50HJQ004---016

50TFQ004---012

50HEQ003---006

Single---Package Rooftop

Standard and High Efficiency Heat Pump Units

Product Data

C06101

50HJQ004--007, 50TFQ004--007, 50HEQ003--006

C06102

50HJQ008--012, 50TFQ008--012

C06103

50HJQ014--016

Standard-Efficiency (TFQ), and High-Efficiency (HJQ and

HEQ) heat pump units offer:

S

Pre-painted galvanized steel cabinet for long life and
quality appearance.

S

Commercial strength base rails with built-in rigging
capability.

S

Convertible

design

for

vertical

or

horizontal

supply/return.

S

Non-corrosive, sloped condensate drain pan, meets
ASHRAE 62 (IAQ).

S

Two-inch return-air filters.

S

A wide assortment of factory-installed options
available, including high-static drives that provide

additional performance range.

S

Factory-installed PremierLink

digital communicating

controls.

S

Factory-installed optional gear driven EconoMi$er IV
(vertical return for sizes 004-012 only) for use with
standard rooftop unit controls (in-cludes CO

2

sensor

control capability).

S

Factory-installed optional gear driven EconoMi$er2
(vertical return only) for use with PremierLink DDC
controls (includes 4 to 20 mA actuator for demand

control ventilation).

S

State-of-the-art defrost system.

S

Dependable 4-way valve operation.

Heat Options

S

Field-installed electric heat available.

S

Glycol hydronic coils.

FEATURES/BENEFITS

Every compact one-piece unit arrives fully assembled, charged,
tested, and ready to run.
Quiet, efficient operation and dependable performance.
Compressors have vibration isolators for quiet operation.
Efficient fan and motor design permits operation at low sound

levels.

Summary of Contents for APOLLO CONTROL 50HJQ004-016

Page 1: ... that provide additional performance range S Factory installed PremierLink digital communicating controls S Factory installed optional gear driven EconoMi er IV vertical return for sizes 004 012 only for use with standard rooftop unit controls in cludes CO2 sensor control capability S Factory installed optional gear driven EconoMi er2 vertical return only for use with PremierLink DDC controls incl...

Page 2: ...t board can be easily configured for defrost cycles every 30 50 or 90 minutes Dependable 4 way valve operation safely and efficiently accomplishes cycle reversals defrost and normal operation Easy installation and conversion All units are shipped in the vertical duct configuration for fit up to standard roof curbs 3 different curb sizes fit unit sizes 003 007 008 012 and 014 016 respectively The c...

Page 3: ...016 are equipped with a manual 25 damper Service options Servicing a rooftop unit has never been easier with the new factory installed service options for these rooftop units These options include the following S Hinged access panels are provided for the filter indoor fan motor compressors indoor fan and control box areas Quick access to major components is accomplished by simply unlatching and sw...

Page 4: ...e growth of mold and mildew The 62AQ Energy Recycler unit provides the best solution to retaining the energy conserving benefits of today s tighter building construction while improving indoor air quality MODEL NUMBER NOMENCLATURE 50 TFQ 004 P 5 0 1 AA TFQ Standard Efficiency Heat Pump 50 Electric Cooling Design Series 0 Original Factory Installed Option Code Nominal Capacity 004 3 Tons 008 7 1 2 ...

Page 5: ...5 50HEQ003 006 ...

Page 6: ...m Fin Copper Tube Indoor Coil V Pre Coated Aluminum Fin Copper Tube Outdoor Coil and Aluninum Fin Copper Tube Indoor Coil Refer to 50HJQ Price Pages for FIOP factory installed option code table Quality Assurance Certified to ISO 9001 2000 50HJQ004 012 50 HJQ 016 C 6 2 1 YA HJQ High Efficiency Heat Pump Fan Drive Motor Standard Motor 50 Electric Cooling Design Series 2 Gear Driven EconoMi er IV Des...

Page 7: ...th ARI Standards 210 240 95 and 270 95 2 Ratings are net values reflecting the effects of circulating fan heat 3 ALL the 50HJQ and 50TFQ004 005 and 006 units are in compliance with ASHRAE 90 1 2001 Energy Standard for minimum SEER and EER requirements Refer to state and local codes or visit the following website http bcap energy org to determine if compliance with this standard pertains to a given...

Page 8: ...ng air temperature and 17 F db 15 F wb outdoor entering air temperature LEGEND COP Coefficient of Performance Cap Net Capacity Btuh EER Energy Efficiency Ratio HSPF Heating Seasonal Performance Factor IPLV Integrated Part Load Values SEER Seasonal Energy Efficiency Ratio EER Energy Efficiency Ratio ARI CAPACITY RATINGS 50HJQ014 016 UNITS COOLING HEATING HIGH TEMP HEATING LOW TEMP SOUND UNIT 50HJQ ...

Page 9: ...001 Energy Standard for minimum SEER and EER requirements Refer to state and local codes or visit the following website http bcap energy org to determine if compliance with this standard pertains to a given geographical area of the United States 4 Ratings are based on Cooling Standard 80_F db 67_F wb indoor entering air temperature and 95_F db air entering outdoor unit IPLV Standard 80_F db 67_F w...

Page 10: ...nel Kit for Economizer X Indoor Air Quality CO2 Sensor X Manual Outdoor Air Damper 50 or 100 X Motormaster I II IV Head Pressure Control Low Ambient Kit X Novar Control X Outdoor Air Enthalpy Sensor X Outdoor Air Return Air Temperature Sensor X Outdoor Coil Grille X Outdoor Coil Hail Guard Assembly X Power Exhaust Transformer for 575 v X Power Exhaust with Barometric Relief X Pre coat Aluminum Fin...

Page 11: ... Economizer X Indoor Air Quality CO2 Sensor X Manual Outdoor Air Damper X Motormaster I II IV Head Pressure Control Low Ambient Kit X Novar Control X Outdoor Air Enthalpy Sensor X Outdoor Coil Grille X Outdoor Coil Hail Guard Assembly X Outdoor Air Return Air Temperature Sensor X Power Exhaust Transformer for 575 v X Power Exhaust with Barometric Relief X Pre coat Aluminum Fins on Outdoor Coil X P...

Page 12: ... Hydronic Glycol Coil X Indoor Air Quality CO2 Sensor X Manual Outdoor Air Damper X Motormaster V Head Pressure Control Low Ambient Kit X Outdoor Air Enthalpy Sensor X Power Exhaust without Barometric Relief X Pre coat Aluminum Fins on Outdoor Coil X PremierLink DDC Communicating Control X X Return Air Enthalpy Sensor X Return Air Temperature Sensor X Roof Curbs Vertical and Horizontal Discharge X...

Page 13: ...an accessory Both 25 or 100 outdoor air dampers are available Head pressure control Motormaster accessory package maintains condensing temperature between 90_F and 110_F at outdoor ambient temperatures down to 20_F by condenser fan speed modulation or condenser fan cycling and wind baffles Electric resistance heaters are one stage per heater module Single point kits are required as specified to me...

Page 14: ...PPORT RAIL C06059 ACCESSORY ENERGY RECYCLER 3 TO 12 1 2 TON UNITS ONLY TR1 24 Vac COM TR 24 Vac HOT 1 2 3 4 5 EF EF1 _ P1 T1 P T N EXH 2V 10V EXH Set Set 2V 10V 2V 10V DCV DCV Free Cool B C A D SO SR SR SO AQ1 AQ DCV Min Pos Open Max N1 C06038 ECONOMI ER IV CONTROL ECONOMI ER IV CONTROLLER OUTSIDE AIR TEMPERATURE SENSOR LOW AMBIENT SENSOR ACTUATOR WIRING HARNESS C06021 GEAR DRIVEN ECONOMI ER IV CO...

Page 15: ...15 OPTIONS AND ACCESSORIES CONT C06060 UNIT MOUNTED DISCONNECT Sizes 004 012 C06062 CONVENIENCE OUTLET C06061 UNIT MOUNTED DISCONNECT Sizes 014 016 50TFQ HJQ HEQ ...

Page 16: ...NOTE Hinged access panels are not available on 50TFQ units C06065 COMPRESSOR HINGED PANEL OPTION 50HJQ008 012 UNITS SHOWN C06066 COMPRESSOR HINGED PANEL OPTION 50HJQ004 006 UNITS SHOWN NOTE Hinged access panels are not available on 50TFQ units C06067 EVAPORATOR FAN HINGED PANEL OPTION C06068 FILTER HINGED PANEL OPTION 50TFQ HJQ HEQ ...

Page 17: ...ge Std 1070 1460 Alt 760 1000 770 1175 878 1192 High Static 1075 1455 1075 1455 1300 1685 1300 1685 Motor Bearing Type Ball Ball Ball Ball Maximum Allowable Rpm 2100 2100 2100 2100 Motor Pulley Pitch Diameter Min Max in Std 2 8 3 8 Alt 1 9 2 9 1 9 2 9 2 4 3 4 High Static 2 8 3 8 2 8 3 8 3 4 4 4 3 4 4 4 Nominal Motor Shaft Diameter in Std 1 2 1 2 1 2 5 8 Alt 1 2 1 2 5 8 High Static 5 8 5 8 5 8 5 8 ...

Page 18: ... Static 860 1080 830 1130 Motor Bearing Type Ball Ball Maximum Allowable Rpm 2100 2100 Motor Pulley Pitch Diameter Min Max in Std 2 4 3 4 2 8 3 8 Alt 2 8 3 8 3 4 4 4 High Static 4 0 5 0 2 8 3 8 Nominal Motor Shaft Diameter in Std 5 8 5 8 Alt 5 8 7 8 High Static 7 8 7 8 Fan Pulley Pitch Diameter in Std 7 0 7 0 Alt 7 0 7 0 High Static 8 0 5 8 Belt Quantity Type Length in Std 1 A 53 1 A 49 Alt 1 A 49...

Page 19: ...19 BASE UNIT DIMENSIONS 50TFQ004 007 50 TFQ C06069 50TFQ ...

Page 20: ...20 BASE UNIT DIMENSIONS 50TFQ008 012 C06070 50TFQ ...

Page 21: ...limeters 4 Roof curb galvanized steel 5 Attach ductwork to curb flanges of duct rest on curb 6 Service clearance 4 ft on each side 7 Direction of airflow 8 Connector packages CRBTMPWR001A00 and 002A00 are for thru the curb type gas Packages CRBTMPWR003A00 and 004A00 are for thru the bottom type gas connections CONNECTOR PKG ACCY B C D ALT DRAIN HOLE GAS POWER CONTROL CRBTMPWR001A00 1 911 16 551 1 ...

Page 22: ... 19 NPT 1 2 12 7 NPT CRBTMPWR004A00 3 4 19 NPT 11 4 31 7 NOTES 1 Roof curb accessory is shipped disassembled 2 Insulated panels 1 in thick polyurethane foam 13 4 lb density 3 Dimensions in are in millimeters 4 Roof curb 16 gage steel 5 Attach ductwork to curb flanges of duct rest on curb 6 Service clearance 4 ft on each side 7 Direction of airflow 8 Connector packages CRBTMPWR001A00 and 2A00 are f...

Page 23: ...s required The required heating capacity is 35 000 Btuh Therefore 17 000 Btuh 35 000 18 000 additional electric heat is required Determine additional electric heat capacity in kW 17 000 Btuh 5 0 kW of heat required 3413 Btuh kW Enter the Electric Heating Capacities table for 50TFQ005 at 208 230 3 phase The 6 5 kW heater at 240 v most closely satisfies the heating required To calculate kW at 230 v ...

Page 24: ... 63 TC 46 6 42 4 38 0 48 8 44 6 40 6 50 2 45 8 43 2 115 SHC 21 7 27 9 33 6 24 3 32 4 38 7 26 8 36 1 41 2 115 kW 5 08 4 90 4 66 5 21 5 01 4 81 5 29 5 06 4 96 TC 44 0 39 6 35 4 45 6 41 6 38 3 47 0 42 9 40 9 125 SHC 20 9 26 9 32 4 23 3 31 6 36 5 25 9 35 6 39 0 125 kW 5 45 5 21 4 96 5 51 5 34 5 14 5 60 5 41 5 30 50TFQ006 5 TONS Temp F Indoor Entering Air Cfm BF Temp F Outdoor E t i Ai 1500 0 05 2000 0...

Page 25: ... 94 6 70 6 48 TC 105 2 96 4 87 0 111 4 102 2 92 6 113 0 104 0 95 0 114 6 105 8 97 6 85 SHC 42 8 55 6 67 6 48 4 65 0 80 0 50 8 69 0 84 4 53 4 73 8 88 8 85 kW 7 20 6 94 6 64 7 42 7 14 6 82 7 48 7 20 6 90 7 54 7 28 7 00 TC 100 6 91 0 82 0 105 6 96 2 87 4 107 2 98 0 89 8 108 6 99 6 92 8 95 SHC 41 6 54 0 65 8 47 0 63 2 77 8 49 4 67 4 81 4 52 0 72 2 84 6 95 kW 7 78 7 42 7 08 7 96 7 62 7 30 8 00 7 70 7 4...

Page 26: ...m tlwb Wet bulb temperature corresponding to enthalpy of air leaving indoor coil hlwb h total capacity Btuh hlwb hewb 4 5 x cfm Where hewb Enthalpy of air entering evaporator coil 3 The Shc is based on 80_F edb termperature of air entering indoor coil Below 80_F edb subtract corr factor x cfm from SHC Above 80_F edb add corr factor x cfm to SHC INSTANTANEOUS AND INTEGRATED HEATING RATINGS 50TFQ004...

Page 27: ...Outdoor Coil F Air F db Standard Air 0 10 17 30 40 47 50 60 1500 Cap 29 7 25 2 34 5 31 7 38 4 35 0 46 0 40 3 52 4 52 4 57 2 57 2 59 6 59 6 67 9 67 9 1500 kW 3 96 4 14 4 30 4 62 4 90 5 14 5 25 5 67 55 2000 Cap 29 8 25 4 34 7 31 8 38 6 35 2 46 3 40 6 52 9 52 9 57 7 57 7 60 1 60 1 68 7 68 7 55 2000 kW 3 83 3 98 4 12 4 38 4 63 4 82 4 91 5 25 2500 Cap 29 8 25 4 34 8 31 9 38 7 35 3 46 6 40 8 53 1 53 1 5...

Page 28: ...ture Entering Outdoor Coil F Air F db Standard Air 0 10 17 30 40 47 50 60 2000 Cap 36 6 31 2 44 0 40 4 49 8 45 4 61 4 53 8 70 4 70 4 77 4 77 4 80 6 80 6 91 8 91 8 2000 kW 5 24 5 64 5 94 6 58 7 08 7 50 7 68 8 32 55 2600 Cap 37 6 32 0 45 2 41 4 51 2 46 6 63 0 55 2 72 4 72 4 79 6 79 6 83 0 83 0 92 4 92 4 55 2600 kW 5 18 5 56 5 82 6 40 6 84 7 20 7 36 7 78 3200 Cap 38 2 32 4 45 8 42 0 51 8 47 2 63 8 55...

Page 29: ...100 Cap 51 0 43 2 60 6 55 6 68 6 62 6 83 6 73 2 95 6 95 6 104 2 104 2 108 4 108 4 123 4 123 4 4100 kW 7 74 8 06 8 32 8 82 9 26 9 62 9 78 10 40 4400 Cap 51 0 43 4 60 8 55 8 68 8 62 6 83 8 73 4 95 8 95 8 104 4 104 4 108 6 108 6 123 8 123 8 4400 kW 7 70 8 02 8 26 8 74 9 16 9 50 9 66 10 26 2650 Cap 47 6 40 6 57 6 52 8 64 6 58 8 80 2 70 4 92 0 92 0 101 0 101 0 105 2 105 2 119 8 119 8 2650 kW 8 72 9 20 ...

Page 30: ...44 1205 0 86 855 1500 900 0 51 504 1002 0 62 617 1090 0 74 731 1169 0 85 846 1242 0 97 963 50TFQ004 3 TONS ALTERNATE MOTOR AND DRIVE cont Airflow External Static Pressure in wg Airflow Cf 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 1110 0 54 538 1177 0 63 627 1239 0 72 718 1298 0 82 813 1355 0 92 911 1000 1141 0 61 607 1207 0 70 700 1269 0 80 7...

Page 31: ... 09 1088 1444 1 21 1200 1300 1239 0 87 863 1303 0 98 972 1364 1 09 1084 1421 1 21 1199 1475 1 32 1316 1400 1273 0 97 967 1337 1 09 1082 1397 1 21 1200 1453 1 33 1320 1507 1 45 1443 1500 1309 1 09 1082 1371 1 21 1204 1430 1 33 1327 1486 1 46 1453 1540 1 59 1581 LEGEND Bhp Brake Horsepower Input to Fan Watts Input Watts to Motor Motor drive range 1075 to 1455 rpm All other rpms require a field suppl...

Page 32: ...0 811 0 35 352 920 0 45 451 1013 0 55 550 1095 0 66 652 1170 0 76 756 1400 855 0 43 423 960 0 53 529 1051 0 64 636 1132 0 75 744 1205 0 86 855 1500 900 0 51 504 1002 0 62 617 1090 0 74 731 1169 0 85 846 1242 0 97 963 1600 945 0 60 594 1044 0 72 716 1130 0 84 837 1207 0 96 959 1278 1 09 1083 1700 991 0 70 696 1086 0 83 825 1170 0 96 954 1246 1 09 1083 1316 1 22 1214 1800 1038 0 81 810 1130 0 95 947...

Page 33: ...23 1600 847 0 49 432 948 0 63 557 1042 0 79 694 1130 0 96 843 1213 1 14 1003 1700 887 0 57 501 983 0 72 632 1073 0 88 774 1158 1 06 928 1239 1 24 1092 1800 928 0 66 579 1020 0 82 715 1106 0 98 863 1188 1 16 1021 1266 1 35 1189 1900 969 0 76 666 1057 0 92 808 1140 1 09 960 1219 1 28 1123 1295 1 48 1296 2000 1010 0 87 761 1095 1 04 909 1175 1 21 1066 1251 1 41 1234 1325 1 61 1411 2100 1052 0 99 866 ...

Page 34: ...1485 2 30 2020 1547 2 54 2228 1608 2 79 2445 2400 1516 2 49 2182 1577 2 73 2395 2500 1549 2 69 2357 LEGEND Bhp Brake Horsepower Input to Fan Watts Input Watts to Motor Motor drive range 1300 to 1685 rpm All other rpms require a field supplied drive See General Fan Performance notes NOTES 1 Shaded cells indicate field supplied drive is required 2 Maximum continuous bhp is 2 90 50TFQ007 6 TONS STAND...

Page 35: ...8 2 40 2104 1499 2 63 2309 1559 2 87 2522 2800 1354 2 17 1901 1417 2 39 2096 1478 2 62 2300 1537 2 86 2510 2900 1398 2 39 2098 1459 2 62 2299 1518 2 86 2508 3000 1442 2 63 2308 1501 2 87 2516 50TFQ007 6 TONS HIGH STATIC MOTOR AND BELT DRIVE cont Airflow External Static Pressure in wg Airflow Cf 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1341 ...

Page 36: ...25 2098 3200 662 1 42 1324 726 1 65 1542 784 1 89 1765 838 2 14 1994 888 2 39 2229 3300 679 1 54 1438 741 1 78 1663 798 2 03 1892 851 2 28 2126 3400 695 1 67 1558 756 1 92 1790 812 2 17 2025 3500 712 1 81 1686 772 2 06 1923 827 2 32 2165 3600 729 1 95 1820 787 2 21 2065 3700 746 2 10 1962 803 2 37 2213 3750 754 2 18 2036 50TFQ008 71 2 TONS STANDARD MOTOR AND DRIVE cont Airflow External Static Pres...

Page 37: ...62 1 42 1324 726 1 65 1542 784 1 89 1765 838 2 14 1994 888 2 39 2229 3300 679 1 54 1438 741 1 78 1663 798 2 03 1892 851 2 28 2126 3400 695 1 67 1558 756 1 92 1790 812 2 17 2025 3500 712 1 81 1686 772 2 06 1923 827 2 32 2165 3600 729 1 95 1820 787 2 21 2065 3700 746 2 10 1962 803 2 37 2213 3750 754 2 18 2036 50TFQ008 71 2 TONS ALTERNATE DRIVE cont Airflow External Static Pressure in wg Airflow Cf 1...

Page 38: ...6 953 3 21 2990 3750 754 2 18 2036 811 2 46 2290 864 2 73 2548 913 3 01 2809 960 3 30 3076 50TFQ008 71 2 TONS HIGH STATIC MOTOR AND DRIVE cont Airflow External Static Pressure in wg Airflow Cf 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 831 1 53 1423 880 1 74 1627 927 1 97 1840 971 2 21 2061 1013 2 46 2289 2300 836 1 57 1465 885 1 79 1671 931 ...

Page 39: ... 00 1866 876 2 22 2067 4300 741 1 67 1559 794 1 89 1767 843 2 12 1973 889 2 34 2179 4400 755 1 78 1660 807 2 01 1873 856 2 23 2084 4500 770 1 89 1766 821 2 13 1984 869 2 36 2200 4600 785 2 01 1876 835 2 25 2099 4700 800 2 14 1991 849 2 38 2219 4800 815 2 26 2111 4900 829 2 40 2235 5000 50TFQ012 10 TONS STANDARD MOTOR AND DRIVE cont Airflow External Static Pressure in wg Airflow Cf 1 2 1 4 1 6 1 8 ...

Page 40: ...415 956 2 82 2630 4600 785 2 01 1876 835 2 25 2099 882 2 49 2320 926 2 72 2541 4700 800 2 14 1991 849 2 38 2219 895 2 62 2445 939 2 86 2670 4800 815 2 26 2111 863 2 51 2344 909 2 76 2575 4900 829 2 40 2235 877 2 65 2473 5000 844 2 54 2365 891 2 80 2608 50TFQ012 10 TONS ALTERNATE MOTOR AND DRIVE cont Airflow External Static Pressure in wg Airflow Cf 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Wat...

Page 41: ...w External Static Pressure in wg Airflow Cf 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 836 1 42 1322 881 1 57 1467 923 1 73 1613 963 1 89 1761 1001 2 05 1909 3100 846 1 50 1398 890 1 66 1547 932 1 82 1698 972 1 98 1849 1010 2 15 2002 3200 856 1 58 1477 899 1 75 1631 941 1 92 1786 980 2 08 1942 1018 2 25 2099 3300 866 1 67 1559 909 1 84 1718 9...

Page 42: ... 80 799 1261 0 92 917 1300 1218 0 89 885 1400 1246 0 99 980 1500 LEGEND Bhp Brake Horsepower Input to Fan Watts Input Watts to Motor Motor drive range 760 to 1000 rpm All other rpms require a field supplied drive See General Fan Performance notes NOTES 1 Shaded cells indicate field supplied drive is required 2 Maximum continuous bhp is 1 00 50TFQ004 3 TONS HIGH STATIC MOTOR BELT DRIVE Airflow Exte...

Page 43: ...Pressure in wg Airflow Cfm 0 2 0 4 0 6 0 8 1 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 708 0 26 256 836 0 36 359 941 0 47 464 1033 0 57 572 1116 0 69 683 1300 743 0 31 307 868 0 42 417 971 0 53 530 1062 0 65 645 1143 0 77 764 1400 780 0 37 364 900 0 49 483 1002 0 61 603 1091 0 73 726 1172 0 86 851 1500 816 0 43 428 934 0 56 556 1033 0 69 685 1121 0 82 815 120...

Page 44: ...5 1938 1800 1362 1 45 1446 1428 1 61 1605 1490 1 78 1767 1550 1 94 1930 1606 2 11 2096 1900 1392 1 60 1587 1458 1 76 1753 1519 1 93 1922 1578 2 10 2092 1634 2 28 2265 2000 1423 1 75 1738 1488 1 92 1912 1549 2 10 2088 1607 2 28 2266 LEGEND Bhp Brake Horsepower Input to Fan Watts Input Watts to Motor Motor drive range 1075 to 1455 rpm All other rpms require a field supplied drive See General Fan Per...

Page 45: ... 30 for single phase units and 2 40 for three phase units 50TFQ006 5 TONS HIGH STATIC MOTOR BELT DRIVE Airflow External Static Pressure in wg Airflow Cfm 0 2 0 4 0 6 0 8 1 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 776 0 38 340 883 0 51 454 977 0 65 579 1061 0 80 715 1138 0 97 860 1600 813 0 45 397 916 0 58 517 1007 0 73 646 1089 0 89 786 1165 1 05 935 1700 85...

Page 46: ... DRIVE Airflow External Static Pressure in wg Airflow Cfm 0 2 0 4 0 6 0 8 1 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 888 0 60 532 984 0 75 662 1069 0 90 802 1148 1 07 951 1221 1 25 1109 1900 927 0 69 610 1019 0 84 747 1102 1 00 892 1179 1 18 1046 1250 1 36 1208 2000 965 0 78 697 1054 0 94 839 1135 1 11 990 1210 1 29 1149 1280 1 48 1316 2100 1004 0 89 792 109...

Page 47: ... 738 1 77 1649 797 2 02 1885 851 2 28 2125 3400 608 1 36 1271 683 1 63 1517 749 1 89 1759 807 2 15 2002 3500 622 1 47 1372 695 1 74 1625 760 2 01 1874 818 2 28 2124 3600 635 1 58 1477 707 1 86 1738 771 2 14 1995 3700 648 1 70 1588 720 1 99 1857 783 2 27 2121 3750 655 1 77 1646 726 2 06 1918 788 2 34 2187 50TFQ008 71 2 TONS STANDARD MOTOR AND DRIVE cont Airflow External Static Pressure in wg Airflo...

Page 48: ... 671 1 52 1414 738 1 77 1649 797 2 02 1885 851 2 28 2125 3400 608 1 36 1271 683 1 63 1517 749 1 89 1759 807 2 15 2002 3500 622 1 47 1372 695 1 74 1625 760 2 01 1874 818 2 28 2124 3600 635 1 58 1477 707 1 86 1738 771 2 14 1995 3700 648 1 70 1588 720 1 99 1857 783 2 27 2121 3750 655 1 77 1646 726 2 06 1918 788 2 34 2187 50TFQ008 71 2 TONS ALTERNATE DRIVE cont Airflow External Static Pressure in wg A...

Page 49: ... 2 63 2454 897 2 92 2722 50TFQ008 71 2 TONS HIGH STATIC MOTOR AND DRIVE cont Airflow External Static Pressure in wg Airflow Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 806 1 42 1326 855 1 63 1521 902 1 85 1723 946 2 07 1932 988 2 30 2148 2300 810 1 46 1363 859 1 67 1561 906 1 89 1765 950 2 12 1976 991 2 35 2194 2400 818 1 55 1443 868 1 76 ...

Page 50: ...4 2 12 1979 890 2 34 2184 4400 710 1 59 1482 760 1 80 1677 808 2 01 1876 855 2 23 2081 4500 723 1 69 1577 773 1 90 1775 820 2 12 1978 866 2 35 2187 4600 737 1 80 1675 785 2 01 1877 832 2 24 2085 4700 751 1 91 1778 798 2 13 1984 844 2 35 2195 4800 765 2 02 1885 812 2 25 2095 4900 779 2 14 1996 825 2 37 2210 5000 793 2 26 2112 50TFQ012 10 TONS STANDARD MOTOR AND DRIVE cont Airflow External Static Pr...

Page 51: ...70 2514 4700 751 1 91 1778 798 2 13 1984 844 2 35 2195 889 2 59 2412 932 2 82 2633 4800 765 2 02 1885 812 2 25 2095 856 2 48 2310 900 2 71 2531 4900 779 2 14 1996 825 2 37 2210 869 2 61 2430 912 2 85 2654 5000 793 2 26 2112 838 2 50 2330 881 2 74 2554 50TFQ012 10 TONS ALTERNATE MOTOR AND DRIVE cont Airflow External Static Pressure in wg Airflow Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Wat...

Page 52: ...IVE cont Airflow External Static Pressure in wg Airflow Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 830 1 39 1298 883 1 57 1466 934 1 76 1638 982 1 95 1815 1029 2 14 1996 3100 837 1 46 1363 889 1 65 1534 938 1 83 1710 986 2 03 1891 1033 2 23 2075 3200 843 1 53 1431 894 1 72 1606 944 1 91 1785 991 2 11 1969 1037 2 31 2157 3300 850 1 61 1502...

Page 53: ...80 1345 1305 1265 1225 1185 1150 1110 1070 007 1685 1647 1608 1570 1531 1493 1454 1416 1377 1339 1300 008 840 815 790 765 740 715 690 665 635 615 590 008 935 910 885 860 835 810 785 760 735 710 685 008 1080 1025 1007 988 970 952 933 915 897 878 860 009 935 910 885 860 835 810 785 760 735 710 685 009 1080 1025 1007 988 970 952 933 915 897 878 860 012 935 910 885 860 835 810 785 760 735 710 685 012 ...

Page 54: ...6 5 7 9 9 6 10 5 12 0 14 7 16 0 15 8 19 3 21 0 19 9 24 3 26 5 002 004 005 004 004 004 005 002 003 003 460 480 3 phase 5 5 6 0 10 6 11 5 12 9 14 0 21 1 23 0 23 4 25 5 006 008 009 008 008 008 009 007 208 230 240 3 phase 4 9 6 0 6 5 7 9 9 6 10 5 12 0 14 7 16 0 15 8 19 3 21 0 19 9 24 3 26 5 002 004 005 004 004 004 006 002 002 003 003 007 460 480 3 phase 5 5 6 0 10 6 11 5 12 9 14 0 21 1 23 0 23 4 25 5 ...

Page 55: ...d 017 010 and 012 012 012 015 017 017 012 460 480 3 phase 15 2 16 5 25 6 27 8 30 4 33 0 38 4 41 7 45 9 50 0 013 014 015 014 and 016 013 and 015 011 014 014 016 016 575 3 phase 17 0 34 0 51 0 018 019 018 and 019 011 014 016 Two heater packages required to provide kW indicated Use CRSINGLE004A00 for units with convenience outlet NOTES 1 The rated heater voltage is 240 480 and 575 v If power distribu...

Page 56: ... 007 Standard 575 2 40 2120 3 0 84 007 208 230 8 6 84 High Static 460 2 90 2562 3 9 High Static 575 2 90 2562 3 9 208 230 6 0 Standard Alternate 460 2 40 2120 3 0 008 Standard Alternate 575 2 40 2120 3 0 80 008 208 230 11 7 80 High Static 460 3 70 3313 5 5 High Static 575 3 70 3313 5 5 208 230 6 0 Standard 460 2 40 2120 3 0 Standard 575 2 40 2120 3 0 208 230 8 6 012 Alternate 460 2 90 2615 3 9 80 ...

Page 57: ... 55 STD 414 508 4 8 40 0 0 8 1 7 11 5 13 8 25 4 30 24 59 14 0 16 8 29 1 30 27 62 8 9 15 9 48 6 0 7 2 17 9 20 17 55 460 3 60 ALT 414 508 4 8 40 0 0 8 2 1 8 8 10 6 22 2 25 21 59 460 3 60 ALT 414 508 4 8 40 0 0 8 2 1 11 5 13 8 26 2 30 25 62 14 0 16 8 29 9 30 28 65 9 4 15 9 62 6 0 7 2 18 4 20 18 70 HIGH STATIC 414 508 4 8 40 0 0 8 2 6 8 8 10 6 22 7 25 22 73 HIGH STATIC 414 508 4 8 40 0 0 8 2 6 11 5 13...

Page 58: ...26 7 26 7 30 30 26 26 138 138 4 9 6 5 13 6 15 6 43 7 46 2 45 50 42 44 152 154 STD 187 254 15 4 124 0 1 5 5 9 7 9 10 5 21 9 25 3 54 0 58 3 60 60 51 55 160 163 STD 187 254 15 4 124 0 1 5 5 9 12 0 16 0 33 3 38 5 68 3 74 8 70 80 65 70 171 177 15 8 21 0 43 9 50 5 81 5 89 8 90 90 77 84 182 189 19 9 26 5 55 2 63 8 95 7 106 4 100 110 90 100 193 202 26 6 26 6 30 30 26 26 169 169 4 9 6 5 13 6 15 6 43 6 46 1...

Page 59: ...and 480 v If power distribution voltage to unit varies from rated heater voltage heater kW will vary accordingly Fuse or HACR circuit breaker Optional disconnect switch is unavailable NOTES 1 In compliance with NEC requirements for multimotor and combination load equipment refer to NEC Articles 430 and 440 the overcurrent pro tective device for the unit shall be fuse or HACR breaker 2 Unbalanced 3...

Page 60: ...6 0 33 3 38 5 85 2 91 7 90 100 85 91 306 311 HIGH STATIC 187 254 13 4 91 0 1 4 10 6 18 6 24 8 51 6 59 7 108 1 118 2 110 125 106 115 324 332 24 0 32 0 66 6 77 0 126 8 139 8 150 150 123 135 339 350 31 8 42 4 88 3 102 0 153 9 171 1 175 175 148 164 361 375 008 19 1 20 20 108 008 13 9 16 7 40 0 40 39 124 008 71 T STD 414 508 6 7 42 0 0 7 2 6 16 5 19 8 43 8 45 43 128 71 2 Tons STD 414 508 6 7 42 0 0 7 2...

Page 61: ...6 100 110 98 104 395 401 HIGH STATIC 187 254 17 2 124 0 1 4 15 0 24 0 32 0 66 6 77 0 139 8 152 8 150 175 137 149 429 439 31 8 42 4 88 3 102 0 166 9 184 0 175 200 162 177 450 464 37 6 50 0 104 4 120 3 187 0 176 8 200 200 180 198 466 482 23 4 25 24 143 16 5 19 8 48 1 50 47 163 STD 414 508 8 6 59 6 0 7 2 6 27 8 33 4 65 1 70 63 176 STD 414 508 8 6 59 6 0 7 2 6 33 0 39 7 73 0 80 70 183 012 41 7 50 2 86...

Page 62: ...8 4 8 40 0 0 8 1 7 11 5 13 8 27 5 30 26 61 14 0 16 8 31 3 35 30 64 11 1 15 11 50 6 0 7 2 20 1 25 20 57 460 3 60 ALT 414 508 4 8 40 0 0 8 2 1 8 8 10 6 24 3 25 24 61 460 3 60 ALT 414 508 4 8 40 0 0 8 2 1 11 5 13 8 28 3 30 27 64 14 0 16 8 32 1 35 31 67 11 6 15 12 65 6 0 7 2 20 6 25 20 72 HIGH STATIC 414 508 4 8 40 0 0 8 2 6 8 8 10 6 24 8 25 24 75 HIGH STATIC 414 508 4 8 40 0 0 8 2 6 11 5 13 8 28 8 30...

Page 63: ...298 309 31 5 31 5 35 40 32 32 143 143 4 9 6 5 13 6 15 6 48 5 51 0 50 60 47 50 157 159 STD 187 254 15 4 124 0 1 5 5 9 7 9 10 5 21 9 25 3 58 8 63 1 60 70 57 61 165 168 STD 187 254 15 4 124 0 1 5 5 9 12 0 16 0 33 3 38 5 73 1 79 6 80 90 70 76 176 181 15 8 21 0 43 9 50 5 86 3 94 6 90 100 82 90 187 193 19 9 26 5 55 2 63 8 100 5 111 2 110 125 95 105 198 207 31 4 31 4 35 35 32 32 174 174 4 9 6 5 13 6 15 6...

Page 64: ...ltage to unit varies from rated heater voltage heater kW will vary accordingly Fuse or HACR circuit breaker Optional disconnect switch is unavailable NOTES 1 In compliance with NEC requirements for multimotor and combination load equipment refer to NEC Articles 430 and 440 the overcurrent pro tective device for the unit shall be fuse or HACR breaker 2 Unbalanced 3 Phase Supply Voltage Never operat...

Page 65: ...414 508 6 7 42 0 0 7 4 8 27 8 33 4 65 2 70 63 165 33 0 39 7 73 1 80 71 171 41 7 50 2 86 2 90 83 182 17 1 20 18 99 STD 518 632 5 4 39 0 0 7 2 6 17 0 17 1 38 5 40 38 116 575 3 60 STD 518 632 5 4 39 0 0 7 2 6 34 0 34 1 59 7 60 57 133 575 3 60 18 9 20 20 116 HIGH STATIC 518 632 5 4 39 0 0 7 4 8 17 0 17 1 40 2 45 40 133 HIGH STATIC 518 632 5 4 39 0 0 7 4 8 34 0 34 1 61 5 70 59 150 52 1 52 1 60 60 55 55...

Page 66: ...n voltage to unit varies from rated heater voltage heater kW will vary accordingly Fuse or HACR circuit breaker Optional disconnect switch is unavailable NOTES 1 In compliance with NEC requirements for multimotor and combination load equipment refer to NEC Articles 430 and 440 the overcurrent pro tective device for the unit shall be fuse or HACR breaker 2 Unbalanced 3 Phase Supply Voltage Never op...

Page 67: ...erload LPS Low Pressure Switch LSM Limit Switch Manual Reset OARH Outdoor Air Relative Humidity Sensor OAT Outdoor Air Thermostat OFC Outdoor Fan Contactor OFM Outdoor Fan Motor P Plug PL Plug Assembly POT Potentiometer QT Quadruple Terminal RAT Return Air Temperature Sensor RSV Reversing Valve SAT Supply Air Thermostat SEN Sensor TRAN Transformer Field Splice Marked Wire Terminal Marked Terminal ...

Page 68: ...68 TYPICAL PIPING 50TFQ VERTICAL D ISCH ARGE D UCTING HORIZONTAL D ISCH ARGE D UCTING LEGEND NEC National Electrical Code C06080 50TFQ ...

Page 69: ... Unit shall have a factory installed sloped condensate drain pan made of a non corrosive material providing a minimum 3 4 in connection with both vertical and horizontal drains and shall comply with ASHRAE 62 f Unit shall have factory installed filter access panel to provide filter access with toolless removal g Unit shall have standard thru the bottom power connection capability 3 Fans a Indoor b...

Page 70: ...e is low enough to indicate a heavy frost condition Defrost cycle shall terminate when defrost thermostat is satisfied and shall have a positive termination time of 10 minutes 3 Unit shall contain high pressure loss of charge low pressure and freeze protection switches It shall mounton factory installedSchrader fittings b Standard Safeties Unit shall incorporate compressor overtemperature and over...

Page 71: ...rms and rods 18 Control LEDs When the outdoor air damper is capable of providing free cooling the Free Cool LED shall illuminate The IAQ LED indicates when the module is on the DCV mode The EXH LED indicates when the exhaust fan contact is closed 19 Remote Minimum Position Control A field installed accessory remote potentiometer shall allow the outdoor air damper to be opened or closed beyondthemi...

Page 72: ...ll mount and wall mount with LED display The set point shall have adjustment capability 3 Requires EconoMi er2 PremierLink control options t Outdoor Coil Hail Guard Assembly Hail guard shall protect against damage from hail and flying debris u Indoor Air Quality CO2 Room Sensor EconoMi er IV Sensor shall have the ability to provide demand ventilation control through the EconoMi er IV The IAQ senso...

Page 73: ...otor Pulley Pitch Diameter Min Max in High Static 2 8 3 8 2 8 3 8 3 4 4 4 3 4 4 4 Nominal Motor Shaft Diameter in Std 1 2 1 2 5 8 5 8 Nominal Motor Shaft Diameter in High Static 5 8 5 8 5 8 5 8 Fan Pulley Pitch Diameter in Std 4 5 4 0 4 5 3 7 Fan Pulley Pitch Diameter in High Static 4 5 4 5 4 5 4 5 Belt Quantity Type Length in Std 1 A 34 1 A 34 1 A 39 1 A 40 Belt Quantity Type Length in High Stati...

Page 74: ...1080 High Static 860 1080 860 1080 922 1219 Motor Bearing Type Ball Ball Ball Maximum Allowable Rpm 2100 2100 2100 Motor Pulley Pitch Diameter Min Max in Standard 3 4 4 4 3 4 4 4 4 0 5 0 High Static 4 0 5 0 4 0 5 0 3 1 4 1 Nominal Motor Shaft Diameter in Standard 7 8 7 8 7 8 High Static 7 8 7 8 7 8 Fan Pulley Pitch Diameter in Standard 8 0 7 0 8 0 High Static 8 0 8 0 5 8 Belt Quantity Type Length ...

Page 75: ...6000 Maximum Continuous Bhp 4 25 3 45 5 90 Fan Rpm Range STD 891 1179 1159 1429 817 1038 ALT 1227 1559 1082 1303 Motor Nominal Rpm 1725 1550 1745 Maximum Allowable Rpm 1550 1550 Motor Pulley Pitch Diameter in STD 3 1 4 1 4 3 5 3 3 7 4 7 ALT 3 7 4 7 4 9 5 9 Fan Pulley Pitch Diameter in STD 6 0 6 4 7 9 ALT 5 2 7 9 Belt Quantity Type Length in STD 1 BX 42 1 BX 45 1 BX 46 ALT 1 BX 42 1 BX 50 Pulley Ce...

Page 76: ...76 BASE UNIT DIMENSIONS 50HJQ004 007 C06006 50HJQ ...

Page 77: ...77 BASE UNIT DIMENSIONS 50HJQ008 012 C06081 50HJQ ...

Page 78: ...Left side 4 0 1219 for proper outdoor coil airflow c Front 4 0 1219 for control box access d Right side 4 0 1219 for proper operation of damper and power exhaust if so equipped e Top 6 0 1829 to assure proper outdoor fan operation f Local codes or jurisdiction may prevail 6 With the exception of clearance for the outdoor coil and the damper and power exhaust as stated in note no 5 a remov able fen...

Page 79: ...airflow 8 Connector packages CRBTMPWR001A01 and 002A01 are for thru the curb type gas Packages CRBTMPWR003A01 and 004A01 are for thru the bottom type gas connections CONNECTOR PKG ACCY B C D ALT DRAIN HOLE GAS POWER CONTROL ACCESSORY POWER CRBTMPWR001A01 1 911 16 551 1 4 406 13 4 44 5 3 4 19 NPT 3 4 19 NPT 1 2 12 7 NPT 1 2 12 7 NPT CRBTMPWR002A01 11 4 31 7 CRBTMPWR003A01 1 2 12 7 NPT 3 4 19 NPT CR...

Page 80: ...yurethane foam 13 4 lb density 3 Dimensions in are in millimeters 4 Roof curb 16 gage steel 5 Attach ductwork to curb flanges of duct rest on curb 6 Service clearance 4 ft on each side 7 Direction of airflow 8 Connector packages CRBTMPWR001A01 and 2A01 are for thru the curb gas type Packages CRBTMPWR003A01 and 4A01 are for the thru the bottom type gas connections ROOF CURB ACCESSORY A UNIT SIZE CR...

Page 81: ...s shipped disassembled 2 Insulated panels 1 thick neoprene coated 1 1 2 lb density 3 Dimensions in are in millimeters 4 Direction of airflow 5 Roof curb 16 ga VA03 56 stl 6 A 90 degree elbow must be installed on the supply ductwork below the unit discharge for units equipped with electric heaters 7 To prevent the hazard of stagnant water build up in the drain pan of the indoor section unit can onl...

Page 82: ...l adapter For Horizontal return applications The power exhaust and barometric relief dampers must be installed in the return air duct 23 14 3 4 6 3 1 2 FULLY INSULATED SUPPLY PLENUM 1 INSULATION 1 1 2 DENSITY STICK PINNED GLUED 2 X 1 4 SUPPORT TYP STITCH WELDED 12 WIDE STANDING SEAM PANELS ACCESSORY PACKAGE NO CURB HEIGHT DESCRIPTION CRRFCURB013A00 1 11 584 Pre Assembled Horizontal Adapter Roof Cu...

Page 83: ...83 NON FUSED D ISCO NNECT 50 HJQ014 016 C06088 2 1 5 8 2 2 1 16 1 6 5 16 POWER EXHAUST 50H JQ014 01 6 C06089 50HJQ ...

Page 84: ...en made No correction is required The required heating capacity is 35 000 Btuh Therefore 12 600 Btuh 35 000 22 400 additional electric heat is required Determine additional electric heat capacity in kW 12 600 Btuh 3 7 kW f h t i d 3413 Btuh kW 3 7 kW of heat required Enter the Electric Heating Capacities table for 50HJQ005 at 208 230 3 phase The 6 5 kW heater at 240v most closely satisfies the hea...

Page 85: ... 8 29 1 32 9 22 4 33 0 36 1 25 1 36 9 39 3 125 kW 4 72 4 70 4 62 4 73 4 71 4 66 4 74 4 72 4 71 50HJQ006 5 Tons Temp F Indoor Entering Air Cfm BF Temp F Outdoor 1500 0 17 1750 0 25 2000 0 31 2500 0 42 Outdoor Entering Air Edb Indoor Entering Air Ewb F Entering Air Edb 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 TC 70 2 65 3 59 9 56 6 71 7 66 8 61 9 59 7 72 8 67 8 63 4 62 4 74 1 69 9 65 8 65 8 7...

Page 86: ...0 7 41 7 30 7 50 7 43 7 35 TC 91 7 82 2 70 7 94 8 87 3 76 6 97 0 90 1 83 4 105 SHC 46 3 57 4 65 9 50 9 66 3 76 4 54 8 74 1 83 4 105 kW 8 37 8 22 8 04 8 39 8 33 8 15 8 44 8 35 8 26 TC 87 7 77 4 66 9 91 7 81 6 72 5 93 9 85 3 78 8 115 SHC 44 9 55 4 64 0 50 3 64 2 72 5 55 0 72 5 78 6 115 kW 9 33 9 16 8 98 9 44 9 27 9 11 9 48 9 33 9 22 TC 83 6 73 3 66 7 87 1 76 0 69 1 89 5 79 0 74 4 125 SHC 43 6 53 9 6...

Page 87: ...1 00 10 80 11 30 11 10 10 80 TC 155 0 141 0 127 0 157 0 144 0 131 0 160 0 146 0 133 0 161 0 149 0 137 0 163 0 149 0 140 0 95 SHC 76 1 96 3 115 0 80 3 105 0 126 0 84 4 110 0 132 0 86 5 117 0 137 0 91 7 121 0 140 0 95 kW 12 20 11 80 11 40 12 20 11 90 11 50 12 40 12 00 11 60 12 40 12 10 11 80 12 50 12 10 11 90 TC 147 0 133 0 120 0 150 0 137 0 124 0 152 0 138 0 127 0 153 0 140 0 131 0 154 0 141 0 134 ...

Page 88: ... sensible capacity Btuh tldb tedb 1 10 x cfm tlwb Wet bulb temperature corresponding to enthalpy of air leaving indoor coil hlwb total capacity Btuh hlwb hewb 4 5 x cfm Where hewb Enthalpy of air entering indoor coil 3 The Shc is based on 80_F edb termperature of air entering indoor coil Below 80_F edb subtract corr factor x cfm from SHC Above 80_F edb add corr factor x cfm to SHC BYPASS ENTERING ...

Page 89: ...16 0 14 7 20 9 19 2 26 0 22 1 35 8 32 7 35 8 32 7 44 6 39 1 51 3 51 3 56 4 56 4 62 9 62 9 63 0 63 0 55 1750 kW 3 19 3 28 3 36 3 52 3 52 3 67 3 80 3 90 4 04 4 04 55 2000 Cap 16 9 15 6 21 9 20 2 27 0 23 0 36 9 33 7 36 9 33 7 45 6 40 1 52 3 52 3 56 7 56 7 62 8 62 8 62 6 62 6 2000 kW 3 41 3 49 3 56 3 69 3 69 3 83 3 93 4 01 4 12 4 11 2500 Cap 18 9 17 6 23 9 22 1 29 1 25 0 38 9 35 7 38 9 35 7 47 8 42 1 ...

Page 90: ...93 6 23 6 57 6 54 3000 Cap 15 4 14 1 18 8 17 3 24 1 20 5 32 2 29 6 39 6 36 3 50 4 44 2 61 6 61 6 68 9 68 9 74 3 74 3 74 5 74 5 3000 kW 4 54 4 74 4 91 5 14 5 29 5 64 5 95 6 17 6 37 6 36 50HJQ008 71 2 Tons Return Air Cfm Standard Temperature Air Entering Outdoor Coil F db at 70 rh Air F db Standard Air 20 10 0 10 17 30 40 47 50 60 2250 Cap 31 4 28 8 37 8 34 9 44 5 41 0 52 1 47 8 57 6 52 5 70 2 61 5 ...

Page 91: ... Air F db Standard Air 20 10 0 10 17 30 40 47 50 60 3000 Cap 37 7 34 6 45 5 41 9 53 5 49 2 62 6 57 5 69 2 63 1 84 3 74 0 101 3 101 3 111 3 111 3 116 0 116 0 134 2 134 2 3000 kW 6 87 7 07 7 25 7 43 7 55 7 88 8 26 8 52 8 64 9 20 55 4000 Cap 40 0 36 7 47 6 43 8 55 6 51 1 64 8 59 4 71 6 65 2 86 7 75 8 103 7 103 7 114 0 114 0 118 9 118 9 133 2 133 2 55 4000 kW 7 45 7 63 7 78 7 93 8 05 8 33 8 67 8 92 9 ...

Page 92: ... 110 0 12 96 150 2 14 00 178 2 14 72 189 4 15 08 228 0 16 32 3750 70 39 6 10 04 54 4 10 96 69 8 11 86 80 4 12 48 85 8 12 78 103 4 13 82 141 6 15 02 168 4 15 84 179 0 16 26 214 0 17 64 3750 80 35 0 10 20 50 2 11 20 65 8 12 20 76 8 12 90 81 8 13 24 99 2 14 38 136 0 15 70 161 8 16 60 172 0 17 04 206 0 18 52 55 47 8 10 02 62 0 10 78 77 0 11 48 87 6 11 96 93 2 12 20 112 0 12 98 153 2 13 92 182 2 14 58 ...

Page 93: ...inuous bhp is 1 20 50HJQ004 3 TONS HIGH STATIC MOTOR BELT DRIVE Airflow External Static Pressure in wg Airflow Cfm 0 2 0 4 0 6 0 8 1 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 566 0 14 142 690 0 23 228 791 0 32 320 879 0 42 418 957 0 52 522 1000 598 0 17 173 718 0 27 267 817 0 37 366 903 0 47 471 981 0 58 581 1100 632 0 21 210 748 0 31 311 844 0 42 418 929 0 53...

Page 94: ...p Watts 1200 666 0 25 252 778 0 36 361 873 0 48 476 956 0 60 594 1031 0 72 718 1300 701 0 30 300 809 0 42 418 902 0 54 540 983 0 67 665 1057 0 80 796 1400 737 0 36 355 842 0 48 481 932 0 61 610 1012 0 75 744 1085 0 89 881 1500 774 0 42 417 875 0 55 551 962 0 69 689 1041 0 83 830 1112 0 98 974 1600 811 0 49 487 909 0 63 629 994 0 78 774 1071 0 93 923 1141 1 08 1076 1700 849 0 57 565 943 0 72 715 10...

Page 95: ... 412 931 0 60 536 1022 0 75 670 1104 0 92 813 1180 1 09 966 1700 866 0 54 478 966 0 68 608 1054 0 84 747 1134 1 01 895 1208 1 19 1053 1800 905 0 62 551 1001 0 77 687 1087 0 94 832 1165 1 11 985 1238 1 29 1148 1900 944 0 71 633 1037 0 87 774 1120 1 04 925 1197 1 22 1084 1268 1 41 1251 2000 983 0 81 723 1073 0 98 870 1154 1 16 1026 1229 1 34 1190 1299 1 53 1362 2100 1023 0 92 821 1110 1 10 975 1189 ...

Page 96: ...0 1627 2 90 2574 2400 1489 2 37 2106 1547 2 60 2312 1603 2 84 2526 2500 1522 2 56 2272 1579 2 80 2484 LEGEND Bhp Brake Horsepower Input to Fan Watts Input Watts to Motor Motor drive range 1300 to 1685 rpm All other rpms require a field supplied drive See General Fan Performance notes NOTES 1 Shaded cells indicate field supplied drive is required 2 Maximum continuous bhp is 2 90 50HJQ007 6 TONS STA...

Page 97: ... 2 56 2275 1539 2 82 2501 2800 1305 1 99 1772 1381 2 26 2003 1450 2 52 2235 1514 2 78 2467 2900 1346 2 20 1951 1420 2 47 2191 1488 2 74 2431 3000 1387 2 41 2142 1459 2 69 2391 50HJQ007 6 TONS HIGH STATIC MOTOR BELT DRIVE cont Airflow External Static Pressure in wg Airflow Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1304 1 51 1337 1365 1 69...

Page 98: ...51 3400 696 1 46 1361 756 1 74 1623 812 2 03 1896 864 2 34 2181 913 2 66 2478 3500 713 1 58 1469 772 1 86 1737 827 2 16 2017 878 2 48 2308 926 2 80 2610 3600 729 1 70 1583 787 1 99 1857 841 2 30 2144 892 2 62 2441 3700 746 1 83 1703 803 2 13 1985 856 2 44 2277 906 2 77 2580 3750 755 1 89 1766 811 2 20 2051 864 2 52 2346 913 2 84 2653 50HJQ008 71 2 TONS STANDARD MOTOR BELT DRIVE cont Airflow Extern...

Page 99: ...46 913 2 84 2653 959 3 18 2969 50HJQ008 71 2 TONS HIGH STATIC MOTOR BELT DRIVE cont Airflow External Static Pressure in wg Airflow Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 832 1 71 1592 882 1 99 1855 928 2 29 2131 973 2 59 2420 1015 2 92 2720 2300 837 1 75 1630 886 2 03 1896 933 2 33 2174 977 2 64 2463 1020 2 97 2766 2400 847 1 83 1710 ...

Page 100: ...1 1 67 1559 794 1 89 1767 843 2 12 1973 889 2 34 2179 932 2 56 2384 50HJQ009 81 2 TONS STANDARD MOTOR BELT DRIVE cont Airflow External Static Pressure in wg Airflow Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2500 791 1 06 988 837 1 19 1112 881 1 33 1236 922 1 46 1362 962 1 60 1490 2600 799 1 12 1049 845 1 26 1177 889 1 40 1306 930 1 54 1436 96...

Page 101: ...t Airflow External Static Pressure in wg Airflow Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2500 791 1 06 988 837 1 19 1112 881 1 33 1236 922 1 46 1362 962 1 60 1490 2600 799 1 12 1049 845 1 26 1177 889 1 40 1306 930 1 54 1436 969 1 68 1568 2700 808 1 19 1113 854 1 34 1245 897 1 48 1378 938 1 62 1513 977 1 77 1648 2800 817 1 26 1179 863 1 41 1...

Page 102: ... 3 16 2944 1005 3 41 3178 5000 844 2 54 2365 891 2 80 2608 936 3 06 2849 978 3 31 3089 1018 3 57 3328 50HJQ012 10 TONS STANDARD MOTOR BELT DRIVE cont Airflow External Static Pressure in wg Airflow Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 836 1 42 1322 881 1 57 1467 923 1 73 1613 963 1 89 1761 1001 2 05 1909 3100 846 1 50 1398 890 1 66 1...

Page 103: ...IVE cont Airflow External Static Pressure in wg Airflow Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 836 1 42 1322 881 1 57 1467 923 1 73 1613 963 1 89 1761 1001 2 05 1909 3100 846 1 50 1398 890 1 66 1547 932 1 82 1698 972 1 98 1849 1010 2 15 2002 3200 856 1 58 1477 899 1 75 1631 941 1 92 1786 980 2 08 1942 1018 2 25 2099 3300 866 1 67 1559...

Page 104: ...NOTES 1 Maximum continuous bhp is 4 25 and maximum continuous watts are 3775 Do not adjust motor rpm such that motor maximum bhp and or watts is exceeded at the maximum operating cfm 2 Fan performance is identical for horizontal discharge applications us ing horizontal adapter curb CRRFCURB013A00 50HJQ014 575 V 121 2 TONS Airflow External Static Pressure in wg Airflow Cfm 0 2 0 4 0 6 0 8 1 0 Cfm R...

Page 105: ...3 3 4 1193 3422 3 8 1262 3810 4 3 6300 1135 3286 3 7 1204 3660 4 1 1271 4052 4 5 6600 1151 3549 4 0 1218 3928 4 4 1283 4325 4 8 6900 1167 3821 4 3 1232 4207 4 7 1295 4608 5 2 7200 1183 4113 4 6 1246 4505 5 0 7500 1202 4437 5 0 1264 4837 5 4 LEGEND BHP Brake Horsepower Input to Fan FIOP Factory Installed Option Watts Input Watts Standard drive range is 817 to 1038 rpm Alternate drive range is 1082 ...

Page 106: ...mum continuous bhp is 1 20 50HJQ004 3 TONS HIGH STATIC MOTOR BELT DRIVE Airflow External Static Pressure in wg Airflow Cfm 0 2 0 4 0 6 0 8 1 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 900 554 0 14 134 681 0 22 222 783 0 32 316 870 0 42 416 947 0 53 523 1000 583 0 16 163 707 0 26 257 808 0 36 358 894 0 47 465 971 0 58 578 1100 612 0 20 195 735 0 30 298 834 0 41 406 ...

Page 107: ...Rpm Bhp Watts 1200 643 0 23 233 762 0 35 344 860 0 46 459 944 0 58 579 1020 0 71 705 1300 674 0 28 276 791 0 40 395 887 0 52 517 970 0 65 645 1045 0 78 777 1400 706 0 33 324 820 0 45 451 914 0 59 582 997 0 72 717 1071 0 86 857 1500 738 0 38 379 849 0 52 515 942 0 66 653 1024 0 80 796 1097 0 95 942 1600 771 0 44 440 879 0 59 584 971 0 74 731 1051 0 89 881 1124 1 04 1035 1700 804 0 51 507 910 0 66 6...

Page 108: ...28 0 74 660 1111 0 91 808 1600 757 0 39 343 866 0 51 455 962 0 65 580 1050 0 81 719 1132 0 98 870 1700 790 0 45 398 894 0 58 514 988 0 72 643 1074 0 88 784 1154 1 06 938 1800 823 0 52 458 924 0 65 579 1015 0 80 712 1099 0 96 857 1177 1 14 1013 1900 857 0 59 525 955 0 73 650 1043 0 89 787 1125 1 05 936 1201 1 23 1096 2000 892 0 67 599 986 0 82 729 1072 0 98 870 1151 1 15 1022 1226 1 33 1185 2100 92...

Page 109: ...Horsepower Input to Fan Watts Input Watts to Motor Motor drive range 1300 to 1685 rpm All other rpms require a field supplied drive See General Fan Performance notes NOTES 1 Shaded cells indicate field supplied drive is required 2 Maximum continuous bhp is 2 90 50HJQ007 6 TONS STANDARD MOTOR BELT DRIVE Airflow External Static Pressure in wg Airflow Cfm 0 2 0 4 0 6 0 8 1 0 Cfm Rpm Bhp Watts Rpm Bhp...

Page 110: ...1204 1 77 1572 1281 2 00 1779 1353 2 24 1989 1419 2 48 2202 1482 2 72 2419 3000 1240 1 94 1725 1315 2 18 1939 1385 2 43 2156 1451 2 68 2376 50HJQ007 6 TONS HIGH STATIC MOTOR BELT DRIVE cont Airflow External Static Pressure in wg Airflow Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1800 1244 1 33 1182 1308 1 51 1345 1369 1 70 1513 1427 1 90 1687 ...

Page 111: ...1 81 1685 818 2 13 1985 872 2 46 2294 3600 635 1 27 1187 708 1 59 1481 771 1 91 1781 829 2 24 2088 882 2 58 2403 3700 649 1 36 1272 720 1 69 1573 783 2 02 1881 840 2 35 2195 892 2 70 2517 3750 655 1 41 1316 726 1 74 1621 789 2 07 1932 845 2 41 2250 897 2 76 2575 50HJQ008 71 2 TONS STANDARD MOTOR BELT DRIVE cont Airflow External Static Pressure in wg Airflow Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watt...

Page 112: ...2575 50HJQ008 71 2 TONS HIGH STATIC MOTOR BELT DRIVE cont Airflow External Static Pressure in wg Airflow Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2250 806 1 60 1494 856 1 87 1747 903 2 15 2009 947 2 45 2282 988 2 75 2564 2300 811 1 64 1528 860 1 91 1784 907 2 20 2048 950 2 49 2323 992 2 80 2607 2400 819 1 71 1599 868 1 99 1859 915 2 28 2129 ...

Page 113: ...1 1777 844 2 12 1979 890 2 34 2184 50HJQ009 81 2 TONS STANDARD MOTOR BELT DRIVE cont Airflow External Static Pressure in wg Airflow Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2500 804 1 09 1013 861 1 25 1164 915 1 41 1319 967 1 59 1479 1017 1 76 1642 2600 809 1 14 1065 864 1 31 1219 918 1 48 1378 969 1 65 1541 1018 1 83 1708 2700 813 1 20 1119...

Page 114: ... DRIVE cont Airflow External Static Pressure in wg Airflow Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2500 804 1 09 1013 861 1 25 1164 915 1 41 1319 967 1 59 1479 1017 1 76 1642 2600 809 1 14 1065 864 1 31 1219 918 1 48 1378 969 1 65 1541 1018 1 83 1708 2700 813 1 20 1119 869 1 37 1277 921 1 54 1439 972 1 72 1606 1021 1 90 1776 2800 819 1 26 1...

Page 115: ... 50 2330 881 2 74 2554 923 2 98 2782 965 3 23 3014 50HJQ012 10 TONS STANDARD MOTOR BELT DRIVE cont Airflow External Static Pressure in wg Airflow Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 830 1 39 1298 883 1 57 1466 934 1 76 1638 982 1 95 1815 1029 2 14 1996 3100 837 1 46 1363 889 1 65 1534 938 1 83 1710 986 2 03 1891 1033 2 23 2075 3200...

Page 116: ...1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3000 830 1 39 1298 883 1 57 1466 934 1 76 1638 982 1 95 1815 1029 2 14 1996 3100 837 1 46 1363 889 1 65 1534 938 1 83 1710 986 2 03 1891 1033 2 23 2075 3200 843 1 53 1431 894 1 72 1606 944 1 91 1785 991 2 11 1969 1037 2 31 2157 3300 850 1 61 1502 901 1 80 1680 949 2 00 1863 996 2 20 2051 1041 2 40 2242 34...

Page 117: ... 1454 1416 1377 1339 1300 008 950 930 905 885 865 840 820 795 775 750 730 008 1080 1060 1035 1015 990 970 950 925 905 880 860 009 1085 1061 1036 1012 987 963 938 914 889 865 840 009 1080 1058 1036 1014 992 970 948 926 904 882 860 012 1080 1060 1035 1015 990 970 950 925 905 880 860 012 1219 1195 1170 1145 1120 1095 1071 1046 1021 996 972 947 922 014 208 230 V and 460 V 1179 1150 1121 1093 1064 1035...

Page 118: ...3 9 81 7 208 230 3 60 15 8 87 5 016 460 3 60 5 90 5180 7 9 87 5 016 575 3 60 5 90 5180 6 0 87 5 INDOOR FAN MOTOR PERFORMANCE HIGH STATIC MOTORS UNIT 50HJQ UNIT VOLTAGE MAXIMUM CONTINUOUS BHP MAXIMUM OPERATING WATTS MAXIMUM AMP DRAW MOTOR EFFICIENCY 004 208 230 3 60 2 40 2120 6 0 75 004 460 3 60 2 40 2120 3 0 75 005 208 230 3 60 2 40 2120 6 0 75 005 460 3 60 2 40 2120 3 0 75 006 208 230 3 60 2 90 2...

Page 119: ... 14 0 21 1 23 0 23 4 25 5 006 008 009 008 008 008 009 007 208 230 240 3 phase 4 9 6 0 6 5 7 9 9 6 10 5 12 0 14 7 16 0 15 8 19 3 21 0 19 9 24 3 26 5 002 004 005 004 004 004 006 002 002 003 003 007 6 tons 460 480 3 phase 5 5 6 0 10 6 11 5 12 9 14 0 21 1 23 0 23 4 25 5 006 008 009 008 008 008 009 Two heater packages required to provide kW indicated NOTES 1 The rated heater voltage is 240 and 480 v If...

Page 120: ... 016 46 0 50 0 115 113 016 Two heater packages required to provide kW indicated NOTES 1 The rated heater voltage is 240 and 480 v If power distribution voltage varies from rated heater voltage heater kW will vary accordingly 2 To determine heater kW at voltages other than those shown in table use the following formula Heater kWnew Heater kW rated x unit power distribution voltage rated heater volt...

Page 121: ...5 146 17 102 LEGEND Cap Btuh x 1000 EDB Entering Dry Bulb Temperature F EGT Entering Glycol Temperature F Gpm Gallons per Minute Ldb Leaving Dry Bulb Temperature F This accessory glycol coil is intended for use with a MINIMUM of 25 glycol solution It IS NOT intended for use solely with water due to freeze up conditions and the resulting water damage to the conditioned space NOTE Fluid t 20 F GLYCO...

Page 122: ...60 187 254 12 4 88 0 0 7 4 9 12 0 16 0 33 3 38 5 62 7 69 2 70 70 59 65 135 140 15 8 21 0 43 9 50 5 76 0 84 2 80 90 71 79 145 152 10 6 15 10 51 6 0 7 2 19 6 20 19 58 460 3 60 414 508 6 4 44 0 0 4 2 2 11 5 13 8 27 9 30 26 65 460 3 60 414 508 6 4 44 0 0 4 2 2 14 0 16 8 31 6 35 30 68 23 0 27 7 45 2 50 42 79 40 4 40 4 45 45 39 39 188 188 4 9 6 5 23 6 27 1 69 9 74 2 70 80 66 70 211 215 208 230 1 60 187 ...

Page 123: ...ps Heater capacity kW is based on heater voltage of 208 v 240 v and 480 v If power distribution voltage to unit varies from rated heater voltage heat er kW will vary accordingly Heaters are field installed only Fuse or HACR circuit breaker Electrical disconnect cannot be used if electric heater is installed NOTES 1 In compliance with NEC requirements for multimotor and combination load equipment r...

Page 124: ...4 Tons 208 230 3 60 187 254 12 4 88 0 0 7 4 9 12 0 16 0 33 3 38 5 67 5 74 0 70 80 65 71 139 145 15 8 21 0 43 9 50 5 80 8 89 0 90 90 77 84 150 157 12 8 15 13 53 6 0 7 2 21 8 25 21 60 460 3 60 414 508 6 4 44 0 0 4 2 2 11 5 13 8 30 0 35 29 67 460 3 60 414 508 6 4 44 0 0 4 2 2 14 0 16 8 33 8 35 32 70 23 0 27 7 47 4 50 45 81 45 2 45 2 50 50 45 45 193 193 4 9 6 5 23 6 27 1 74 7 79 0 80 80 72 76 216 220 ...

Page 125: ...Amps Heater capacity kW is based on heater voltage of 208 v 240 v and 480 v If power distribution voltage to unit varies from rated heater voltage heat er kW will vary accordingly Heaters are field installed only Fuse or HACR circuit breaker Electrical disconnect cannot be used if electric heater is installed NOTES 1 In compliance with NEC requirements for multimotor and combination load equipment...

Page 126: ...0 4 2 6 11 5 13 8 28 3 30 27 79 460 3 60 414 508 6 4 44 0 0 4 2 6 14 0 16 8 32 0 35 30 82 23 0 27 7 45 6 50 43 93 30 6 30 6 35 35 30 30 187 187 4 9 6 5 13 6 15 6 47 6 50 1 50 60 46 48 200 202 208 230 3 60 187 254 17 3 123 0 1 5 7 5 7 9 10 5 21 9 25 3 58 0 62 3 60 70 55 59 209 212 208 230 3 60 187 254 17 3 123 0 1 5 7 5 12 0 16 0 33 3 38 5 72 3 78 8 80 80 69 75 220 225 006 15 8 21 0 43 9 50 5 85 5 ...

Page 127: ...Load Amps Heater capacity kW is based on heater voltage of 208 v 240 v and 480 v If power distribution voltage to unit varies from rated heater voltage heat er kW will vary accordingly Heaters are field installed only Fuse or HACR circuit breaker Electrical disconnect cannot be used if electric heater is installed NOTES 1 In compliance with NEC requirements for multimotor and combination load equi...

Page 128: ...25 22 75 460 3 60 414 508 6 4 44 0 0 4 2 6 11 5 13 8 28 9 30 28 80 460 3 60 414 508 6 4 44 0 0 4 2 6 14 0 16 8 34 2 35 33 84 23 0 27 7 47 8 50 45 95 35 4 35 4 40 40 36 36 192 192 4 9 6 5 13 6 15 6 52 4 54 9 60 60 51 54 205 207 208 230 3 60 187 254 17 3 123 0 1 5 7 5 7 9 10 5 21 9 25 3 62 8 67 1 70 70 61 65 213 217 208 230 3 60 187 254 17 3 123 0 1 5 7 5 12 0 16 0 33 3 38 5 77 1 83 6 80 90 74 80 22...

Page 129: ...ad Amps Heater capacity kW is based on heater voltage of 208 v 240 v and 480 v If power distribution voltage to unit varies from rated heater voltage heat er kW will vary accordingly Heaters are field installed only Fuse or HACR circuit breaker Electrical disconnect cannot be used if electric heater is installed NOTES 1 In compliance with NEC requirements for multimotor and combination load equipm...

Page 130: ... 37 37 75 80 50 96 84 84 110 110 89 89 72 82 26 34 174 187 175 200 101 112 499 485 208 230 187 253 28 2 160 28 2 160 3 1 7 5 15 8 158 117 135 42 56 231 219 250 225 153 173 499 485 208 230 187 253 28 2 160 28 2 160 3 1 7 5 15 8 158 89 89 110 110 94 94 4 6 18 8 72 82 26 34 179 191 200 200 106 118 518 504 4 6 18 8 117 135 42 56 235 224 250 225 158 179 518 504 42 50 44 016 39 32 91 100 54 238 016 460 ...

Page 131: ...ater Relay IFC Indoor Fan Contactor IFM Indoor Fan Motor LPS Low Pressure Loss of Charge Switch LSM Limit Switch Manual Reset OFM Outdoor Fan Motor OLR Overload Relay QT Quadruple Terminal RVS Reversing Valve Solenoid SAT Supply Air Thermostat SW1 Switch Fully Open TB Terminal Block TRAN Transformer Field Splice Terminal Marked Marked Wire Terminal Unmarked Terminal Block Splice Splice Marked Fact...

Page 132: ...132 TYPICAL WIRING SCHEMATICS 50HJQ 50HJQ016 460V SHOWN C06092 50HJQ ...

Page 133: ...and is not intended to include all details for any specific installation 2 Installation must comply with all applicable codes 3 A 90 degree elbow must be installed on the supply ductwork below the unit discharge for units equipped with electric heat NEC National Electrical Code C06096 50HJQ ...

Page 134: ...ensity flexiblefiberglass insulation neoprene coatedon the air side Aluminum foil faced fiberglass insulation shall be used in the gas heat compartment c Cabinet panels shall be easily removable for servicing d Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead rigging e Unit shall have a factory installed sloped condensate drain pan made of a non...

Page 135: ...tering system AcutrolTM device b Refrigerant filter drier c Reversing valve d Service gauge connections on suction discharge and liquid lines 8 Filter Section a Standard filter section shall consist of factory installed low velocity throwaway 2 in thick fiberglass filters of commercially available sizes b Filter face velocity shall not exceed 320 fpm at nominal airflows c Filter section should use...

Page 136: ...icroprocessor control shall provide control of internal building pressure through its accessory power exhaust function Factory set at 100 with a range of 0 to 100 11 EconoMi er2 shall be capable of control from a 4 to 20 mA signal through optional 4 to 20 mA design without microprocessor control required for PremierLink or third party control interface 12 EconoMi er IV Microprocessor Occupied Mini...

Page 137: ... 2 A supplementary supply air fan kit to provide increased air movement into the 62AQ unit 3 A field installed 460 v to 208 230 v transformer to provide power when the Energy Recycler is used with a 460 v rooftop unit s Power Exhaust Accessory for EconoMi er IV or EconoMi er2 Power exhaust shall be used in conjunction with EconoMi er IV or EconoMi er2 to provide system exhaust of up to 100 of retu...

Page 138: ...ld installed in the indoor section of the unit aimed at the indoor coil and condensate pan The short wave length ultra violet light inhibitsandkillsmold fungusandmicrobial growth The lamps have an output rating at 45 F in 400 fpm airflow of 120 microwatts cm2 at 1 meter ab Hinged Panel Option Hinged panel option provide hinged access panels for the filter compressor evaporator fan and control box ...

Page 139: ... 2 in thick 1 lb density flexible fiberglass insulation neoprene coated on the air side Aluminum foil faced fiberglass insulation shall be used in the gas heat compartment c Cabinet panels shall be easily removable for servicing d Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead rigging e Unit shall have a factory installed sloped condensate dra...

Page 140: ...chedule b Heater elements shall be openwire adequatelysupported and insulated with ceramic bushings 7 Refrigerant Components Refrigerant circuit components shall include a Fixed orifice metering system AcutrolTM device b Refrigerant filter drier c Reversing valve d Service gage connections on suction discharge and liquid lines 8 Filter Section a Standard filter section shall consist of factory ins...

Page 141: ...alenthalpycontrol shallbe provided as field installed accessories 9 The EconoMi er IV and EconoMi er2 shall have a gear driven parallel blade design 10 EconoMi er IV microprocessor control shall provide control of internal building pressure through its accessory power exhaust function Factory set at 100 with a range of 0 to 100 11 EconoMi er2 shall be capable of control from a 4 to 20 mA signal th...

Page 142: ...alpy sensor the EconoMi er IV or EconoMi er2 device will provide differential enthalpy control s Return Air Temperature Sensor EconoMi er IV or EconoMi er2 The return air temperature sensor shall be used with the EconoMi er IV or EconoMi er2 device When used in conjunction with the standard outdoor air temperature sensor the EconoMi er IV or EconoMi er2 device will provide differential temperature...

Page 143: ...ey Pitch Diameter Min Max in High Static 2 8 3 8 2 8 3 8 3 4 4 4 Nominal Motor Shaft Diameter in Std 1 2 1 2 1 2 5 8 Nominal Motor Shaft Diameter in High Static 5 8 5 8 5 8 Fan Pulley Pitch Diameter in Std 5 2 4 5 4 0 4 5 Fan Pulley Pitch Diameter in High Static 4 5 4 5 4 5 Belt Quantity Type Length in Std 1 A 36 1 A 34 1 A 34 1 A 39 Belt Quantity Type Length in High Static 1 A 39 1 A 39 1 A 40 Pu...

Page 144: ...144 BASE UNIT DIMENSIONS 50HEQ003 006 C06058 50HEQ ...

Page 145: ...airflow 8 Connector packages CRBTMPWR001A01 and 002A01 are for thru the curb type gas Packages CRBTMPWR003A01 and 004A01 are for thru the bottom type gas connections CONNECTOR PKG ACCY B C D ALT DRAIN HOLE GAS POWER CONTROL ACCESSORY POWER CRBTMPWR001A01 1 911 16 551 1 4 406 13 4 44 5 3 4 19 NPT 3 4 19 NPT 1 2 12 7 NPT 1 2 12 7 NPT CRBTMPWR002A01 11 4 31 7 CRBTMPWR003A01 1 2 12 7 NPT 3 4 19 NPT CR...

Page 146: ...kW 2 36 2 34 2 31 2 38 2 35 2 33 2 38 2 36 2 35 TC 38 6 35 0 31 7 40 4 36 7 33 4 41 3 37 6 34 8 95 SHC 18 9 23 4 27 4 20 8 26 6 31 6 22 4 29 2 34 7 95 kW 2 65 2 62 2 58 2 66 2 63 2 61 2 67 2 64 2 63 TC 37 1 33 2 30 0 38 7 35 0 31 5 39 3 36 0 33 2 105 SHC 18 3 22 7 26 6 20 3 26 1 30 7 21 7 29 0 33 2 105 kW 2 96 2 92 2 88 2 98 2 95 2 90 2 97 2 96 2 93 TC 35 1 31 4 28 0 36 7 32 8 29 7 37 7 33 8 31 6 ...

Page 147: ... 1 82 1 94 2 03 2 06 2 18 1500 Cap 11 1 10 2 14 6 13 4 17 6 16 2 21 2 19 4 24 4 22 1 28 9 25 3 33 5 33 5 36 5 36 5 37 7 37 7 41 2 41 2 1500 kW 1 43 1 49 1 54 1 60 1 66 1 74 1 83 1 90 1 92 2 00 900 Cap 8 67 7 97 11 9 10 9 15 1 13 9 18 6 17 1 22 2 20 2 26 4 23 1 30 5 30 5 33 6 33 6 34 7 34 7 39 0 39 0 900 kW 1 69 1 83 1 95 2 08 2 21 2 38 2 54 2 67 2 72 2 92 70 1200 Cap 9 15 8 42 12 4 11 4 15 7 14 5 ...

Page 148: ...Cap 13 9 12 9 19 4 17 9 24 9 21 3 34 9 31 8 34 9 31 8 43 5 38 2 50 6 50 6 56 2 56 2 63 0 63 0 63 2 63 2 2000 kW 3 73 3 87 3 98 4 15 4 15 4 32 4 47 4 58 4 73 4 73 2500 Cap 16 0 14 9 21 5 19 9 27 0 23 3 37 1 34 0 37 1 34 0 45 8 40 4 52 9 52 9 57 7 57 7 63 3 63 3 63 1 63 1 2500 kW 4 24 4 37 4 46 4 60 4 60 4 74 4 85 4 92 5 03 5 01 1500 Cap 9 93 9 14 15 7 14 5 21 5 18 2 31 6 28 8 31 6 28 8 39 9 35 0 46...

Page 149: ...1 873 0 48 476 956 0 60 594 1031 0 72 718 1300 701 0 30 300 809 0 42 418 902 0 54 540 983 0 67 665 1057 0 80 796 1400 737 0 36 355 842 0 48 481 932 0 61 610 1012 0 75 744 1085 0 89 881 1500 774 0 42 417 875 0 55 551 962 0 69 689 1041 0 83 830 1112 0 98 974 AIRFLOW EXTERNAL STATIC PRESSURE in wg AIRFLOW Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watt...

Page 150: ...ke Horsepower Input to Fan Watts Input Watts to Motor Motor drive range 680 to 1044 rpm All other rpms require field supplied drive NOTES Grey box indicates field supplied drive is required Maximum continuous bhp is 1 20 See General Fan Performance Notes FAN PERFORMANCE 50HEQ005 VERTICAL DISCHARGE UNITS STANDARD MOTOR BELT DRIVE AIRFLOW EXTERNAL STATIC PRESSURE in wg AIRFLOW Cfm 0 2 0 4 0 6 0 8 1 ...

Page 151: ...IRFLOW EXTERNAL STATIC PRESSURE in wg AIRFLOW Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1100 0 85 845 1165 0 98 977 1225 1 12 1112 1282 1 26 1252 1337 1 40 1395 1300 1126 0 94 930 1189 1 07 1069 1249 1 22 1211 1306 1 36 1356 1360 1 51 1506 1400 1152 1 03 1023 1215 1 17 1168 1274 1 32 1317 1330 1 48 1469 1384 1 63 1625 1500 1179 1 13 1123...

Page 152: ...8 1900 944 0 71 633 1037 0 87 774 1120 1 04 925 1197 1 22 1084 2000 983 0 81 723 1073 0 98 870 1154 1 16 1026 2100 1023 0 92 821 1110 1 10 975 1189 1 28 1137 2200 1063 1 05 929 1147 1 23 1089 2300 1104 1 18 1046 2400 2500 AIRFLOW EXTERNAL STATIC PRESSURE in wg AIRFLOW Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1224 1 18 1045 1600 1250 1 2...

Page 153: ...1145 1 32 1174 1223 1 52 1346 1296 1 72 1526 1364 1 93 1712 1428 2 15 1905 2500 1185 1 48 1311 1262 1 68 1490 1333 1 89 1676 1399 2 10 1868 1462 2 33 2067 AIRFLOW EXTERNAL STATIC PRESSURE in wg AIRFLOW Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1224 1 18 1045 1291 1 36 1212 1354 1 56 1387 1414 1 77 1570 1472 1 98 1761 1600 1250 1 27 1128 ...

Page 154: ...76 1399 2 10 1868 1462 2 33 2067 AIRFLOW EXTERNAL STATIC PRESSURE in wg AIRFLOW Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1224 1 18 1045 1291 1 36 1212 1354 1 56 1387 1414 1 77 1570 1472 1 98 1761 1600 1250 1 27 1128 1316 1 46 1299 1379 1 66 1478 1438 1 87 1664 1495 2 09 1858 1700 1278 1 37 1219 1343 1 57 1394 1405 1 77 1576 1463 1 99 17...

Page 155: ...3 762 0 35 344 860 0 46 459 944 0 58 579 1020 0 71 705 1300 674 0 28 276 791 0 40 395 887 0 52 517 970 0 65 645 1045 0 78 777 1400 706 0 33 324 820 0 45 451 914 0 59 582 997 0 72 717 1071 0 86 857 1500 738 0 38 379 849 0 52 515 942 0 66 653 1024 0 80 796 1097 0 95 942 AIRFLOW EXTERNAL STATIC PRESSURE in wg AIRFLOW Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts ...

Page 156: ... Input to Fan Watts Input Watts to Motor Motor drive range 1075 to 1455 rpm All other rpms require field supplied drive NOTES Grey box indicates field supplied drive is required Maximum continuous bhp is 2 40 See General Fan Performance Notes FAN PERFORMANCE 50HEQ005 HORIZONTAL DISCHARGE UNITS STANDARD MOTOR BELT DRIVE AIRFLOW EXTERNAL STATIC PRESSURE in wg AIRFLOW Cfm 0 2 0 4 0 6 0 8 1 0 Cfm Rpm ...

Page 157: ...IRFLOW EXTERNAL STATIC PRESSURE in wg AIRFLOW Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1200 1089 0 84 835 1153 0 98 971 1212 1 12 1111 1269 1 26 1256 1322 1 41 1404 1300 1114 0 92 915 1177 1 06 1056 1236 1 21 1202 1292 1 36 1353 1346 1 52 1508 1400 1139 1 01 1000 1202 1 15 1149 1261 1 31 1301 1316 1 47 1457 1369 1 63 1618 1500 1164 1 10 1093...

Page 158: ... 1 23 1096 2000 892 0 67 599 986 0 82 729 1072 0 98 870 1151 1 15 1022 2100 927 0 77 680 1017 0 92 815 1101 1 08 960 1178 1 26 1116 2200 962 0 87 769 1050 1 02 909 1131 1 19 1059 2300 997 0 97 865 1082 1 14 1010 2400 1033 1 09 970 1115 1 26 1120 2500 1069 1 22 1084 AIRFLOW EXTERNAL STATIC PRESSURE in wg AIRFLOW Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm...

Page 159: ...1448 1332 1 83 1625 2500 1069 1 22 1084 1149 1 39 1239 1223 1 58 1403 1293 1 77 1576 1360 1 98 1757 AIRFLOW EXTERNAL STATIC PRESSURE in wg AIRFLOW Cfm 1 2 1 4 1 6 1 8 2 0 Cfm Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1500 1188 1 09 970 1261 1 29 1143 1330 1 49 1327 1395 1 71 1523 1457 1 95 1729 1600 1208 1 16 1033 1279 1 36 1208 1347 1 57 1394 1412 1 79 1590 1474 2 02 1...

Page 160: ...1 97 1748 1508 2 20 1957 1900 1273 1 43 1266 1341 1 63 1447 1405 1 84 1638 1467 2 07 1839 1527 2 31 2050 2000 1296 1 53 1359 1363 1 74 1542 1427 1 95 1736 1488 2 18 1939 1546 2 42 2151 2100 1320 1 64 1459 1386 1 85 1646 1448 2 07 1842 1508 2 30 2047 1566 2 55 2262 2200 1345 1 77 1568 1409 1 98 1758 1471 2 20 1956 1530 2 44 2164 1587 2 68 2380 2300 1371 1 90 1686 1434 2 11 1878 1494 2 34 2080 1553 ...

Page 161: ...138 1107 1075 005 1185 1144 1102 1061 1019 978 936 895 853 812 770 005 1455 1423 1392 1360 1328 1297 1265 1233 1202 1170 1138 1107 1075 006 1460 1425 1390 1355 1319 1284 1249 1214 1179 1144 1108 1073 1035 006 1685 1647 1608 1570 1531 1493 1454 1416 1377 1339 1300 007 1585 1538 1492 1445 1399 1352 1305 1259 1212 1166 1119 007 1685 1647 1608 1570 1531 1493 1454 1416 1377 1339 1300 Approximate fan rp...

Page 162: ... 240 3 phase 4 9 5 8 6 5 7 9 9 6 10 5 12 0 14 7 16 0 15 8 19 3 21 0 19 9 24 3 26 5 002 004B00 005 004B00 004B00 004 005 002 002 003 002 460 480 3 phase 5 5 6 0 10 6 11 5 12 9 14 0 21 1 23 0 23 4 25 5 006 008 009 008 008 008 009 007 208 230 240 3 phase 4 9 5 8 6 5 7 9 9 6 10 5 12 0 14 7 16 0 15 8 19 3 21 0 19 9 24 3 26 5 002 004B00 005 004B00 004B00 004B00 006 002 002 003 003 007 6 Tons 460 480 3 p...

Page 163: ...1 115 0 0 7 4 9 6 5 8 7 31 3 36 3 71 0 77 2 80 80 67 72 160 165 208 230 1 60 197 254 21 115 0 0 7 4 9 9 8 13 0 47 1 54 2 90 7 99 6 100 100 85 93 175 182 13 1 17 4 63 0 72 5 110 6 122 5 125 125 103 114 191 201 15 8 21 0 76 0 87 5 126 9 141 2 150 150 118 131 204 216 005 23 2 23 2 25 25 23 23 108 108 005 4 T 4 9 6 5 13 6 15 6 40 2 42 7 45 45 38 41 122 124 4 Tons 208 230 3 60 187 254 14 1 95 0 0 7 4 9...

Page 164: ...5 13 6 15 6 41 1 43 6 45 45 39 42 151 153 208 230 3 60 187 254 14 1 95 0 0 7 5 8 6 5 8 7 18 0 20 9 46 6 50 3 50 60 44 48 159 159 005 208 230 3 60 187 254 14 1 95 0 0 7 5 8 12 0 16 0 33 3 38 5 65 8 72 3 70 80 62 68 171 176 005 4 T 15 8 21 0 43 9 50 5 79 0 87 3 80 90 74 82 182 188 4 Tons 11 9 15 12 66 6 0 7 2 20 9 25 20 74 460 3 60 414 508 7 1 45 0 0 4 2 6 11 5 13 8 29 1 30 27 80 460 3 60 414 508 7 ...

Page 165: ... 60 60 54 57 149 151 6 5 8 7 31 3 36 3 75 8 82 0 80 90 72 78 164 169 208 230 1 60 197 254 21 0 115 0 0 7 4 9 9 8 13 0 47 1 54 2 95 5 104 4 100 110 90 98 180 187 13 1 17 4 63 0 72 5 115 4 127 3 125 150 109 119 196 206 15 8 21 0 76 0 87 5 131 7 146 0 150 150 124 137 209 221 005 28 0 28 0 30 30 28 28 113 113 005 4 T 4 9 6 5 13 6 15 6 45 0 47 5 50 50 44 46 127 129 4 Tons 208 230 3 60 187 254 14 1 95 0...

Page 166: ...10 125 99 109 247 255 5 Tons 16 9 20 17 104 6 0 7 2 25 9 30 25 111 11 5 13 8 34 1 35 33 118 460 3 60 414 508 8 4 70 0 0 8 3 4 14 0 16 8 37 9 40 36 121 60 3 60 508 8 0 0 0 8 3 23 0 27 7 51 5 60 49 132 25 0 30 1 54 5 60 52 134 LEGEND FLA Full Load Amps HACR Heating Air Conditioning and Refrigeration IFM Indoor Fan Motor LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP Maximum Overcurrent Protecti...

Page 167: ...ater Relay IFC Indoor Fan Contactor IFM Indoor Fan Motor LPS Low Pressure Loss of Charge Switch LSM Limit Switch Manual Reset OFM Outdoor Fan Motor OLR Overload Relay QT Quadruple Terminal RVS Reversing Valve Solenoid SAT Supply Air Thermostat SW1 Switch Fully Open TB Terminal Block TRAN Transformer Field Splice Terminal Marked Marked Wire Terminal Unmarked Terminal Block Splice Splice Marked Fact...

Page 168: ...nsity flexiblefiberglass insulation neoprene coatedon the air side Aluminum foil faced fiberglass insulation shall be used in the gas heat compartment c Cabinet panels shall be easily removable for servicing d Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead rigging e Unit shall have a factory installed sloped condensate drain pan made of a non ...

Page 169: ...tering system AcutrolTM device b Refrigerant filter drier c Reversing valve d Service gauge connections on suction discharge and liquid lines 8 Filter Section a Standard filter section shall consist of factory installed low velocity throwaway 2 in thick fiberglass filters of commercially available sizes b Filter face velocity shall not exceed 320 fpm at nominal airflows c Filter section should use...

Page 170: ...croprocessor control shall provide control of internal building pressure through its accessory power exhaust function Factory set at 100 with a range of 0 to 100 11 EconoMi er2 shall be capable of control from a 4 to 20 mA signal through optional 4 to 20 mA design without microprocessor control required for PremierLink or third party control interface 12 EconoMi er IV Microprocessor Occupied Minim...

Page 171: ... 2 A supplementary supply air fan kit to provide increased air movement into the 62AQ unit 3 A field installed 460 v to 208 230 v transformer to provide power when the Energy Recycler is used with a 460 v rooftop unit s Power Exhaust Accessory for EconoMi er IV or EconoMi er2 Power exhaust shall be used in conjunction with EconoMi er IV or EconoMi er2 to provide system exhaust of up to 100 of retu...

Page 172: ...ld installed in the indoor section of the unit aimed at the indoor coil and condensate pan The short wave length ultra violet light inhibitsandkillsmold fungusandmicrobial growth The lamps have an output rating at 45 F in 400 fpm airflow of 120 microwatts cm2 at 1 meter ab Hinged Panel Option Hinged panel option provide hinged access panels for the filter compressor evaporator fan and control box ...

Page 173: ...1 0 2 0 3 0 4 0 5 003 007 008 012 STATIC PRESSURE in wg FLOW cfm C06073 VERTICAL ECONOMI ER IV AND ECONOMI ER2 PERFORMANCE DATA 50HEQ003 006 50HJQ004 012 50TFQ004 012 HORIZONTAL POWER EXHAUST PERFORMANCE 0 500 1000 1500 2000 2500 0 05 0 15 0 25 Static Pressure in wg Flow in cubic feet per minute cfm 003 007 008 012 0 5 10 15 20 25 30 0 1 0 2 0 3 0 4 0 5 Static Pressure in wg Flow in cubic feet per...

Page 174: ...ER EXHAUST DESCRIPTION APPLICATION USAGE POWER OUTPUT Hp per fan Fans per PE CRPWREXH028A01 Horizontal Power Exhaust 208 230 1 60 All 0 48 1 CRPWREXH029A01 Horizontal Power Exhaust 460 3 60 All 0 48 1 Single or three phase OUTDOOR SOUND POWER TOTAL UNIT 50HJQ ARI RATING OCTAVE BANDS Lw A 50HJQ HEQ RATING decibels 63 125 250 500 1000 2000 4000 8000 003 004 005 76 50 8 63 4 62 2 65 9 69 2 65 9 63 0 ...

Page 175: ... 012 50HJQ008 012 COMPONENT CFM COMPONENT 2250 2500 2750 3000 3250 3500 3750 4000 4250 4500 4750 5000 5250 6250 Vertical EconoMi er IV and EconoMi er2 0 06 0 075 0 09 0 115 0 13 0 15 0 17 0 195 0 22 0 25 0 285 0 325 0 36 Horizontal EconoMi er IV and EconoMi er2 0 1 0 125 0 15 0 18 0 21 0 25 0 275 0 3 0 34 0 388 LEGEND FIOP Factory Installed Option The static pressure must be added to external stat...

Page 176: ...emoved only when using differen tial enthalpy or dry bulb 2 If a separate field supplied 24v transformer is used for the IAQ sensor power supply it cannot have the secondary of the transformer grounded 3 For field installed remote minimum position POT remove black wire jumper between P and P1 and set control minimum position POT to the minimum position C06076 LEGEND AL Ambient Limit OA Outdoor Air...

Page 177: ...py sensor 3 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500 ohm resistor C06077 ECONOMI ER2 WIRING 4 3 5 2 8 6 7 1 10 11 9 12 PINK VIOLET BLACK BLUE YELLOW NOTE 1 NOTE 3 RUN 500 OHM RESISTOR OPTIONAL CO SENSOR 4 20 mA OUTPUT 50HJ540573 ACTUATOR ASSEMBLY RED WHITE ECONOMISER2 PLUG DIRECT DRIVE ACTUATOR 2 NOTES 1 Switch on actuator must be in run position for economize...

Page 178: ... SWITCH SECONDARY 120V SECONDARY 120V X4 X2 X3 X1 600V H1 H3 RED YEL BLU GRA 460V H2 H4 X4 X2 X3 X1 CONVENIENCE O UTLET OPTIONAL SIZES 004 012 C06078 NOTE Convenience outlet is intended for intermittent use of service equipment and not as a power source for extended operation of electrical loads FIELD POWER SUPPLY UNIT DISCONNECT BLK YEL BLU BLK YEL BLU BLK YEL BLU SINGLE POINT CONNECTION BOX BLK ...

Page 179: ... Option is ordered for size 014 and 016 units the Non Fused Disconnect will be factory installed 2 The Disconnect takes the place of TB 1 as shown on the unit wiring diagram label and the component arrangement label NON FUSED DISCONNECT OPTIONAL 50HJQ014 016 C06095 50TFQ HJQ HEQ ...

Page 180: ...180 TYPICAL PIPING AND WIRING 50HEQ003 006 50HJQ004 012 50TFQ004 012 LEGEND NEC National Electrical Code VERTICAL DISCHARGE DUCTING HORIZONTAL DISCHARGE DUCTING C06080 50TFQ HJQ HEQ ...

Page 181: ...er software CCN DESCRIPTION STATUS UNITS POINT LIMITS ACCESS Space Temperature xxx x dF SPT 40 0 to 245 0 dF R W Supply Air Temperature xxx x dF SAT 40 0 to 245 0 dF R W Outside Air Temperature xxx x dF OAT 40 0 to 245 0 dF R W Control Setpoint xxx x dF CLSP R Cooling Total Capacity xxx CCAP 0 to 100 R Heating Total Capacity xxx HCAP 0 to 100 R EconoMi er2 Active No Yes ECOS 0 to 1 R Supply Fan Re...

Page 182: ... SENSOR T 56 SENSOR T 56 SENSOR TM016 WITH PREMIERLINK CONTROL HJ014 WITH PREMIERLINK CONTROL TM004 WITH PREMIERLINK CONTROL HG016 WITH COMFORTLINK CONTROL 3 WIRE COM BUS LID2B DATA LINK ASCII 3 PARTY CONTROL RD BUILDING MECHANICAL ROOM OR OR T 56 SENSOR Warm Cool 3 WIRE COM BUS AT ROOFTOP LEVEL CARRIER CO MFORTLINK PREMIERLINK CO NTROLS C06097 50TFQ HJQ HEQ ...

Page 183: ...LU HS1 WHT HS2 PNK ORN HS3 EXH RVS RED PWR CUT FOR DUAL TRANSFORMER EQUIPMENT RELAYS RED TSTAT CONTROL G Y1 Y2 W1 W2 ENTH GRN YEL BLU WHT PNK ORN RED RED RED RED RED RED J4 DISCRETE SWITCH POSITION 0 POSITION 1 1 LEN CCN LOAD FACTORY DEFAULTS ON POWERUP NO ACTION 4 R Y1 Y2 W1 W2 G C X DDC CONTROL TSTAT CONTROL Y1 CMP SAFE FSD Y2 SFS W1 X X C C RMTOCC NOT USED G W2 TB2 C WHT OR BLK FROM IGC G BLU F...

Page 184: ... Sensor OAT PNK VIO YEL YEL BLU BLU Economi er2 4 20mA BLK RED WHT PremierLink GRN YEL BLU BLU BLU Outdoor Air Quality Sensor Power Exhaust Energy Recycler CCN Comm RMTOCC SFS CMPSAFE FSD RTU Terminal Board TR TR1 SR 2 3 S RED BRN BLK RED GRAY GRAY OUTDOOR AIR ENTHALPY SENSOR RETURN AIR ENTHALPY SENSOR LEGEND COMMS Communications OAT Outdoor Air Temperature Sensor PWR Power RTU Rooftop Unit SAT Su...

Page 185: ...30 seconds to initiate Damper movement from full closed to full open or vice versa will take between 11 2 and 21 2 minutes If free cooling can be used as determined from the appropriate changeover command switch dry bulb enthalpy curve differential dry bulb or differential enthalpy then the control will modulate the dampers open to maintain the mixed air temperature set point at 50 to 55 F If ther...

Page 186: ...fan motor will be energized The unit will now operate in the Heating mode If the thermostat is satisfied during a defrost cycle the unit will continue in the Defrost mode until the time or temperature constraints are satisfied Defrost 50TFQ008 012 and 50HJQ008 012 When the temperature of the outdoor coil drops below 28_F as sensed by the defrost thermostat DFT2 and the defrost timer is at the end ...

Page 187: ... no 1 016 contactor is energized and compressor 014 or compressor no 1 016 will start The outdoor air damper stays at vent position while the indoor fan is operating On units equipped with electric heat when additional heat is needed heating contactor no 2 in the thermostat closes energizing W2 Defrost cycle When the temperature of the outdoor coil drops below 28 F as sensed by the defrost thermos...

Page 188: ...nor speed changes the fan sheave size should be changed Do not reduce the size of the motor sheave this will result in reduced belt horse power ratings and reduced belt life CONCENTRIC D UCT DISTRIBUTION 50H JQ014 016 NOTE 1 Do not drill in this area damage to basepan may result in water leak 2 A 90 degree elbow must be provided in the supply ductwork to comply with UL Underwriters Laboratories co...

Page 189: ...s typically installed in the return duct or occupied space When implementing a DCV control scheme with the EconoMi er IV the control algorithm will modulate the position of the damper between two user configured damper positions Maximum DCV Position and Minimum Occupied position Design airflow rates for these two damper positions should be such that when the damper is at the Maximum DCV position e...

Page 190: ... air damper position will be set at the minimum position Deciding which curve is used is a function of the outdoor climate and the type of economizer utilized Since EconoMi er IV is a fully integrated economizer the range where outdoor air can be utilized for free cooling is expanded and the A and B curves may be used The control point table in the EconoMi er IV Changeover diagram below provides a...

Page 191: ... CRCBDIOX005A00 CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units As such these kits may contain parts that will not be needed for installation 33ZCSENCO2 is an accessory CO2 sensor 33ZCASPCO2 is an accessory aspirator box required for duct mounted applications CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2 accessories Copyright 2007 C...

Reviews: