background image

2---2

12. Connect power cable to refrigeration unit. Start

genset as detailed in paragraph 2.3 and then turn

refrigeration unit on to check operation.

(Refer to paragraph b.)

13. Grease Fuel Solenoid plunger.

(Use P/N 07---00245---00.)

b. After Starting Generator Set

1. Refer to paragraph 2.3 for starting and stopping

instructions.

2. Check voltmeter. Should be 460 volts a---c (

¦

5% no load). Volt meter indicating needle should be

pointing to high side of green band (1820 to 1840 rpm, no

load) (1710 rpm, with load).

3. Check total time meter operation.

(Run engine 10 minutes)

4. Listen for abnormal bearing noise.

(12 vdc alternator and main alternator)

5. Check fuel lines, lube oil lines and filters for

leaks.

6. Check radiator and hoses for leaks.
7. Check exhaust system for leaks.
8. Check operation of indicator light.

(Refer to paragraph 1.7.2.f.)

2.3 STARTING AND STOPPING

INSTRUCTIONS

a. Starting Instructions

WARNING

Under no circumstances should ether or any

other unauthorized starting aids be used in

conjunction with the glow plugs.

NOTE

When starting the engine, it is necessary to

continue to hold the glow plug switch in the

UP position until the engine develops

sufficient oil pressure to close the oil pressure

safety switch, energizing and completing all

circuits for unit operation.

1. Hold glow plug switch in the UP position for 30

seconds. (See Figure 1---2)

NOTE

Below 0

_

F, hold glow plug switch for two

minutes, release switch for 30 seconds and

again hold glow plug switch for two minutes. If

engine does not start after 10 seconds

cranking, wait for 30 seconds before repeating

starting procedure.

2. With glow plug switch held in the

UP

position,

push the ignition switch to the

START

position.

3. After engine has started, continue to hold the

glow plug switch in the

UP

position until the oil pressure

safety switch closes (when engine develops sufficient oil

pressure). The glow plug switch will automatically be in

the

OFF

position when released.

4. Complete pre---trip inspection.

(Refer to paragraph 2.2.b.)

b. Stopping Instructions

1. Push ignition switch to the

OFF

position.

2.4 CONTROL CIRCUIT OPERATION

WARNING

Beware of moving V---belts and belt driven

components.

CAUTION

The generator set circuit breaker must be in the

ON position in order to supply power to the

refrigeration unit.

When the glow plug switch is held in the pre---heat

position, current flows to the glow plugs. The glow plugs

(starting aids) provide a source of heat to pre---heat the

combustion chamber during start---up. Power also flows

to the run control relay which energizes, and closes the

RCR

contacts. From the relay

RCR

, power flows through

the high water temperature switch to ground.

In order to start engine, hold the glow plug switch in

the up position for the recommended time as detailed in

paragraph 2.3.a. and then hold the ignition (Start---Run---

Off) switch in the

START

position. With ignition switch in

the

START

position, starter solenoid is energized closing

starter motor contactor contacts (SS), which energizes

starter motor. The starter motor turns over the engine

resulting in pumping fuel to the engine cylinders by the

injection pump. This fuel is ignited by heat of compres-

sion; thus starting the engine. Also, run control relay is

energized at the same time to close a set of contacts and

completes a circuit to the fuel solenoid.

When the engine has developed sufficient oil pres-

sure, oil pressure safety switch contacts close to maintain

a circuit to the run control relay. Energizing this relay

closes (RCR) contacts providing a circuit to keep the fuel

run solenoid energized as long as the safety switch

contacts remain closed. The glow plug switch is then

released and the ignition switch is released to the

RUN

position. Releasing glow plug switch de---energizes the

glow plugs.

Total time meter is energized simultaneously with the

fuel solenoid.

With the engine running, the belt---driven alternator

provides 12---volt d---c power to operate the control

system and charge the battery.

Summary of Contents for 69GN15-114

Page 1: ...SERVICE MANUAL OPERATION AND DIESEL DRIVEN 69GN15 114 124 T 242 03 GENERATOR SET MODELS...

Page 2: ...ier Corporation 1990 Printed in U S A 0890 S Carrier Transicold Division Carrier Corporation P O Box 4805 Syracuse N Y 13221 OPERATION AND DIESEL DRIVEN GENERATOR SET MODELS 69GN15 114 124 SERVICE MAN...

Page 3: ...on 1 5 1 9 3 Voltage Regulator Operation 12 volts d c 1 5 1 10 Main Alternator A C Generator 1 6 1 10 1 Principle of Operation 1 6 1 10 2 A C Generator Main Alternator Circuit Diagram 1 6 2 OPERATION...

Page 4: ...er 4 3 4 3 8 Servicing Glow Plugs 4 4 4 4 Servicing the Alternator 4 4 4 4 1 Preliminary Checks and Tests 4 4 4 4 2 Test Tools 4 4 4 4 3 Problem Area Determination 4 4 4 4 4 In Unit Alternator Regulat...

Page 5: ...2 4 2 Speed Adjustment 4 3 4 3 Mechanical Fuel Pump 4 3 4 4 Air Cleaner 4 3 4 5 Engine Crankcase Breather 4 4 4 6 Open Diode Trio Test 4 4 4 7 Open Regulator Test 4 5 4 8 Alternator Output Test 4 5 4...

Page 6: ...TY DEVICES System components are protected from damage caused by unsafe operating conditions by automatically shutting down the diesel engine when such conditions occur This is accomplished by the saf...

Page 7: ...A C Generator 20 Electrical Receptacle Figure 1 1 Generator Set Front View Typical 1 Circuit Breaker CB 1 2 Oil Pressure Gauge 3 Water Temperature Gauge 4 Ammeter 5 Terminal Board 6 Circuit Breaker CB...

Page 8: ...engine piston goes through the intake stroke the piston draws clean fresh air down into the cylinder for the compression and power strokes As the engine goes through its exhaust stroke the upward mov...

Page 9: ...aker Trip Light This light red may be checked unit not running by placing the circuit breaker CB in the off position and at the same time moving the ignition switch to the run position When the circui...

Page 10: ...the brushes and rotor slip rings Two completely sealed ball bearings support the rotor in the front and rear housing 1 2 3 4 5 6 7 1 AC Tap 2 Back Cover 3 Positive Output B 4 Integral Regulator 5 Exci...

Page 11: ...windings and the generator stator windings are internally con nected within the stator housing Only the output power leads of the generator unit are brought out to the generator terminal box 1 10 2 A...

Page 12: ...frigeration unit power plug in genset power receptacle 6 Install battery charger plug in receptacle at the base of the generator control box 69GN15 114 only b Removal Reverse steps in paragraph a 2 2...

Page 13: ...tch will automatically be in the OFF position when released 4 Complete pre trip inspection Refer to paragraph 2 2 b b Stopping Instructions 1 Push ignition switch to the OFF position 2 4 CONTROL CIRCU...

Page 14: ...ers Replace Faulty fuel control operation 4 3 3 Run control relay 4 3 3 Glow plug s defective 4 3 8 Plugged fuel lines to injector s Engine Manual Mechanical fuel pump malfunction 4 3 5 c Starter cran...

Page 15: ...n does not Defective starter Engine Manual disengage after engine is running 3 1 4Malfunction In the Engine Starting Circuit a No power to Battery defective Correct starter motor Loose electrical conn...

Page 16: ...ater pump Engine Manual d Excessive crankcase pressure Plugged crankcase breather line 4 3 7 3 2 ALTERNATOR AUTOMOTIVE TYPE Battery Undercharged Defective cables dirty battery posts or corroded termin...

Page 17: ...tuating voltage Fluctuating speed 4 3 4 or May be indicated by Irregular speed of engine Engine Manual flickering lights Loose terminal or load connections Tighten Defective bearing causing uneven air...

Page 18: ...2 b X 4 Check total time meter Run 10 min 4 1 3Every 1000 Hour Maintenance Normal Operating Conditions X X 1 Complete 400 Hour Maintenance 4 1 2 X 2 Tighten engine and generator mounting bolts 4 7 X 3...

Page 19: ...eeze meeting GM specifications GM 6038M or equal c Close drain cock and fill system with clean untreated water to which three to five percent of an akalined based radiator cleaner should be added six...

Page 20: ...counter clockwise to loosen and re move item 1 2 Remove banjo fitting item 2 and let it hang loose making sure to keep copper rings item 4 for re placement 3 Turn filter item 3 counter clockwise and...

Page 21: ...r charging or damage to the charging system 2 Badly corroded battery cables could prevent the battery from reaching a fully charged condition c Check battery condition and charge if necessary A low or...

Page 22: ...gure 4 7 Open Regulator Test Test No 3 Alternator Output Test CONDITIONS Engine running after voltmeter is connected as shown in Figure 4 8 VOLTS AC TAP TACH POS OUTPUT B BATTERY GROUND INTEGRAL REGUL...

Page 23: ...3 Check belt tension correct specifications are 40 45 lbs on the Burroughs gauge Carrier Transicold Part No 07 00203 4 6 SERVICING THE GENERATOR MAIN ALTERNATOR 4 6 1Preventive Maintenance and Operat...

Page 24: ...mically balanced to a high degree on precision machines to assure minimum vibration They will therefore remain dynamically stable at speed well beyond the synchronous speed of the generator The rotors...

Page 25: ...or output voltage does not build up 4 6 2Installation and Removal a Removing the Generator 1 Remove ground wire from frame of generator set 2 Remove generator leads from power junction box then remove...

Page 26: ...r 1 Battery w box must be removed along with discon necting the ground strap and moving the control box aside for clear access to the generator s shockmounts 2 Follow the procedure for removing engine...

Page 27: ...crews 3 8 securing tank to bottom frame members 5 Remove two capscrews 1 4 item 10 securing bottom flange of control box to frame front view 6 Remove two capscrews 1 4 securing control box item 4 and...

Page 28: ...it breaker CB1 and the start stop switch are in the OFF position Also disconnect power plug and cable Make sure the power plug s are clean and dry before connecting to any power receptacle WARNING Hig...

Page 29: ...GP GLOW PLUG SWITCH 9 HWT WATER TEMP SWITCH 10 IGN IGNITION SWITCH 10 LOP LOW OIL PRESSURE 12 OPG OIL PRESSURE GAUGE 12 OPS OIL PRESSURE SENDER 9 11 RCR RUN CONTROL RELAY 5 SM STARTER MOTOR 5 17 SS S...

Page 30: ...5 3 1 thru 10 are wires from A C generator Figure 5 1 Electrical Wiring Schematic Diagram Models 69GN15 114 Drawing Number 69GN15 1064 Revision D Sheet 2 of 2...

Page 31: ...ITION SWITCH 10 LOP LOW OIL PRESSURE 12 OPG OIL PRESSURE GAUGE 12 OPS OIL PRESSURE SENDER 9 11 RCR RUN CONTROL RELAY 5 SM STARTER MOTOR 5 17 SS STARTER SOLENOID 14 TT TOTAL TIME METER 1 V VOLTMETER 6...

Page 32: ...5 5 5 6 1 thru 10 are wires from A C generator Figure 5 2 Electrical Wiring Schematic Diagram Models 69GN15 124 Drawing Number 69GN15 1104 Revision B Sheet 2 of 2...

Reviews: