Wiring inputs and outputs
Carrier® ChillerVu™
(OPN-PSM-MPCXPE)
Carrier Proprietary and Confidential
CARRIER CORPORATION ©2017
Installation and Start-up Guide
19
All rights reserved
4
Set each input's
Universal Input Mode Select
jumper to indicate the type of input.
5
Connect digital and analog output wiring to the
UO
screw terminals on the Carrier® ChillerVu™ and to the
controlled device. Connect the ground wire to the UO's
Gnd
terminal.
WARNING!
Binary outputs are powered, 24 Vdc channels. Dry contact binary outputs are not
supported in the Carrier® ChillerVu™ product line. Do NOT apply 24 Vac to these universal outputs.