off timer when changing the FAN MODE NOTE The following selections are not available if the thermostat has been configured for non programmable operatio...

Page 19: ...lect ADVANCED to configure same day of each week s of that month To delete a holiday on the Mobile app swipe the selected holiday to the left and select Delete Web app select x on right side of the holiday SETTINGS Enter the name and location of the thermostat for the user s reference The user can enter an email address for alerts and a mobile phone number to receive text alert messages NOTE Requi...

Page 20: ...thermostat primarily from the Home screen The center portion of the screen displays the current space temperature in whole degrees The default temperature scale is F but can be changed to C in the Installer settings page 28 The top of the screen displays a banner that cycles system information every 3 seconds To see the scrolling messages faster than 3 seconds press the banner area of the screen t...

Page 21: ...djust to the correct value Repeat with the remaining 2 digits When the 3 digit PIN is correct press SAVE This screen has an OCC UNOCC button to temporarily override the program schedule settings without knowing the PIN The PIN must be entered for all other thermostat changes Pressing the OCC UNOCC button temporarily overrides the program schedule settings with the occupied or unoccupied settings T...

Page 22: ...f the display changes the setpoints to either the program schedule s occupied or unoccupied settings The label on this button shows the opposite of the word above the space temperature Example If the thermostat is in an occupied program period the middle button displays UNOCC so you can change the thermostat settings to the unoccupied values Overriding the program schedule using the OCC UNOCC butt...

Page 23: ...ERRIDE The override remains active for the rest of the current program schedule Changing the mode You can change the mode from the home screen by pressing the MODE button Changing from one mode to another does not affect the thermostat s operation until the mode selection has remained constant for at least 5 seconds Changing from one mode to another e g HEAT mode to COOL mode requires the thermost...

Page 24: ...ved 20 The menu allows the user to access more advanced features of the thermostat 1 When you press the MENU button the first menu option is CURRENT FAN 2 Press SELECT to activate the up and down arrows 3 Press the up or down arrows to advance through the menu options to view or change the value for each setting Using the menu for advanced features ...

Page 25: ...current month D R Jan Jan to Dec SET DAY OF MONTH The current day of the month D R 1 1 to 31 SET HOUR The hour of the day using 12 hour a m A p m P format D R 12 A 12 A 11 P SET MINUTE The current minute D R 0 0 to 59 SYNC TIME TO SERVER When the thermostat is first registered and connected to a Wi Fi router both the date and time are synced with the server based on the geographic location of the ...

Page 26: ...OINT If the installer has configured the thermostat for non programmable operation and remote occupancy is disabled this setting is not available D R 85 F 52 to 90 F UNOCC HEAT The heat setpoint during unoccupied periods NOTES The maximum value is limited by the unoccupied cool setpoint heat setpoint cannot be greater than the cool setpoint and the installer setting for MAX HEAT SETPOINT If the in...

Page 27: ... setting is not available D R 2 2 or 4 PROGRAM SCHEDULE The program schedule specifies the programmed start times for the thermostat to control the space to the occupied or unoccupied fan and setpoint values 1 From the SET PROGRAM screen press SELECT to view the program schedule for SUNDAY P1 2 From the SUNDAY P1 screen use the up and down arrows to advance through the program schedule to the next...

Page 28: ...er the 3 digit PIN after pressing any button on the home screen If the PIN is entered successfully the thermostat is unlocked until the dormant screen displays After 5 failed attempts to unlock the thermostat a notification fault is sent through the Wi Fi to the registered owner of the thermostat Additional unlock attempts are not allowed for 15 minutes NOTE If the user enables LOCKOUT but does no...

Page 29: ...w the holidays The up and down arrows scroll through the holidays displaying one per screen Maximum number of holidays in the holiday list is 24 There are two different holiday formats Standard holidays are the same every year such as Jan 1st and Dec 25th Special holidays are occurrences of a day of the week such as Memorial Day Labor Day and Thanksgiving The day of the week is shown in the heat s...

Page 30: ...es are not so a power cycle does not retain partial hour runtime FILTER REMINDER displays on the home screen and dormant screen banners when the filter timer counts down to zero If you touch the home screen banner when the FILTER REMINDER message displays the thermostat transitions directly to FLT HRS LEFT screen The banner message button is a shortcut to the FLT HRS LEFT screen when the filter ti...

Page 31: ...he dormant screen when the mode is set to COOL or AUTO R YES NO HEAT SETPT When set to NO the heat setpoint is not displayed on the dormant screen banner When set to YES the heat setpoint is displayed on the dormant screen banner NOTES The heat setpoint is not displayed on the home screen banner The heat setpoint is displayed on the dormant screen when the mode is set to HEAT EHEAT or AUTO R YES N...

Page 32: ... return to the SELECT screen Setting Default Range HEAT EQUIP Set the type of heating equipment being used If you set the COMPRESSOR to HP the heading of this screen is EHEAT EQUIP instead HEAT EQUIP D R GAS GAS ELEC Electric Heat HEAT STAGES If the COMPRESSOR EQUIPMENT TYPE is set to HP the heading of this screen is EHEAT STAGES The option of 0 heat stages is only available if the HEATING EQUIPME...

Page 33: ...ection of AUTO mode when the mode button is pressed AUTO mode allows the thermostat to automatically switch from heating to cooling to maintain the conditioned temperature between the heating and cooling setpoints NOTE AUTO ALLOWED is only available if both a heating source and a cooling source are available HEAT STAGES greater than 0 and COMPRESSOR equal to AC or HP D R YES YES Auto mode is avail...

Page 34: ...stat is set to NP non programmable OCC UNOCC RESUME SCHEDULE button is not displayed on the home screen OCCUPIED UNOCCUPIED and SCHEDULE PAUSED icons are not displayed on the home screen The program schedule cannot be viewed When the REMOTE SENSOR setting is set to OCC Occupancy this setting is forced to NP and is not displayed to the installer Default setpoint times and temperature settings Setti...

Page 35: ... have been in the linear progression at the same time as when the temporary hold was not active NOTE The smart recovery setting is only available if the thermostat is configured as a programmable thermostat D R 30 NO 30 minutes 60 minutes 90 minutes FAN ON WITH W Sets the fan to turn on with any W output when the fan is set to AUTO Range YES The G output is turned on by the thermostat when the W1 ...

Page 36: ... remote input is not shorted This selection disables the timed air filter reminder NOTES If the remote sensor is set to NONE or ID the outdoor temperature is acquired via Wi Fi through the server based on the geolocation of the phone tablet used to connect the thermostat to a router The outdoor temperature is available if the thermostat is not connected to Wi Fi and the ODT option is not selected ...

Page 37: ... setting is OFF If the system does not have a 2 stage heat pump this selection is not available D R OFF OFF 80 110 F 5 F increments ON LOW HEAT LOCKOUT TEMPERATURE Sets an outdoor air temperature below which low speed compressor heating is locked out Below the specified air temperature all heating demands that use the compressor use high speed compressor heating Range OFF Functionality disabled Co...

Page 38: ...me must elapse from the start of one cycle before another cycle can start The Range The maximum number of times the equipment can turn on per hour NOTE When the equipment is off and the user changes the setpoint to create a heating or cooling demand the cycles per hour requirement is ignored to provide a timely response to the user s request The cycles per hour limitation become active again when ...

Page 39: ...ething other than ODT there is no outdoor air temperature being provided by the server and AUX HEAT LOCKOUT is set to a temperature the message OUTDOOR N A is displayed in the home and dormant screen banners to indicate an outdoor sensor is required but there is no outdoor temperature information available In a dual fuel unit the auxiliary heat lockout temperature is set to a value less than the h...

Page 40: ...able Do not set the heat pump lockout temperature to a value greater than the auxiliary heat lockout temperature unless the auxiliary heat lockout temperature setting is OFF This prevents the condition where the range of outdoor air temperatures between the auxiliary heat lockout and the heat pump lockout temperature result in no equipment operation Below the heat pump lockout temperature the AUX ...

Page 41: ...t pump equipment the humidifier and the dehumidifier setting of HumidiMiZer The W2 output is used for 2 stages of heating the humidifier and the dehumidifier setting of HumidiMiZer Any output that is already being used is not shown in the OCCUPANCY OUTPUT selections D R OFF OFF Y3 O B W2 OCCUPANCY INPUT Select what to do when a short on the remote temperature sensor is detected The OCC occupied se...

Page 42: ...TAGES is set to NONE D R NO NO YES HUM OUTPUT Select which output relay to use for the humidifier The choices only include outputs that are not already assigned to another function The output that is selected Y3 O B or W2 is used to control the humidifier equipment NOTE HUM OUTPUT is only available if the HUMIDIFIER setting is YES The HUM OUTPUT option is not available if the Y3 O B and W2 relays ...

Page 43: ...on demand HMZR When configured as a HumidiMiZer output and the humidity level is above the dehumidify target 24V is output at the selected terminal When the humidity level is below the dehumidify target 0 Vac is output on the selected terminal There is a 1 4 hysteresis around the dehumidify target to prevent rapid on off cycling of the selected output This output may be connected to compressor out...

Page 44: ...gaps in MAC address and setting the MS TP Max Master parameter of the device with the highest MAC address to a value equal to its MAC address The downside to setting the MS TP Max Master to a value less than 127 is if new devices are added to the network with addresses above the Max Master value they won t be discovered or added to the network NOTES Changing the MS TP Max Master requires restartin...

Page 45: ...time logic is then applied to the standard time to get the local time with Daylight Saving NOTE For reception of the UTC Time synchronization service to be enabled and UTC offset used on the device the SYNCH TIME TO SERVER option has to be set to NO and DST must be set to ENABLED This setting is not displayed if BACnet is disabled D R 5 00 5 hours 0 minutes 13 00 to 13 00 15 minute increments DEVI...

Page 46: ...ONFIG WRITE configuration is set to YES The top line in this screen scrolls to display the DEVICE DES and the description NOTE This setting is not displayed if BACnet is disabled D R DESCRIPTION The display is limited to showing only the first 28 characters of the maximum 32 characters allowed BACnet BMS OCC Enable or disable occupancy scheduling through the BACnet BMS by enabling or disabling the...

Page 47: ...t is disabled D R OFF disabled OFF disabled ACTV energized active INAC energized inactive NET GP W2 MODE Select the Network General Purpose Output W2 mode for control over the BACnet network Setting the mode to OFF disabled sets the Present Value of the BACnet object to Inactive and read only and the corresponding output relay will be in a de energized state Setting the mode to OFF disabled sets t...

Page 48: ...l equipment humidifier dehumidifier and occupancy output Any output that is still available after configuring primary and optional equipment can be made available as a BACnet network controlled output This setting is not displayed if BACnet is disabled D R OFF disabled OFF disabled ACTV energized active INAC energized inactive DISCONNECT WI FI Allows the installer to disconnect from the Wi Fi netw...

Page 49: ... if another stage exists the banner text changes to 2ND STAGE and a new 180 second countdown timer starts If no other stage exists the test cycle ends and the MODE is set to OFF When HEAT or EHEAT modes are running and there is a configured humidifier the output that controls the humidifier is energized When COOL mode is running and a dehumidifier has been configured for operating a HumidiMiZer th...

Page 50: ...elapse After the factory settings are restored the control returns to BACNET ENABLE to allow the installer to properly configure the thermostat Screen Factory defaults HEATING EQUIP TYPE GAS HEATING EQUIP STAGES 1 COMPRESSOR EQUIP TYPE A C COMPRESSOR EQUIP STAGES 1 AUTO ALLOWED YES AUTO CHANGEOVER 30 MIN PROG OR NON PROG PROG MAX TEMP HOLD TIME 2 FAHRENHEIT OR CELSIUS F SMART RECOVERY 30 FAN ON WI...

Page 51: ...AL 1 0 F AIR FILTER REMINDER 3000 HRS OCCUPANCY OUTPUT OFF OCCUPANCY INPUT OCCUPIED BACNET ENABLE NO MSTP BAUD RATE 76 8k MSTP MAC 1 BACNET UTC OFFSET 5h 0min EST MSTP MAX MASTER 127 DEVICE ID 160000 last 4 of S N DEVICE NAME DEVICE16 last 4 of S N DEVICE LOCATION LOCATION DEVICE DESCRIPTION DESCRIPTION BACNET BMS OCCUPANCY NO BACNET CONFIG WRITE ENABLE NO NETWORK GP OUT TIMEOUT 2 MIN NETWORK GP Y...

Page 52: ...Fi join commands The thermostat is already in the setup mode if SETUP WI FI was changed from NO to YES in the past 2 minutes or if the installer disconnected from a Wi Fi network in the past 2 minutes The following screen indicates that the thermostat is ready to join a Wi Fi network If the thermostat is connected to a Wi Fi network the SETUP WI FI screen is not displayed NOTE The SELECT button is...

Page 53: ... the numbers 0 through 9 DSN The DSN is the name used to identify the thermostat in the Carrier Connect Mobile App The name starts with the letters AC followed by 13 letters and numbers The DSN scrolls across the top of the display Registration When the thermostat has been successfully registered to a user account with the Carrier Connect mobile app the registered status displays YES When the ther...

Page 54: ...e demand is satisfied If the user changes the setpoint to satisfy the demand the 5 minute minimum on time is ignored and the heating or cooling equipment turns off Non volatile memory The thermostat can store settings in non volatile memory to ensure that settings remain the same after a power outage either intentional or unintentional Items stored in non volatile memory include Installer settings...

Page 55: ... when main thermistor P102 or RT1 reads 39 F Fault is cleared when temperature 4 F When this fault occurs the thermostat uses the temperature reading from the temperature humidity sensor as the space temperature REMOTE SENSOR HIGH Remote temperature 122 F only flagged if remote sensor set to use as indoor temperature REMOTE SENSOR setting set to INDOOR or AVERAGE REMOTE SENSOR LOW Remote temperatu...

Page 56: ...connected to Ayla server NO WI FI ROUTER Router signal strength is not connected WI FI HARDWARE FAULT Communications error occurred with Wi Fi module resets after valid message received LOCKOUT 5 WRONG PINS An incorrect PIN was entered consecutive times ECONOMIZER FAULT Remote sensor is set to ECFL and there is a short between terminals T and C System Events FILTER REMINDER Filter change reminder ...

Page 57: ...AV 407 Screen Timeout READ_WRITE SECONDS SCRN_TMT AV 408 Heat Setpoint READ_WRITE DEGREES_FAHRENHEIT HEAT_SP AV 409 Cool Setpoint READ_WRITE DEGREES_FAHRENHEIT COOL_SP AV 410 Active Backlight READ_WRITE PERCENT ACTV_BCKLT AV 411 Dormant Backlight READ_WRITE PERCENT DRMNT_BCKLT AV 412 Indoor Equip Stages GATED_WRITE ID_STAGES AV 500 Outdoor Equip Stages GATED_WRITE OD_STAGES AV 501 Max Temperature ...

Page 58: ...ier Out Status READ_ONLY 0 OFF 1 ON DEHUM_OUT BV 210 Network General Purpose Out Y3 READ_WRITE 0 OFF 1 ON NET_GP_Y3_OUT BV 211 Network General Purpose Out W2 READ_WRITE 0 OFF 1 ON NET_GP_W2_OUT BV 212 Network General Purpose Out OB READ_WRITE 0 OFF 1 ON NET_GP_OB_OUT BV 213 Wi Fi Time Synchronization READ_WRITE 0 DISABLED 1 ENABLED WIFI_TIME_SYNC BV 400 Auto DST Time Shift READ_WRITE 0 DISABLED 1 ...

Page 59: ...03 HUM TEMP SENSOR HIGH READ_ONLY 0 INACTIVE 1 ACTIVE HUM_TEMP_HI BV 904 HUM TEMP SENSOR LOW READ_ONLY 0 INACTIVE 1 ACTIVE HUM_TEMP_LO BV 905 ID TEMP RANGE HIGH READ_ONLY 0 INACTIVE 1 ACTIVE ID_TEMP_RNG_HI BV 906 ID TEMP RANGE LOW READ_ONLY 0 INACTIVE 1 ACTIVE ID_TEMP_RNG_LO BV 907 HUM SENSOR FAILURE READ_ONLY 0 INACTIVE 1 ACTIVE HUM_SENS_FAIL BV 908 HUMIDITY RANGE HIGH READ_ONLY 0 INACTIVE 1 ACTI...

Page 60: ...READ_WRITE 1 AUTO 2 ON 3 OVERRIDE AUTO 4 OVERRIDE ON FAN MODE MSV 406 Indoor Equipment Type READ_ONLY 1 NO INDOOR 2 FURNACE 3 AIR HANDLER ID_EQUIP_TYPE MSV 500 Outdoor Equipment Type GATED_WRITE 1 NO OUTDOOR 2 A C 3 HEAT PUMP OD_EQUIP_TYPE MSV 501 Remote Sensor Type GATED_WRITE 1 NONE 2 OUTDOOR 3 SPACE 4 AVERAGE 5 OCCUPANCY 6 FAULT_INPUT 7 SAT REMOTE_SENSOR MSV 502 Dehumidification Type GATED_WRIT...

Page 61: ...nt Name BACnet Object ID Network GP W2 Mode GATED_WRITE 1 DISABLED 2 ENERGIZED_ACTIVE 3 ENERGIZED_INACTIVE NET_GP_W2_MODE MSV 510 Network GP OB Mode GATED_WRITE 1 DISABLED 2 ENERGIZED_ACTIVE 3 ENERGIZED_INACTIVE NET_GP_OB_MODE MSV 511 Humidity Source GATED_WRITE 1 STAT 2 REMOTE HUM_SOURCE MSV 512 Remote Humidity Scale GATED_WRITE 1 2 10V 4 20mA w ext 500 Ohm 2 0 10V REM_HUM_SCALE MSV 513 ...

Page 62: ...state Value Objects BACnet Interoperability Building Blocks BIBBs Data Sharing BIBBs Execute Read Property DS RP B Execute Read Property Multiple DS RPM B Execute Write Property DS WP B Execute Write Property Multiple DS WPM B Device Management BIBBs Execute Who Is and Initiate I Am DM DDB B Execute Who Has and Initiate I Have DM DOB B Execute TimeSynchronization DM TS B Execute UTCTimeSynchroniza...

Page 63: ...t Reliability Property In addition to indicating sensor issues the BACnet Reliability property of the BACnet Objects conveys when the configuration does not support a given point Reliability Value Meaning No fault detected Configuration matches the object description and value is in range Shorted loop The Present_Value of this object indicates a shorted sensor Open loop The Present_Value of this o...

Page 64: ...mostat 33CONNECTSTAT43FX CARRIER CORPORATION 2021 Installation Guide All rights reserved 60 Instance Range Object Type 1XX Device Inputs 2XX Device Outputs 3XX Status 4XX User Configuration 5XX Installer Configuration 9XX Faults Appendix D BACnet Object Instance Ranges ...

Page 65: ...e is a configuration object and is backed up to non volatile memory If the network object s value has not been written to within 5 minutes the output of the multiplexer defaults to the measured input value Input Meas Input Object Network Object Object Used for Equip Control Space Temp ID_SPACE_TEMP AI100 NET_SP_TEMP AV103 SP_TEMP_CTRL AV104 Space Humidity ID_SPACE_HUM AI101 NET_SP_HUM AV105 SP_HUM...

Page 66: ...ive ENERGIZED_ACTIVE No De energized Inactive ENERGIZED_INACTIVE No Energized Active ENERGIZED_ACTIVE No Energized Active ENERGIZED_INACTIVE No De energized The following table shows the three outputs and the objects that configure and control them Controlling Object Mode Object Physical Output NET_GP_Y3_OUT BV211 NET_GP_Y3_MODE MSV509 Y3 NET_GP_W2_OUT BV212 NET_GP_W2_MODE MSV510 W2 NET_GP_OB_OUT ...

Page 67: ...ER CORPORATION 2021 Installation Guide All rights reserved 63 Important changes to this document are listed below Minor changes such as typographical or formatting errors are not listed Date Topic Change description Code No changes yet For internal use only Document revision history ...

Page 68: ......

Page 69: ......

Page 70: ...Carrier 2021 Catalog No 11 808 872 01 12 3 2021 ...

Reviews: