Wiring for third party protocols
Carrier® ChillerVu™
(OPN-PSM-MPCXPE)
Carrier Proprietary and Confidential
CARRIER CORPORATION ©2017
Installation and Start-up Guide
31
All rights reserved
7
Under
Options controlling local serial lines
, enter the following settings:
Field
Value
Serial line to connect
to
Replace X with the computer's port number that the USB Link Kit cable is
connected to.
NOTE
To find the port number, select
Start
>
Control Panel
>
System
>
Device Manager
>
Ports (Com & LPT)
. The COM port number is beside
Silicon Labs CP210x USB to UART Bridge
.
Speed (baud)
115200
Data Bits
8
Stop Bits
1
Parity
None
Flow Control
None
8
Click
Open
. A window similar to the one below appears.
9
Type
3
and press
Enter
.
10
Type the IP address and press
Enter
.
11
Repeat steps 9 and 10 to enter the Subnet Mask and default Gateway.
12
Type
1
, then press
Enter
to restart the controller.
13
When finished, set the Carrier® ChillerVu™'s
Enhanced Access
DIP switch to
OFF
to restore normal
functionality to the
Local Access
port.
14
Turn the Carrier® ChillerVu™'s power
Off
, then
On
.