![Carrier 50JZ024 Installation, Start-Up And Service Instructions Manual Download Page 4](http://html1.mh-extra.com/html/carrier/50jz024/50jz024_installation-start-up-and-service-instructions-manual_2561594004.webp)
UNIT
ELECTRICAL CHARACTERISTICS
UNIT WEIGHT
UNIT HEIGHT
IN. [MM]
"A"
CENTER OF GRAVITY
IN. [MM]
lb
kg
X
Y
Z
50JZ042
208/230-1-60, 208/230-3-60, 460-3-60
350
158.8
40.98 [1040.9]
21.0 [533.4]
20.5 [520.7]
16.6 [421.6]
50JZ048
208/230-1-60, 208/230-3-60, 460-3-60
355
161.0
40.98 [1040.9]
20.0 [508.0]
21.3 [539.8]
18.0 [457.2]
50JZ060
208/230-1-60, 208/230-3-60, 460-3-60
428
194.1
42.98 [1091.7]
21.0 [533.4]
20.0 [508.0]
17.6 [447.0]
Fig. 3—50JZ 042-060 Unit Dimensions
C00065
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
in. [mm]
EVAP. COIL ACCESS SIDE..............................................................36.00 [914.0]
POWER ENTRY SIDE......................................................................36.00 [914.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP .......................................................................................48.00 [1219.0]
SIDE OPPOSITE DUCTS ................................................................36.00 [914.0]
DUCT PANEL ...................................................................................12.00 [304.8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
in. [mm]
TOP OF UNIT ...................................................................................14.00 [355.6]
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]
BOTTOM OF UNIT .............................................................................0.50 [12.7]
ELECTRIC HEAT PANEL .................................................................36.00 [914.4]
NEC. REQUIRED CLEARANCES.
in. [mm]
BETWEEN UNITS, POWER ENTRY SIDE ....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE ...36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
4 4 . 5 [ 1 . 7 5 ]
4
Summary of Contents for 50JZ024
Page 9: ...Fig 12 Wiring Schematics 208 230 1 60 C00097 9...
Page 10: ...Fig 13 Wiring Schematics 208 230 3 60 C00098 10...
Page 11: ...Fig 14 Wiring Schematics 460 3 60 C00099 11...
Page 26: ...26...
Page 27: ...27...