![Carrier 69NT40-489-100 Series Operation And Service Manual Download Page 85](http://html1.mh-extra.com/html/carrier/69nt40-489-100-series/69nt40-489-100-series_operation-and-service-manual_2563838085.webp)
61
T-305
e. Partially frontseat (turn clockwise) the suction service
valve and slowly add charge until the refrigerant
appears at the proper level.
6.8 COMPRESSOR
WARNING
Make sure power to the unit is OFF and
power plug disconnected before replacing
the compressor.
NOTES
1 The compressor should not operate in a
vacuum greater than 500 mm/hg (20
inches/hg).
2 The service replacement compressor is
sold without shutoff valves (but with valve
pads), and without terminal box and cover.
Customer should retain the original
terminal box, cover, and high pressure
switch for use on replacement compressor.
3 Check oil level in service replacement
compressor. (Refer to section 6.8.6, page
65.)
4 A compressor terminal wiring kit must be
ordered as a separate item when ordering
replacement compressor. Appropriate
installation instructions are included with
kit.
5 Refer to Table 17, page 82 and Table 18,
page 83 for applicable compressor wear
limits and torque values.
6 See to Figure 54, page 85 for charts on
compressor pressure, temperature and
motor current curves.
6.8.1 Removal and Replacement of Compressor
a. Remove the protective guard from lower section of
the unit.
b. Pump down low side (refer to section 6.4, page 59) or
frontseat compressor service valves and remove re-
frigerant from compressor using a refrigerant recov-
ery system.
c. Locate the compressor junction box. Tag and discon-
nect wiring from compressor terminals and remove
compressor junction box.
d. Loosen service valve mounting bolts, break seal and
then remove bolts.
e. Remove compressor plate mounting bolts.
f. Remove compressor and mounting plate. Refer to
section 2.2, page 11 for weight of compressor.
g. Remove high pressure switch (HPS) from compres-
sor and check operation of switch (refer to section
6.9.2, page 66).
1
2
3
4
5
6
7
8
10
11
12
13
14
15
9
16
1. Discharge Valve
Flange
2. High Side Pressure
Connection
3. Low Side Pressure
Connection
4. Suction Valve Flange
5. Motor End Cover
6. Serial/Model No. Plate
7. Crankcase Heater
8. Bottom Plate
9. Sight Glass
10. Oil Drain Plug
11. Oil Charging Valve
12. Bearing Head
13. Oil Pump
14. Oil Fill Plug
15. Cylinder Head
16. Valve Plate
Figure 27. Compressor
h. Remove compressor mounting bolts from mounting
plate and install mounting plate on replacement com-
pressor.
i. Install replacement compressor terminal wiring kit,
following instructions included with kit.
j. Install high pressure switch on compressor.
k. Install compressor and mounting plate in unit.
l. Connect junction box(es) to compressor and connect
all wiring per wiring diagram. Install junction box
cover(s).
m.Install new gaskets on service valves.
n. Install mounting bolts in service valves and torque to
2.77 to 4.15 mkg (20-30 ft/lb).
o. Attach two hoses (with hand valves near vacuum
pump) to the suction and discharge service valves.
Dehydrate and evacuate compressor to 500 microns
(75.9 cm Hg vacuum = 29.90 inches Hg vacuum).
Turn off valves on both hoses to pump.
p. Fully backseat (open) both suction and discharge
service valves.
q. Remove vacuum pump lines.
r. Start unit and check refrigerant charge. (Refer to sec-
tion 6.7, page 60.)
s. Check moisture-liquid indicator for wetness. Change
filter-drier if necessary. (Refer to section 6.13, page
68.)
t. Check compressor oil level per section 6.8.6, page
65. Add oil if necessary.
Summary of Contents for 69NT40-489-100 Series
Page 2: ......
Page 4: ......
Page 14: ...Safety 10 T 305...
Page 28: ...4 T 305...
Page 40: ...16 T 305...
Page 50: ...26 T 305 Figure 12 Standard Configuration Report...
Page 112: ...88 T 305...
Page 164: ...140 T 305...
Page 167: ...143 T 305 Based on drawings 62 10526 Rev and 62 10736 Rev Figure 90 Electrical Schematic CA...