Table 4–7 Controller Pre-trip Test Codes
CODE #
TITLE
DESCRIPTION
NOTE
“Auto” or “Auto1” menu includes the: P0, P1, P2, P3, P4, P5, P6 and rSLts. “Auto2” menu
includes P0, P1, P2, P3, P4, P5, P6, P7, P8, P9, P10 and rSLts. “Auto3” menu includes P0, P1,
P2, P3, P4, P5, P6, P7 and P8.
P0-0
Pre-trip Initiated
All lights and display segments will be energized for five seconds at the start of
the pre-trip. Since the unit cannot recognize lights and display failures, there are
no test codes or results associated with this phase of pre-trip.
P1-0
Heaters Turned On
Setup:
Heater must start in the OFF condition, and then be turned on. A current
draw test is done after 15 seconds.
Pass/Fail Criteria:
Passes if current draw change is within the range specified.
P1-1
Heaters Turned Off
Setup:
Heater must start in the ON condition, and then be turned off. A current
draw test is done after 10 seconds.
Pass/Fail Criteria:
Passes if current draw change is within the range specified.
P2-0
Condenser Fan On
Requirements:
Water pressure switch or condenser fan switch input must be
closed.
Setup:
Condenser fan is turned ON, a current draw test is done after 15 seconds.
Pass/Fail Criteria:
Passes if current draw change is within the range specified.
P2-1
Condenser Fan Off
Setup:
Condenser fan is turned OFF, a current draw test is done after 10 sec-
onds.
Pass/Fail Criteria:
Passes if current draw change is within the range specified.
P3
Low Speed
Evaporator Fans
Requirements:
The unit must be equipped with a low speed evaporator fan, as
determined by the Evaporator Fan speed select configuration variable.
P3-0
Low Speed
Evaporator Fan Mo-
tors On
Setup:
The High Speed Evaporator fans will be turned on for 10 seconds, then
off for two seconds, then the low speed evaporator fans are turned on. A current
draw test is done after 60 seconds.
Pass/Fail Criteria:
Passes if change in current draw is within the range specified.
P3-1
Low Speed
Evaporator
Fan Motors Off
Setup:
The Low Speed Evaporator fan is turned off, a current draw test is done
after 10 seconds.
Pass/Fail Criteria:
Passes if change in current draw is within the range specified.
P4-0
High Speed
Evaporator
Fan Motors On
Setup:
The high speed evaporator fan is turned on, a current draw test is done
after 60 seconds.
Pass/Fail Criteria:
Passes if change in current draw is within the range specified.
P4-1
High Speed
Evaporator
Fan Motors Off
Setup:
The high speed evaporator fan is turned off, a current draw test is done
after 10 seconds.
Pass/Fail Criteria:
Passes if change in current draw is within the range specified.
P5-0
Supply/Return
Probe Test
Setup:
The High Speed Evaporator Fan is turned on and run for eight minutes,
with all other outputs de-energized.
Pass/Fail Criteria:
A temperature comparison is made between the return and
supply probes.
NOTE
If this test fails, “P5-0” and “FAIL” will be displayed. If both Probe tests
(this test and the PRIMARY/ SECONDARY) pass, the display will read
“P5” “PASS.”
Summary of Contents for 69NT40-561-019
Page 2: ......
Page 4: ......
Page 74: ......
Page 127: ...8 3 T 359 Figure 8 2 SCHEMATIC DIAGRAM Evergreen Unit Configuration ...
Page 128: ...T 359 8 4 Figure 8 3 UNIT WIRING DIAGRAM Evergreen Unit Configuration Sheet 1 of 2 ...
Page 129: ...8 5 T 359 Figure 8 4 UNIT WIRING DIAGRAM Evergreen Unit Configuration Sheet 2 of 2 ...
Page 130: ......
Page 134: ......
Page 135: ......