4–41
T-359
P5-1
Supply Probe Test
Requirements:
For units equipped with secondary supply probe only.
Pass/Fail Criteria
: The temperature difference between supply temperature sen-
sor (STS) and supply recorder sensor (SRS) probe is compared.
If this test fails, “P5-1” and “FAIL” will be displayed. If both Probe tests (this and
the SUPPLY/RETURN TEST) pass, because of the multiple tests, the display will
read “P 5" “PASS.”
P5-2
Return Probe Test
Requirements:
For units equipped with secondary return probe only.
NOTE
Pass/Fail Criteria:
The temperature difference between return tempera-
ture sensor (RTS) and return temperature sensor (RRS) probe is com-
pared.
NOTES
1. If this test fails, “P5-2” and “FAIL” will be displayed. If both Probe tests (this
test and the SUPPLY/RETURN) pass, because of the multiple tests, the dis-
play will read “P 5,” “PASS.”
2. The results of Pre-trip tests 5-0, 5-1 and 5-2 will be used to activate or clear
control probe alarms.
P5-3
Evaporator Fan
Direction Test
Requirements:
Test P5-0 must pass before this test is run.
Setup:
While the evaporator is running on high speed, the temperature differen-
tial between supply temperature sensor (STS) and return temperature sensor
(RTS) probes is measured, with and without heaters energized.
Pass/Fail Criteria:
Passes if differential of STS is 0.25 degree C higher than
RTS.
P5-7
Primary vs Second-
ary Evaporator
Temperature
Sensor Test
Pass/Fail Criteria:
Passes if secondary evaporator temperature sensor (ETS2)
is /- 0.5 degree C of the primary evaporator temperature sensor (ETS1).
P5-8
Suction Pressure
Transducer Test
Requirements:
Test P5-7 must pass before this test is run.
Pass/Fail Criteria:
Passes if suction pressure transducer (SPT) is /- 0 psi
of saturation pressure at current evaporator temperature. Also passes if suction
pressure transducer (SPT) is /- 1 psi of discharge pressure 6 hours after
a power interruption.
P5-9
Suction (Evapora-
tor) Pressure Trans-
ducer Test
Pass/Fail Criteria:
Passes if suction pressure transducer (SPT) is /- 1.5
psi of the evaporator pressure transducer (EPT).
P5-10
Humidity Sensor
Controller Configu-
ration Verification
Test
Requirements:
Test P5-9 must pass before this test is run.
Test is skipped if controller is not configured for the humidity sensor and the volt-
age is less than 0.20 volts.
Pass/Fail Criteria:
Passes if controller configuration has the humidity sensor in
stalled. Fails if controller is not configured for humidity sensor and the voltage is
greater than 0.20 volts.
P5-11
Humidity Sensor
Installation Verifica-
tion Test
Requirements:
Test P5-10 must pass before this test is run.
Pass/Fail Criteria:
Passes if voltage is greater than 0.20 volts for the humidity
sensor. Fails if voltage is less than 0.20 volts for the humidity sensor.
P5-12
Humidity Sensor
Range Check Test
Requirements:
Test P5-11 must pass before this test is run.
Pass/Fail Criteria:
Passes if the voltage for the humidity sensor is between 0.66
volts and 4 volts. Fails if voltage is outside of the 0.66 volt to 4 volt range.
Table 4–7 Controller Pre-trip Test Codes (Continued)
CODE #
TITLE
DESCRIPTION
Summary of Contents for 69NT40-561-019
Page 2: ......
Page 4: ......
Page 74: ......
Page 127: ...8 3 T 359 Figure 8 2 SCHEMATIC DIAGRAM Evergreen Unit Configuration ...
Page 128: ...T 359 8 4 Figure 8 3 UNIT WIRING DIAGRAM Evergreen Unit Configuration Sheet 1 of 2 ...
Page 129: ...8 5 T 359 Figure 8 4 UNIT WIRING DIAGRAM Evergreen Unit Configuration Sheet 2 of 2 ...
Page 130: ......
Page 134: ......
Page 135: ......