background image

will be supplied, resulting in additional outputs being turned on. If
room overheats, specified outputs will not turn off, guaranteeing a
sufficiently warm leaving air temperature during defrost. Tempera-
ture overshoot during defrost can occur, but is almost never
noticeable because of the short duration of the defrost cycle (4
minutes typical, 10 minutes maximum).

An additional feature of Thermidistat Control defrost is that it
always allows defrost cycle to run to completion. The Thermidistat
Control leaves the Y output on as long as outdoor unit holds
voltage on the O line, even if it is satisfied. This prevents
premature termination of defrost cycles, which occur with normal
thermostats.

TO SELECT:

1. Enter configuration mode if not already there. See Step 4 "To

Enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 12.

2. Press SET TIME/TEMP button once to flash large display.

3. Use up or down buttons to move between 0, 1, 2, or 3 (if

available) on large display. See Table 1 for effect of these
choices. Factory default is 0.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to exit
configuration mode.

Option 13—Room Temperature Offset Adjust

This option allows calibration (or deliberate miscalibration) of
room temperature sensor. There are various reasons why home-
owners may want to have displayed temperature adjusted to a
higher or lower value. The selected number is number of degrees
farhenheit, plus or minus, which will be added to actual tempera-
ture. The numbers can range between -5 and +5. Factory default is
0. This adjusted value will be used as actual temperature for both
display and control action. For example, if 2 is selected, 72°F
actual will read 74°F. If set point is 72°F, the room will control to
an actual temperature of 70°F which will be displayed and acted
upon as if it were 72°F. The effect is that a positive number
selection will make the room temperature lower and vice versa.
The Thermidistat Control is calibrated within an accuracy of plus
or minus 1°F when shipped from the factory, so this adjustment
will provide the best accuracy when set to 0.

TO SELECT:

1. Enter configuration mode if not already there. See Step 4 "To

Enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 13.

2. Press SET TIME/TEMP button once to flash large display.

3. Use up or down buttons to move between -5, -4, -3, -2, -1, 0,

1, 2, 3, 4, or 5 on large display. Factory default is 0.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to exit
configuration mode.

Option 14—Heat/Cool Dead Band Adjustment

This option selects the minimum difference between heat and cool
set points. A larger difference saves energy and a smaller differ-
ence decreases temperature difference between heating and cool-
ing. Factory default is 2, which means cooling set point must be a
minimum of 2° above heating set point. An attempt to move them
closer will result in one "pushing" the other to maintain the
required difference.

Depending on set points, moving dead band closer than 2° may
result in regular cycling between heat and cool when AUTO mode
is selected. However, this cycling cannot occur more often than 1
transition every 20 minutes. The system has a built-in requirement

that it cannot switch between heat and cool without a 20 minute
"off" time between the 2 operations. Specifically, to switch from 1
mode to the other, there must be no demand for the old mode and
a demand for the new mode, and this must exist continually for 20
minutes before transition to the new mode will occur.

TO SELECT:

1. Enter configuration mode if not already there. See Step 4 "To

enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 14.

2. Press SET TIME/TEMP button once to flash large display.

3. Use up or down buttons to move between 0, 1, 2, 3, 4, 5, or 6

on large display. Factory default is 2.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to exit
configuration mode.

Option 15—Enable Auto Mode

This option allows the installer to enable or disable AUTO mode
(automatic changeover between heat and cool). When disabled,
AUTO icon does not appear when successive presses of MODE
button are used to move between OFF, HEAT, COOL, and
EHEAT (in heat pump systems). Factory default is ON (AUTO
enabled).

TO SELECT:

1. Enter configuration mode if not already there. See Step 4 "To

Enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 15.

2. Press SET TIME/TEMP button once to flash large display.

3. Use up and down buttons to move between OF and ON on

large display. Factory default is ON (AUTO enabled).

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to exit
configuration mode.

Option 16—Enable Super Comfort Heat Mode

This option requires prior ON selection of heat pump (DIP switch
No. 1) and Configuration Option No. 5 (Select Variable-Speed
Blower). Super Comfort Heat mode is part of the Comfort Heat
Pump system, which comprises a selected combination of Ther-
midistat Control, variable speed Fan Coil, and 3-stage electric
heater to provide superior heat pump leaving air temperatures
under all conditions. This option selection modifies heat pump
blower and auxiliary heat operation to contribute to comfortable
leaving air temperature. Specifically, this selection provides:

Reduced heat pump airflow for outdoor temperatures between
12° and 40°F.

At least 1 stage of electric heat ON for all heating below 12°F.

While outdoor air temperature is between 12°F and 40°F, the
Thermidistat Control removes the G signal during heat pump
heating. The 40FK, FK4C, or FV4A Variable-Speed Fan Coils
respond by reducing their airflow in the absence of the G signal,
raising leaving air temperature. For any heating demand below
12°F, G and W/W1 are turned ON, assuring at least 1 stage of
electric heat is on, and also increasing leaving air temperature.

As part of the Comfort Heat pump system, Configuration Option
No. 9 (Intelligent Heat Staging) should also be set to ON if the heat
pump is single stage and a 3-stage heater is present.

TO SELECT:

1. Enter configuration mode if not already there. See Step 4 "To

Enter Configuration Mode." Use up and down buttons to make
small (now flashing) display indicate 16.

2. Press SET TIME/TEMP button once to flash large display.

6

Summary of Contents for CCPRHO1-B

Page 1: ...programmable configuration it will still have both tem perature and humidity control Humidify and dehumidify outputs provide direct control of humidity Batteries are not used During power loss an internal memory stores programs and settings for unlimited time and the clock continues to run for at least 8 hr INSTALLATION CONSIDERATIONS POWER Note that this control does not require batteries and is ...

Page 2: ...lects a special installer test mode which assists with system startup and checkout See Step 5 System Startup and Check out TO SET OFF for normal operation This is factory default ON for installer test mode Step 3 Install Thermidistat Control Before installing Thermidistat Control turn off all power to equipment There may be more than 1 power disconnect Electrical shock can cause personal injury or...

Page 3: ...ating that up and down buttons now control available choices within that option Each press of TIME TEMP button switches between available option small display and available selections within each option large display CONFIGURATION OPTIONS SELECTION Option 1 Anticipator Adjustment This adjustment controls sensitivity and cycle rate of Thermidistat Control Higher numbers decrease sensitivity and slo...

Page 4: ...ion demand without a cooling demand achieving maximum humidity removal with minimum cooling It is done by supplying blower with a Y signal and no G signal on a call for cooling Not all products with ICM blowers have this feature Check Installation Instructions for ICM air handler used Select OF for normal operation Y and G supplied on a cooling call Select ON for super dehumidification Y with no G...

Page 5: ...oint the heat pump is the most cost efficient to operate and below this point the furnace is the most cost efficient to operate This can be somewhat complicated to determine and it involves knowing the cost of gas and electricity as well as the efficiency of the furnace and heat pump For the most economical operation the heat pump should operate above this temperature assuming it has sufficient ca...

Page 6: ... than 2 may result in regular cycling between heat and cool when AUTO mode is selected However this cycling cannot occur more often than 1 transition every 20 minutes The system has a built in requirement that it cannot switch between heat and cool without a 20 minute off time between the 2 operations Specifically to switch from 1 mode to the other there must be no demand for the old mode and a de...

Page 7: ... keypad label over the original Make sure the new keypad label does not interfere with the motion of the buttons which it surrounds TO SELECT 1 Enter configuration mode if not already there See Step 4 To Enter Configuration Mode Use up and down buttons to make small now flashing display indicate 17 2 Press SET TIME TEMP button once to flash large display 3 Use up and down buttons to move between O...

Page 8: ...em to change with programmed schedule The FAN button may be used to select between AUTO fan on only with equipment and FAN fan on continuously fan modes For further information on temperature selection and program ming refer to Homeowner s Guide HUMIDITY CONTROL FEATURES The various humidity control features of the Thermidistat Control are explained below They are grouped into 2 sections humidifi ...

Page 9: ... no more while attempting to satisfy a dehumidify demand Within this 3 range there is an additional balance between overcooling and humidity satisfaction When overcooling must occur the dehumidify set point is adjusted upward by 2 percent per degree of overcooling For example a cooling set point of 76 F and a dehumidify set point of 60 percent is equivalent to a cooling set point of 75 F and a deh...

Page 10: ...am literature Carrier 58MVP Furnaces also have a DEHUM input The DE HUM input acts differently depending on which style of variable speed furnace control you have The older style variable speed furnace control DOES NOT have a DE connection while the newer style variable speed furnace control has a DE connection Both of these variable speed furnace controls function the same except the DEHUM logic ...

Page 11: ...and DHUM outputs When humidification or dehumidification is active the triangle under its set point is turned on AUTO CHANGEOVER When auto changeover mode is selected a change from heat to cool or vice versa will not occur until an opposite mode demand has existed for 20 minutes If set point is changed 20 minute requirement is deleted EMERGENCY HEAT MODE When Thermidistat Control is configured as ...

Page 12: ...f or On factory default Off or Not Available 11 ______ Balance Point Setting Off or 5 55 F factory default Off or Not Available 12 ______ Defrost Heat Select 0 1 2 3 factory default 0 or Not Available 13 ______ Room Temperature Offset 5 to 5 factory default 0 14 ______ Heat Cool Dead Band 0 to 6 factory default 2 15 ______ Enable Auto Mode On or Off factory default On 16 ______ Enable Super Comfor...

Reviews: