background image

Vacation Dehumidification

Normal Dehumidify, Cool to Dehumidify, and Dehumidify OFF,
are all available in vacation mode, and selection of 1 of these can
be different from that of occupied. Vacation dehumidification
selection and set points are remembered the next time vacation is
used.

Cool to dehumidify operates slightly differently, allowing the
home to be cooled to as low as 70°F when trying to achieve
dehumidify set point. The balance between dehumidify and
temperature set point adjustments is 1 percent set point increase
per degree of overcooling for temperatures below 76°F. For
example, at 74°F dehumidify set point is raised 2 percent, and at
72°F dehumidify set point is raised 4 percent. At temperatures
above 76°F, dehumidify set point is not changed.

OPERATIONAL INFORMATION

FIVE-MINUTE COMPRESSOR TIMEGUARD

This timer prevents compressor from starting unless it has been off
for at least 5 minutes. It can be defeated for 1 cycle by
simultaneously pressing FAN button and INCREASE TEMPERA-
TURE button.

FIFTEEN-MINUTE CYCLE TIMER

This timer prevents the start of a heating or cooling cycle until at
least 15 minutes after the last start of the same cycle. Its function
is to assure that equipment is not cycled more than 4 times per hr.
This timer is defeated for 1 cycle when desired temperature is
manually changed. It can also be defeated for 1 cycle by
simultaneously pressing FAN button and INCREASE TEMPERA-
TURE button.

FIFTEEN-MINUTE STAGING TIMER

In multistage heating or cooling, this timer prevents any higher
stage from turning on until preceding stage has been on for 15
minutes. This timer is defeated if temperature error is greater than
5°F (usually due to a large change in desired temperature).

THREE-MINUTE MINIMUM ON TIME

In normal operation, when a stage turns on, it will not turn off for
a minimum of 3 minutes. If the set point is changed, this timer is
automatically canceled, allowing the equipment to turn off imme-
diately when the demand is removed.

HEAT/COOL SET POINTS (DESIRED TEMPERATURE)

A minimum difference of 2° is enforced between heating and
cooling desired temperatures. This is done by allowing 1 setting to
"push" the other, to maintain this difference. This difference is
adjustable via Configuration Option 14.

EQUIPMENT ON INDICATORS

When cooling equipment is on, a COOL icon preceded by a small
triangle is displayed below cool set point. While cooling equip-
ment turn on is delayed by a staging or cycle timer, triangle will
flash. The same is true for HEAT icon and its preceding triangle

located under heat set point. These 2 arrows are also used to
indicate state of humidify and dehumidify outputs. See next
section.

HUMIDIFY AND DEHUMIDIFY INDICATORS

The humidity screen (selected by pressing the HUMIDITY button)
uses the same triangles referenced in the above paragraph to
indicate the state of the HUM and DHUM outputs. When
humidification or dehumidification is active, the triangle under its
set point is turned on.

AUTO CHANGEOVER

When auto changeover mode is selected, a change from heat to
cool (or vice versa) will not occur until an opposite mode demand
has existed for 20 minutes. If set point is changed, 20-minute
requirement is deleted.

EMERGENCY HEAT MODE

When Thermidistat Control is configured as a heat pump and
emergency heat is selected, all Y signals are locked out, and W
becomes energized upon a call for heat.

POWER ON CHECK

When AC power is first applied, all segments of display are turned
on for a few seconds. Following this, temperature display indicates
model/configuration via following 2-digit code:

AC—1-speed air conditioner, HP—1-speed heat pump, A2—2-
speed air conditioner, H2—2-speed heat pump, HS—1-speed heat
pump with 3-stage auxiliary heat, dF—dual fuel, d2—dual fuel
with 2-speed.

ERROR CODES

"--" — If Thermidistat Control cannot properly read room tem-

perature, display will indicate -- and all outputs (except
fan if on) will turn off.

E1, E2 — There is no E1 or E2 error message.
E3 — If Thermidistat Control cannot properly read outdoor

temperature, and it is needed for proper operation, display
will indicate E3.

E4 — If Thermidistat Control’s internal memory fails, E4 will be

displayed. Replace Thermidistat Control.

E5 — If Thermidistat Control cannot properly read humidity, E5

will be displayed. Replace Thermidistat Control.

E6 — If defrost cycle continues for longer than 15 minutes. E6

will be displayed. Check heat pump wiring or for failed
heat pump defrost control.

SMART RECOVERY

With Smart Recovery selected, transition out of setback begins a
fixed time period before selected recovery time and gradually
adjusts room temperature so desired temperature will be achieved
at selected recovery time. The fixed time period is 1.5 hr. It
operates in both heating and cooling. This only applies to
programmable operation.

Thermidistat Control Troubleshooting

SYMPTOM

WHAT TO CHECK

No display

Open Thermidistat Control. Check for 24vac between R and C at screw terminals on mounting base. Reassemble, making
sure pins on board engage sockets in mounting base. If display does not appear, replace Thermidistat Control.

"--" in place of room temperature

Thermidistat Control cannot properly read room temperature. Replace Thermidistat Control.

"E3" or "--" in place of outdoor temperature Thermidistat Control cannot properly read outdoor temperature. Check outdoor sensor and its wiring.

"E4" or "E5"

Internal failure. Replace Thermidistat Control.

"E6"

System is stuck in defrost. Check wiring and heat pump defrost control board.

"Clean Filter" icon displayed

Filter timer has expired. Clean or replace filter and then press VACATION and HOLD/END buttons together to reset.

Cooling or heating will not come on

See Installer Setup to force heating or cooling. Check for 24vac at equipment terminals. If not present, check wiring.

Humidify or dehumidify will not come on

See Installer Setup to force HUM or DEHUM. Check for 24vac at equipment terminals. If not present, check wiring.

11

Summary of Contents for CCPRHO1-B

Page 1: ...programmable configuration it will still have both tem perature and humidity control Humidify and dehumidify outputs provide direct control of humidity Batteries are not used During power loss an internal memory stores programs and settings for unlimited time and the clock continues to run for at least 8 hr INSTALLATION CONSIDERATIONS POWER Note that this control does not require batteries and is ...

Page 2: ...lects a special installer test mode which assists with system startup and checkout See Step 5 System Startup and Check out TO SET OFF for normal operation This is factory default ON for installer test mode Step 3 Install Thermidistat Control Before installing Thermidistat Control turn off all power to equipment There may be more than 1 power disconnect Electrical shock can cause personal injury or...

Page 3: ...ating that up and down buttons now control available choices within that option Each press of TIME TEMP button switches between available option small display and available selections within each option large display CONFIGURATION OPTIONS SELECTION Option 1 Anticipator Adjustment This adjustment controls sensitivity and cycle rate of Thermidistat Control Higher numbers decrease sensitivity and slo...

Page 4: ...ion demand without a cooling demand achieving maximum humidity removal with minimum cooling It is done by supplying blower with a Y signal and no G signal on a call for cooling Not all products with ICM blowers have this feature Check Installation Instructions for ICM air handler used Select OF for normal operation Y and G supplied on a cooling call Select ON for super dehumidification Y with no G...

Page 5: ...oint the heat pump is the most cost efficient to operate and below this point the furnace is the most cost efficient to operate This can be somewhat complicated to determine and it involves knowing the cost of gas and electricity as well as the efficiency of the furnace and heat pump For the most economical operation the heat pump should operate above this temperature assuming it has sufficient ca...

Page 6: ... than 2 may result in regular cycling between heat and cool when AUTO mode is selected However this cycling cannot occur more often than 1 transition every 20 minutes The system has a built in requirement that it cannot switch between heat and cool without a 20 minute off time between the 2 operations Specifically to switch from 1 mode to the other there must be no demand for the old mode and a de...

Page 7: ... keypad label over the original Make sure the new keypad label does not interfere with the motion of the buttons which it surrounds TO SELECT 1 Enter configuration mode if not already there See Step 4 To Enter Configuration Mode Use up and down buttons to make small now flashing display indicate 17 2 Press SET TIME TEMP button once to flash large display 3 Use up and down buttons to move between O...

Page 8: ...em to change with programmed schedule The FAN button may be used to select between AUTO fan on only with equipment and FAN fan on continuously fan modes For further information on temperature selection and program ming refer to Homeowner s Guide HUMIDITY CONTROL FEATURES The various humidity control features of the Thermidistat Control are explained below They are grouped into 2 sections humidifi ...

Page 9: ... no more while attempting to satisfy a dehumidify demand Within this 3 range there is an additional balance between overcooling and humidity satisfaction When overcooling must occur the dehumidify set point is adjusted upward by 2 percent per degree of overcooling For example a cooling set point of 76 F and a dehumidify set point of 60 percent is equivalent to a cooling set point of 75 F and a deh...

Page 10: ...am literature Carrier 58MVP Furnaces also have a DEHUM input The DE HUM input acts differently depending on which style of variable speed furnace control you have The older style variable speed furnace control DOES NOT have a DE connection while the newer style variable speed furnace control has a DE connection Both of these variable speed furnace controls function the same except the DEHUM logic ...

Page 11: ...and DHUM outputs When humidification or dehumidification is active the triangle under its set point is turned on AUTO CHANGEOVER When auto changeover mode is selected a change from heat to cool or vice versa will not occur until an opposite mode demand has existed for 20 minutes If set point is changed 20 minute requirement is deleted EMERGENCY HEAT MODE When Thermidistat Control is configured as ...

Page 12: ...f or On factory default Off or Not Available 11 ______ Balance Point Setting Off or 5 55 F factory default Off or Not Available 12 ______ Defrost Heat Select 0 1 2 3 factory default 0 or Not Available 13 ______ Room Temperature Offset 5 to 5 factory default 0 14 ______ Heat Cool Dead Band 0 to 6 factory default 2 15 ______ Enable Auto Mode On or Off factory default On 16 ______ Enable Super Comfor...

Reviews: