background image

TO TEST COOLING AND DEHUMIDIFICATION:

Press MODE button until COOL icon turns on. Cooling begins
within 10 sec and remains on for 4 minutes. If system is 2-speed,
low speed comes on for first 2 minutes, followed by high speed for
second 2 minutes. At the end of 4-minute run, cooling stops, and
MODE reverts back to OFF. At any time during 4-minute run time,
cooling may be turned off by pressing MODE button until OFF
appears. While cooling is on, successive presses of HUMIDITY
button turn dehumidify output on and off. While this output is
active, "dh" appears in cool set point display. Equipment outputs
for different equipment types are listed in Table 2.

TO TEST PRIMARY HEATING AND HUMIDIFICATION:

Press MODE button until HEAT icon turns on. Primary heating
begins within 10 sec and remains on for 4 minutes. This will be
furnace or electric heat in AC system and heat pump heating in
heat pump system. If system has 2 stages of primary heat, first
stage will be on for 2 minutes followed by second stage for 2
minutes. At the end of 4-minute run, heating stops, and MODE
reverts back to OFF. At any time during 4-minute run time, heating
may be turned off by pressing MODE button until OFF appears.
While heating is on, successive presses of HUMIDITY button turn
humidify output on and off. While this output is active, "hu"
appears in heat set point display. Equipment outputs for different
equipment types are listed in Table 2.

TO TEST AUXILIARY HEATING:

Auxiliary heating only exists in heat pump systems. To test, press
MODE button until EHEAT icon turns on. This will be electric
heat in standard heat pump systems and furnace in dual fuel
systems. Auxiliary heating begins within 10 sec and remains on for
4 minutes. If there are 2 stages of auxiliary heat, first stage comes
on for 2 minutes followed by second stage for 2 minutes. At the
end of 4-minute run, heating stops and MODE reverts back to
OFF. At any time during 4-minute run time, heating may be turned
off by pressing MODE button until OFF appears. Actual outputs
for different equipment types are listed in Table 2.

Step 6—Final Settings

Be sure to return DIP switch No. 4 back to OFF position to exit
installer setup mode. Assuming system is to be left in operation
after installation is complete, use MODE button to select between
HEAT, COOL, or AUTO to provide desired operation of heating,
cooling, or both.

The default set points and programmed schedule conform to the
Energy Star® requirements of the U.S. Department of Energy for
both heating and cooling. These provide energy saving tempera-
ture settings. Refer to Table 3.

If programmed schedule is to be used, make sure HOLD icon is
off. This feature is turned on and off by HOLD button.

If fixed temperatures are desired, use HOLD button to turn on
HOLD icon. This will maintain set points, not allowing them to
change with programmed schedule.

The FAN button may be used to select between AUTO (fan on
only with equipment) and FAN (fan on continuously) fan modes.

For further information on temperature selection and program-
ming, refer to Homeowner’s Guide.

HUMIDITY CONTROL FEATURES

The various humidity control features of the Thermidistat Control
are explained below. They are grouped into 2 sections: humidifi-
cation and dehumidification. At the end of each section, instruc-
tions on how to select each feature are given.

HUMIDIFICATION

The Thermidistat Control directly connects to a standard 24-vac
humidifier to control humidification in the home. A humidify set
point between 10 and 45 percent relative humidity is selected by
the homeowner, or all humidification can be turned off. When
humidity in home drops below set point, humidifier will be turned
on to raise humidity level. Humidification can only occur in
heating mode (HEAT or AUTO/HEAT). Five different humidifi-
cation selections are available and are described below.

1. Normal Humidify

In normal humidify, humidifier will be on if there is a
humidity demand and any heating equipment is on. This will
include furnace, heat pump, or auxiliary heat. In heat pump
applications, this is an improvement over using an external
humidistat, which only supplies humidity when auxiliary heat
is on.

2. Fan Humidify

This configuration allows a humidify demand to turn on fan
and humidifier together, even if there is no heat demand. It is
particularly useful when the furnace is oversized, resulting in
short heating cycles. It allows the humidifier to run longer,
supplying more humidity to the home. Note that fan hours will
increase, using more electricity. Also, the humidifier delivers
less moisture to cooler air than it does to heated air.

3. Auto Humidify

This feature is designed to eliminate the problem of sweating
windows in very cold weather. When selected, the set point is
automatically reduced by 1 percent for every drop of 2°F in
outdoor temperature between 50°F and 0°F. The set point may
be changed at any time, and it will continue to track outdoor
temperature from the new set point and current outdoor
temperature. The adjusted set point range is still limited to
between 10 and 45 percent relative humidity. To use this
feature, an outdoor temperature sensor MUST be attached. If
not, E3 error message will be displayed.

Table 2—Equipment Outputs

1-SPEED AC

2-SPEED AC

1-SPEED HP

2-SPEED HP

Cool—0 to 2 minutes

Y, G

Y1, G

Y, G, O

Y1, G, O

Cool—2 to 4 minutes

Y, G

Y1, Y2, G

Y, G, O

Y1, Y2, G, O

Heat—0 to 2 minutes

W1

W1

Y, G

Y1, G

Heat—2 to 4 minutes

W1, W2

W1, W2

Y, G

Y1, Y2, G

Eheat—0 to 2 minutes

---

---

W1

W1

Eheat—2 to 4 minutes

---

---

W1, W2†

W1*

* Two-stage heat not available

NOTE: For Y—use terminal Y/Y2, for Y1—use terminal Y1/W2, for W2—use terminal O/W2,

for O—use terminal O/W2, for W1—use terminal W/W1, for W2†, use terminal Y1/W2

Table 3—Energy Star Default Schedule

SCHEDULE

HEAT

COOL

Wake 6:00 AM

68°F

78°F

Day 8:00 AM

60°F

85°F

Evening 5:00 PM

68°F

78°F

Sleep 10:00 PM

60°F

82°F

8

Summary of Contents for CCPRHO1-B

Page 1: ...programmable configuration it will still have both tem perature and humidity control Humidify and dehumidify outputs provide direct control of humidity Batteries are not used During power loss an internal memory stores programs and settings for unlimited time and the clock continues to run for at least 8 hr INSTALLATION CONSIDERATIONS POWER Note that this control does not require batteries and is ...

Page 2: ...lects a special installer test mode which assists with system startup and checkout See Step 5 System Startup and Check out TO SET OFF for normal operation This is factory default ON for installer test mode Step 3 Install Thermidistat Control Before installing Thermidistat Control turn off all power to equipment There may be more than 1 power disconnect Electrical shock can cause personal injury or...

Page 3: ...ating that up and down buttons now control available choices within that option Each press of TIME TEMP button switches between available option small display and available selections within each option large display CONFIGURATION OPTIONS SELECTION Option 1 Anticipator Adjustment This adjustment controls sensitivity and cycle rate of Thermidistat Control Higher numbers decrease sensitivity and slo...

Page 4: ...ion demand without a cooling demand achieving maximum humidity removal with minimum cooling It is done by supplying blower with a Y signal and no G signal on a call for cooling Not all products with ICM blowers have this feature Check Installation Instructions for ICM air handler used Select OF for normal operation Y and G supplied on a cooling call Select ON for super dehumidification Y with no G...

Page 5: ...oint the heat pump is the most cost efficient to operate and below this point the furnace is the most cost efficient to operate This can be somewhat complicated to determine and it involves knowing the cost of gas and electricity as well as the efficiency of the furnace and heat pump For the most economical operation the heat pump should operate above this temperature assuming it has sufficient ca...

Page 6: ... than 2 may result in regular cycling between heat and cool when AUTO mode is selected However this cycling cannot occur more often than 1 transition every 20 minutes The system has a built in requirement that it cannot switch between heat and cool without a 20 minute off time between the 2 operations Specifically to switch from 1 mode to the other there must be no demand for the old mode and a de...

Page 7: ... keypad label over the original Make sure the new keypad label does not interfere with the motion of the buttons which it surrounds TO SELECT 1 Enter configuration mode if not already there See Step 4 To Enter Configuration Mode Use up and down buttons to make small now flashing display indicate 17 2 Press SET TIME TEMP button once to flash large display 3 Use up and down buttons to move between O...

Page 8: ...em to change with programmed schedule The FAN button may be used to select between AUTO fan on only with equipment and FAN fan on continuously fan modes For further information on temperature selection and program ming refer to Homeowner s Guide HUMIDITY CONTROL FEATURES The various humidity control features of the Thermidistat Control are explained below They are grouped into 2 sections humidifi ...

Page 9: ... no more while attempting to satisfy a dehumidify demand Within this 3 range there is an additional balance between overcooling and humidity satisfaction When overcooling must occur the dehumidify set point is adjusted upward by 2 percent per degree of overcooling For example a cooling set point of 76 F and a dehumidify set point of 60 percent is equivalent to a cooling set point of 75 F and a deh...

Page 10: ...am literature Carrier 58MVP Furnaces also have a DEHUM input The DE HUM input acts differently depending on which style of variable speed furnace control you have The older style variable speed furnace control DOES NOT have a DE connection while the newer style variable speed furnace control has a DE connection Both of these variable speed furnace controls function the same except the DEHUM logic ...

Page 11: ...and DHUM outputs When humidification or dehumidification is active the triangle under its set point is turned on AUTO CHANGEOVER When auto changeover mode is selected a change from heat to cool or vice versa will not occur until an opposite mode demand has existed for 20 minutes If set point is changed 20 minute requirement is deleted EMERGENCY HEAT MODE When Thermidistat Control is configured as ...

Page 12: ...f or On factory default Off or Not Available 11 ______ Balance Point Setting Off or 5 55 F factory default Off or Not Available 12 ______ Defrost Heat Select 0 1 2 3 factory default 0 or Not Available 13 ______ Room Temperature Offset 5 to 5 factory default 0 14 ______ Heat Cool Dead Band 0 to 6 factory default 2 15 ______ Enable Auto Mode On or Off factory default On 16 ______ Enable Super Comfor...

Reviews: