background image

4---2

4.2 PRIMING THE FUEL SYSTEM

The unit is equipped with a mechanical fuel lift pump

(Also, refer to paragraph 4.3.5), it is mounted on the

engine next to the injection pump. This pump has a

manual plunger for bleeding fuel when the fuel tank has

been run dry.

Since the unit employs a closed fuel circuit, it is

recommended to use the following steps:

1. Turn bleed valve (Red) counter---clockwise until

fully opened (see Figure 1---5).

2. Turn the top of the manual plunger counter---

clockwise to unlock it. (see Figure 4---3) Then, rapidly

hand pump the manual plunger until a positive pressure

(resistance) is felt, which will indicate fuel flow.

3. Depress and turn the top of the manual plunger

clockwise to lock in place.

4. Start engine. (refer to section 2.3.)
5. When engine is running properly, turn bleed valve

clockwise until fully closed.

4.3 ENGINE SERVICE AND COMPONENTS
4.3.1Cooling System

The radiator, externally and internally, must be clean

for adequate cooling. The fan belt must be adjusted

periodically to provide maximum air flow. (Refer to

paragraph 4.5)

Do the following to service the cooling system:

a. Remove all foreign material from the radiator coil

by reversing the normal air flow (Force air in thru the

front of the radiator and discharge thru the radiator

toward the engine.) Compressed air or water may be

used as a cleaning agent. It may be necessary to use warm

water mixed with any good commercial dishwasher

detergent. Rinse coil(s) with fresh water if a detergent is

used.

b. Drain coolant completely by opening drain---cock

and removing radiator cap.

CAUTION

Use only ethylene glycol, anti---freeze (with

inhibitants) in system as glycol by itself will

damage the cooling system.
Always add pre---mixed 50/50 anti---freeze and

water to radiator/engine. Never exceed more

than a 50% concentration of anti---freeze. Use a

low

silicate

anti---freeze

meeting

GM

specifications GM 6038M or equal.

c. Close drain---cock and fill system with clean,

untreated water to which three to five percent of an

akalined based radiator cleaner should be added; six

ounces --- dry = 151 grams to one gallon (3.8 litre) of

water.

d. Run engine 6 to 12 hours and drain system while

warm. Rinse system three times after it has cooled down.

Refill system with water.

e. Run engine to operating temperature. Drain

system again and fill with treated water/anti---freeze.

(See Caution note and refer to paragraph 1.3.c.)

NEVER

POUR COLD WATER INTO A HOT ENGINE,

however

hot water can always be added to a cold engine.

4.3.2Lube Oil Filters

The full flow filter is located near the run solenoid as

shown in Figure 1---1.

After warming up the engine, stop engine, remove

drain plug from oil reservoir and drain engine lube oil.

Lightly oil gasket on filter before installing.

Replace filters and add lube oil. (Refer to paragraph

1.4.j.) Warm up engine and check for leaks.

4.3.3Servicing the Fuel Solenoid and Linkage

NOTE

Periodically grease (P/N 07---00245---00) Fuel

Solenoid plunger.

1. Remove spring linkage from injection pump run

lever (item 3, Figure 4---1).

1

2

3

4

5

6

RUN

CONTROL

LEVER

2.47

(6.27cm)

(8.18cm)

3.22

ENERGIZED

DE--ENERGIZED

1. Solenoid

4. Clip

2. Solenoid bracket

5. Linkage rod

3. Spring

6. Boot

Figure 4---1. Fuel Solenoid Assembly

2. Disconnect wiring to solenoid. Remove clip (item

4) from linkage rod (item 5). Remove mounting hardware

from solenoid and then remove solenoid.

3. Install new solenoid and mounting hardware,

connect wiring. Place ignition (Start---Run---Off) switch

in the START position to energize solenoid. Check

energized dimension as shown in Figure 4---1. Turn

switch OFF. Check de---energized dimension. If ener-

gized dimension needs adjusting, loosen solenoid mount-

ing bolts and move solenoid.

4. Energize solenoid and check clearance.
5. If the engine does not shut off when the fuel

solenoid is de---energized, loosen the four (4) mounting

bolts and move the solenoid toward the lever until it shuts

off. Tighten the mounting bolts.

Summary of Contents for 69GN15-114

Page 1: ...SERVICE MANUAL OPERATION AND DIESEL DRIVEN 69GN15 114 124 T 242 03 GENERATOR SET MODELS...

Page 2: ...ier Corporation 1990 Printed in U S A 0890 S Carrier Transicold Division Carrier Corporation P O Box 4805 Syracuse N Y 13221 OPERATION AND DIESEL DRIVEN GENERATOR SET MODELS 69GN15 114 124 SERVICE MAN...

Page 3: ...on 1 5 1 9 3 Voltage Regulator Operation 12 volts d c 1 5 1 10 Main Alternator A C Generator 1 6 1 10 1 Principle of Operation 1 6 1 10 2 A C Generator Main Alternator Circuit Diagram 1 6 2 OPERATION...

Page 4: ...er 4 3 4 3 8 Servicing Glow Plugs 4 4 4 4 Servicing the Alternator 4 4 4 4 1 Preliminary Checks and Tests 4 4 4 4 2 Test Tools 4 4 4 4 3 Problem Area Determination 4 4 4 4 4 In Unit Alternator Regulat...

Page 5: ...2 4 2 Speed Adjustment 4 3 4 3 Mechanical Fuel Pump 4 3 4 4 Air Cleaner 4 3 4 5 Engine Crankcase Breather 4 4 4 6 Open Diode Trio Test 4 4 4 7 Open Regulator Test 4 5 4 8 Alternator Output Test 4 5 4...

Page 6: ...TY DEVICES System components are protected from damage caused by unsafe operating conditions by automatically shutting down the diesel engine when such conditions occur This is accomplished by the saf...

Page 7: ...A C Generator 20 Electrical Receptacle Figure 1 1 Generator Set Front View Typical 1 Circuit Breaker CB 1 2 Oil Pressure Gauge 3 Water Temperature Gauge 4 Ammeter 5 Terminal Board 6 Circuit Breaker CB...

Page 8: ...engine piston goes through the intake stroke the piston draws clean fresh air down into the cylinder for the compression and power strokes As the engine goes through its exhaust stroke the upward mov...

Page 9: ...aker Trip Light This light red may be checked unit not running by placing the circuit breaker CB in the off position and at the same time moving the ignition switch to the run position When the circui...

Page 10: ...the brushes and rotor slip rings Two completely sealed ball bearings support the rotor in the front and rear housing 1 2 3 4 5 6 7 1 AC Tap 2 Back Cover 3 Positive Output B 4 Integral Regulator 5 Exci...

Page 11: ...windings and the generator stator windings are internally con nected within the stator housing Only the output power leads of the generator unit are brought out to the generator terminal box 1 10 2 A...

Page 12: ...frigeration unit power plug in genset power receptacle 6 Install battery charger plug in receptacle at the base of the generator control box 69GN15 114 only b Removal Reverse steps in paragraph a 2 2...

Page 13: ...tch will automatically be in the OFF position when released 4 Complete pre trip inspection Refer to paragraph 2 2 b b Stopping Instructions 1 Push ignition switch to the OFF position 2 4 CONTROL CIRCU...

Page 14: ...ers Replace Faulty fuel control operation 4 3 3 Run control relay 4 3 3 Glow plug s defective 4 3 8 Plugged fuel lines to injector s Engine Manual Mechanical fuel pump malfunction 4 3 5 c Starter cran...

Page 15: ...n does not Defective starter Engine Manual disengage after engine is running 3 1 4Malfunction In the Engine Starting Circuit a No power to Battery defective Correct starter motor Loose electrical conn...

Page 16: ...ater pump Engine Manual d Excessive crankcase pressure Plugged crankcase breather line 4 3 7 3 2 ALTERNATOR AUTOMOTIVE TYPE Battery Undercharged Defective cables dirty battery posts or corroded termin...

Page 17: ...tuating voltage Fluctuating speed 4 3 4 or May be indicated by Irregular speed of engine Engine Manual flickering lights Loose terminal or load connections Tighten Defective bearing causing uneven air...

Page 18: ...2 b X 4 Check total time meter Run 10 min 4 1 3Every 1000 Hour Maintenance Normal Operating Conditions X X 1 Complete 400 Hour Maintenance 4 1 2 X 2 Tighten engine and generator mounting bolts 4 7 X 3...

Page 19: ...eeze meeting GM specifications GM 6038M or equal c Close drain cock and fill system with clean untreated water to which three to five percent of an akalined based radiator cleaner should be added six...

Page 20: ...counter clockwise to loosen and re move item 1 2 Remove banjo fitting item 2 and let it hang loose making sure to keep copper rings item 4 for re placement 3 Turn filter item 3 counter clockwise and...

Page 21: ...r charging or damage to the charging system 2 Badly corroded battery cables could prevent the battery from reaching a fully charged condition c Check battery condition and charge if necessary A low or...

Page 22: ...gure 4 7 Open Regulator Test Test No 3 Alternator Output Test CONDITIONS Engine running after voltmeter is connected as shown in Figure 4 8 VOLTS AC TAP TACH POS OUTPUT B BATTERY GROUND INTEGRAL REGUL...

Page 23: ...3 Check belt tension correct specifications are 40 45 lbs on the Burroughs gauge Carrier Transicold Part No 07 00203 4 6 SERVICING THE GENERATOR MAIN ALTERNATOR 4 6 1Preventive Maintenance and Operat...

Page 24: ...mically balanced to a high degree on precision machines to assure minimum vibration They will therefore remain dynamically stable at speed well beyond the synchronous speed of the generator The rotors...

Page 25: ...or output voltage does not build up 4 6 2Installation and Removal a Removing the Generator 1 Remove ground wire from frame of generator set 2 Remove generator leads from power junction box then remove...

Page 26: ...r 1 Battery w box must be removed along with discon necting the ground strap and moving the control box aside for clear access to the generator s shockmounts 2 Follow the procedure for removing engine...

Page 27: ...crews 3 8 securing tank to bottom frame members 5 Remove two capscrews 1 4 item 10 securing bottom flange of control box to frame front view 6 Remove two capscrews 1 4 securing control box item 4 and...

Page 28: ...it breaker CB1 and the start stop switch are in the OFF position Also disconnect power plug and cable Make sure the power plug s are clean and dry before connecting to any power receptacle WARNING Hig...

Page 29: ...GP GLOW PLUG SWITCH 9 HWT WATER TEMP SWITCH 10 IGN IGNITION SWITCH 10 LOP LOW OIL PRESSURE 12 OPG OIL PRESSURE GAUGE 12 OPS OIL PRESSURE SENDER 9 11 RCR RUN CONTROL RELAY 5 SM STARTER MOTOR 5 17 SS S...

Page 30: ...5 3 1 thru 10 are wires from A C generator Figure 5 1 Electrical Wiring Schematic Diagram Models 69GN15 114 Drawing Number 69GN15 1064 Revision D Sheet 2 of 2...

Page 31: ...ITION SWITCH 10 LOP LOW OIL PRESSURE 12 OPG OIL PRESSURE GAUGE 12 OPS OIL PRESSURE SENDER 9 11 RCR RUN CONTROL RELAY 5 SM STARTER MOTOR 5 17 SS STARTER SOLENOID 14 TT TOTAL TIME METER 1 V VOLTMETER 6...

Page 32: ...5 5 5 6 1 thru 10 are wires from A C generator Figure 5 2 Electrical Wiring Schematic Diagram Models 69GN15 124 Drawing Number 69GN15 1104 Revision B Sheet 2 of 2...

Reviews: