background image

4---7

verse currents can cause damage to the assembly or any of

the component parts. The rotating diode bridge may be

removed through the bearing cap on the rear of the

generator. (See Figure 4---11 and Figure 4---10)

1. Remove the bearing cap by removing the four

bolts shown in Figure 4---10 and both the bearing and

rectifier assembly will be visible.

2. Use a bearing puller to remove the bearing from

main shaft being careful to locate the puller on the inner

race of the bearing to avoid bearing damage. Once the

bearing is free, it is then necessary to disconnect the

alternator and exciter rotor leads as shown in

Figure 4---10.

3. Remove the three hold---down cap screws which

secure the rectifier assembly to its adapter. Once this

procedure is complete the rectifier assembly is free for

removal.

Follow the testing procedures outlined in paragraph

4.6.1.d.

After the rectifier assembly has been repaired or

replaced, reverse the procedure as stated above, being

careful that all lead connections are tight and that set

screws are locked with Loctite. (Loctite Corporation)

1

2

2

1

1

1. Bearing

4. Exciter Rotor Lead

2. Rotating Diode Bridge 5. Rotating Diode

3. Alternator Rotor Lead
Figure 4---11. A---C Generator (Rectifier Assembly)

d. Testing Diodes With An Ohmmeter

A

A

C

C

RED LETTERING BLACK LETTERING

“R” After Number

Forward

Reverse

Polarity

Polarity

Diode

Diode

A (+) = Anode

C (---) = Cathode

Figure 4---12. Diode Testing

1. Remove the diode from the circuit. Do not press

body out of heat sink. Disconnect the lead. Do not use

excessive heat in unsoldering the lead.

2. A good diode should have a low resistance when

the + of an ohm meter is connected to the anode and the

--- to the cathode, and a high resistance when the polarity

of the ohmmeter is reversed.

(See Figure 4---12)

If both resistances are high or both are low, then the

diode is defective and should be replaced.

e. Rotor Damage

The damper bars of the generator prevent excessive

hunting when AC generators are operated in parallel.

Damper bars, because they must have a low electrical

resistance and are subjected to extreme centrifugal

forces, must be mechanically secure and permanent.

Consequently, they are welded to end plates completely

covering the field.

All rotors are static and dynamically balanced to a

high degree on precision machines to assure minimum

vibration. They will, therefore, remain dynamically stable

at speed well beyond the synchronous speed of the

generator. The rotors on generators are, however,

subjected to extreme centrifugal forces which can in-

crease beyond safe operating limits at overspeed. There-

fore, the prime mover should be adequately governed to

prevent overspeed.

Damage to the rotor can also occur due to overheat-

ing which can be caused by the air flow being restricted

from dust or other foreign objects collecting in the air

passage.

If a rotor becomes defective, it should be returned to

the factory with full nameplate data, because the rotor

coils are enclosed in welded squirrel case winding. To

repair a rotor the special tooling and technique of the

factory is necessary and essential. Should a failure occur,

Carrier Transicold should be notified immediately and

steps will be taken to get the generator back into service

with the least expense; and more important, to determine

the cause of the failure and take steps to prevent a

recurrence.

f. Generator Windings (Drying)

Generators that have been in transit or storage for

long periods may be subjected to extreme temperature

and moisture changes. This can cause excessive con-

densation, and the generator windings should be thor-

oughly dried out before bringing the generator up to full

nameplate voltage. If this precaution is not taken, serious

damage to the generator can result. The following steps

should be taken to effectively dry the generator windings:

1. (a)Place generator in drying oven or hot room.

(b)Dry with warm air blower directed through

windings.

2. (a)If the generator has been operated and then

put into storage for any period of time, a P.D. George

#11127 type air---dry fungus resistant varnish should be

applied.

Experience has shown that it is necessary to take these

precautions in locations such as seaboard installations

and other highly humid areas. Some installations will be

in atmospheres that are much more corrosive than

others. A little precautions along the lines outlined here

could eliminate an unnecessary repair job.

Each generator was subjected to a standard NEMA

insulation test, which means 1000 volts plus twice the

highest voltage for which the generator is rated was

impressed between the winding and frame. All machines

are insulated with a high safety factor for the class of

Summary of Contents for 69GN15-114

Page 1: ...SERVICE MANUAL OPERATION AND DIESEL DRIVEN 69GN15 114 124 T 242 03 GENERATOR SET MODELS...

Page 2: ...ier Corporation 1990 Printed in U S A 0890 S Carrier Transicold Division Carrier Corporation P O Box 4805 Syracuse N Y 13221 OPERATION AND DIESEL DRIVEN GENERATOR SET MODELS 69GN15 114 124 SERVICE MAN...

Page 3: ...on 1 5 1 9 3 Voltage Regulator Operation 12 volts d c 1 5 1 10 Main Alternator A C Generator 1 6 1 10 1 Principle of Operation 1 6 1 10 2 A C Generator Main Alternator Circuit Diagram 1 6 2 OPERATION...

Page 4: ...er 4 3 4 3 8 Servicing Glow Plugs 4 4 4 4 Servicing the Alternator 4 4 4 4 1 Preliminary Checks and Tests 4 4 4 4 2 Test Tools 4 4 4 4 3 Problem Area Determination 4 4 4 4 4 In Unit Alternator Regulat...

Page 5: ...2 4 2 Speed Adjustment 4 3 4 3 Mechanical Fuel Pump 4 3 4 4 Air Cleaner 4 3 4 5 Engine Crankcase Breather 4 4 4 6 Open Diode Trio Test 4 4 4 7 Open Regulator Test 4 5 4 8 Alternator Output Test 4 5 4...

Page 6: ...TY DEVICES System components are protected from damage caused by unsafe operating conditions by automatically shutting down the diesel engine when such conditions occur This is accomplished by the saf...

Page 7: ...A C Generator 20 Electrical Receptacle Figure 1 1 Generator Set Front View Typical 1 Circuit Breaker CB 1 2 Oil Pressure Gauge 3 Water Temperature Gauge 4 Ammeter 5 Terminal Board 6 Circuit Breaker CB...

Page 8: ...engine piston goes through the intake stroke the piston draws clean fresh air down into the cylinder for the compression and power strokes As the engine goes through its exhaust stroke the upward mov...

Page 9: ...aker Trip Light This light red may be checked unit not running by placing the circuit breaker CB in the off position and at the same time moving the ignition switch to the run position When the circui...

Page 10: ...the brushes and rotor slip rings Two completely sealed ball bearings support the rotor in the front and rear housing 1 2 3 4 5 6 7 1 AC Tap 2 Back Cover 3 Positive Output B 4 Integral Regulator 5 Exci...

Page 11: ...windings and the generator stator windings are internally con nected within the stator housing Only the output power leads of the generator unit are brought out to the generator terminal box 1 10 2 A...

Page 12: ...frigeration unit power plug in genset power receptacle 6 Install battery charger plug in receptacle at the base of the generator control box 69GN15 114 only b Removal Reverse steps in paragraph a 2 2...

Page 13: ...tch will automatically be in the OFF position when released 4 Complete pre trip inspection Refer to paragraph 2 2 b b Stopping Instructions 1 Push ignition switch to the OFF position 2 4 CONTROL CIRCU...

Page 14: ...ers Replace Faulty fuel control operation 4 3 3 Run control relay 4 3 3 Glow plug s defective 4 3 8 Plugged fuel lines to injector s Engine Manual Mechanical fuel pump malfunction 4 3 5 c Starter cran...

Page 15: ...n does not Defective starter Engine Manual disengage after engine is running 3 1 4Malfunction In the Engine Starting Circuit a No power to Battery defective Correct starter motor Loose electrical conn...

Page 16: ...ater pump Engine Manual d Excessive crankcase pressure Plugged crankcase breather line 4 3 7 3 2 ALTERNATOR AUTOMOTIVE TYPE Battery Undercharged Defective cables dirty battery posts or corroded termin...

Page 17: ...tuating voltage Fluctuating speed 4 3 4 or May be indicated by Irregular speed of engine Engine Manual flickering lights Loose terminal or load connections Tighten Defective bearing causing uneven air...

Page 18: ...2 b X 4 Check total time meter Run 10 min 4 1 3Every 1000 Hour Maintenance Normal Operating Conditions X X 1 Complete 400 Hour Maintenance 4 1 2 X 2 Tighten engine and generator mounting bolts 4 7 X 3...

Page 19: ...eeze meeting GM specifications GM 6038M or equal c Close drain cock and fill system with clean untreated water to which three to five percent of an akalined based radiator cleaner should be added six...

Page 20: ...counter clockwise to loosen and re move item 1 2 Remove banjo fitting item 2 and let it hang loose making sure to keep copper rings item 4 for re placement 3 Turn filter item 3 counter clockwise and...

Page 21: ...r charging or damage to the charging system 2 Badly corroded battery cables could prevent the battery from reaching a fully charged condition c Check battery condition and charge if necessary A low or...

Page 22: ...gure 4 7 Open Regulator Test Test No 3 Alternator Output Test CONDITIONS Engine running after voltmeter is connected as shown in Figure 4 8 VOLTS AC TAP TACH POS OUTPUT B BATTERY GROUND INTEGRAL REGUL...

Page 23: ...3 Check belt tension correct specifications are 40 45 lbs on the Burroughs gauge Carrier Transicold Part No 07 00203 4 6 SERVICING THE GENERATOR MAIN ALTERNATOR 4 6 1Preventive Maintenance and Operat...

Page 24: ...mically balanced to a high degree on precision machines to assure minimum vibration They will therefore remain dynamically stable at speed well beyond the synchronous speed of the generator The rotors...

Page 25: ...or output voltage does not build up 4 6 2Installation and Removal a Removing the Generator 1 Remove ground wire from frame of generator set 2 Remove generator leads from power junction box then remove...

Page 26: ...r 1 Battery w box must be removed along with discon necting the ground strap and moving the control box aside for clear access to the generator s shockmounts 2 Follow the procedure for removing engine...

Page 27: ...crews 3 8 securing tank to bottom frame members 5 Remove two capscrews 1 4 item 10 securing bottom flange of control box to frame front view 6 Remove two capscrews 1 4 securing control box item 4 and...

Page 28: ...it breaker CB1 and the start stop switch are in the OFF position Also disconnect power plug and cable Make sure the power plug s are clean and dry before connecting to any power receptacle WARNING Hig...

Page 29: ...GP GLOW PLUG SWITCH 9 HWT WATER TEMP SWITCH 10 IGN IGNITION SWITCH 10 LOP LOW OIL PRESSURE 12 OPG OIL PRESSURE GAUGE 12 OPS OIL PRESSURE SENDER 9 11 RCR RUN CONTROL RELAY 5 SM STARTER MOTOR 5 17 SS S...

Page 30: ...5 3 1 thru 10 are wires from A C generator Figure 5 1 Electrical Wiring Schematic Diagram Models 69GN15 114 Drawing Number 69GN15 1064 Revision D Sheet 2 of 2...

Page 31: ...ITION SWITCH 10 LOP LOW OIL PRESSURE 12 OPG OIL PRESSURE GAUGE 12 OPS OIL PRESSURE SENDER 9 11 RCR RUN CONTROL RELAY 5 SM STARTER MOTOR 5 17 SS STARTER SOLENOID 14 TT TOTAL TIME METER 1 V VOLTMETER 6...

Page 32: ...5 5 5 6 1 thru 10 are wires from A C generator Figure 5 2 Electrical Wiring Schematic Diagram Models 69GN15 124 Drawing Number 69GN15 1104 Revision B Sheet 2 of 2...

Reviews: