REFRIGERANT CIRCUIT — Inspect all refrigerant tubing con-
nections and the unit base for oil accumulation annually. Detecting
oil generally indicates a refrigerant leak.

If oil is detected or if low performance is suspected, leak-test all
refrigerant tubing using an electronic leak detector, or liquid-soap
solution. If a refrigerant leak is detected, refer to Check for
Refrigerant Leaks section.

If no refrigerant leaks are found and low performance is suspected,
refer to Checking and Adjusting Refrigerant Charge section.

INDOOR AIRFLOW — The heating and/or cooling airflow does
not require checking unless improper performance is suspected. If
a problem exists, be sure that all supply- and return-air grilles are
open and free from obstructions, and that the air filter is clean.
When necessary, refer to Indoor Airflow and Airflow Adjustments
section to check the system airflow.

METERING DEVICES—ACCURATER® PISTON — This me-
tering device is a fixed orifice and is contained in the brass
hex-body in the liquid line feeding the indoor and outdoor coils.

PRESSURE SWITCHES — Pressure switches are protective de-
vices wired into control circuit (low voltage). They shut off
compressor if abnormally high or low pressures are present in the
refrigeration circuit. These pressure switches are specifically
designed to operate with Puron (R-410A) systems. R-22 pressure
switches must not be used as replacements for the Puron (R-
410A) system.

LOSS OF CHARGE/LOW-PRESSURE SWITCH (AIR CONDI-
TIONER ONLY) — This switch is located on the liquid line and
protects against low suction pressures caused by such events as
loss of charge, low airflow across indoor coil, dirty filters, etc. It
opens on a pressure drop at about 20 psig. If system pressure is
above this, switch should be closed.

To check switch:

1. Turn off all power to unit.

2. Disconnect leads on switch.

3. Apply ohmeter leads across switch. You should have conti-

nuity on a good switch.

NOTE:

Because these switches are attached to refrigeration

system under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem
exists. If switch must be removed, remove and recover all system

charge so that pressure gauges read 0 psi. Never open system
without breaking vacuum with dry nitrogen.

HIGH-PRESSURE SWITCH — The high-pressure switch is lo-
cated in the discharge line and protects against excessive con-
denser coil pressure. It opens at 610 psig.

High pressure may be caused by a dirty outdoor coil, failed fan
motor, or outdoor air recirculation.

To check switch:

1. Turn off all power to unit.

2. Disconnect leads on switch.

3. Apply ohmeter leads across switch. You should have conti-

nuity on a good switch.

COPELAND SCROLL COMPRESSOR (PURON REFRIGER-
ANT) — The compressor used in this product is specifically
designed to operate with Puron (R-410A) refrigerant and
cannot be interchanged.

The compressor is an electrical (as well as mechanical) device.
Exercise extreme caution when working near compressors. Power
should be shut off, if possible, for most troubleshooting tech-
niques. Refrigerants present additional safety hazards.

Wear safety glasses and gloves when handling refrigerants.
Keep torches and other ignition sources away from refriger-
ants and oils. Failure to follow this warning can cause a fire,
serious injury, or death.

The scroll compressor pumps refrigerant throughout the system by
the interaction of a stationary and an orbiting scroll. The scroll
compressor has no dynamic suction or discharge valves, and it is
more tolerant of stresses caused by debris, liquid slugging, and
flooded starts. The compressor is equipped with an anti-rotational
device and an internal pressure relief port. The anti-rotational
device prevents the scroll from turning backwards and replaces the
need for a cycle protector. The pressure relief port is a safety
device, designed to protect against extreme high pressure. the
relief port has an operating range between 550 and 625 psi
differential pressure.

The Copeland scroll compressor uses Mobil 3MA POE oil.
This is the only oil allowed for oil recharge.

REFRIGERANT SYSTEM

REFRIGERANT

This system uses Puron® (R-410A) refrigerant which has
higher operating pressures than R-22 and other refrigerants.
No other refrigerant may be used in this system. Gauge set,
hoses, and recovery system must be designed to handle
Puron. If you are unsure consult the equipment manufacturer.
Failure to use Puron compatible servicing equipment or
replacement components may result in property damage or
injury.

COMPRESSOR OIL — The compressor in this system uses a
polyolester (POE) oil, Mobil 3MA POE. This oil is extremely
hygroscopic, meaning it absorbs water readily. POE oils can
absorb 15 times as much water as other oils designed for HCFC
and CFC refrigerants. Take all necessary precautions to avoid
exposure of the oil to the atmosphere.

SERVICING SYSTEMS ON ROOFS WITH SYNTHETIC MA-
TERIALS — POE (polyolester) compressor lubricants are known
to cause long term damage to some synthetic roofing materials.

Fig. 30—Refrigerant Circuit

C99097

21

Summary of Contents for 50JZ024

Page 1: ...cautions in the literature tags and labels attached to the unit and other safety precautions that may apply Follow all safety codes Wear safety glasses and work gloves Use quenching cloth for unbrazin...

Page 2: ...house overhang is 48 in above the unit top The maximum horizontal extension of a partial over hang must not exceed 48 in IMPORTANT Do not restrict outdoor airflow An air restriction at either the out...

Page 3: ...ENTS 36 914 UNIT TOP 48 1219 SIDE OPPOSITE DUCTS 36 914 DUCT PANEL 12 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LESS THAN 12 IN 304 8 MM FROM WALL SYSTEM THEN THE SYSTEM PERFORMANCE MAY BE COMPROMISED...

Page 4: ...IL ACCESS SIDE 36 00 914 0 POWER ENTRY SIDE 36 00 914 0 EXCEPT FOR NEC REQUIREMENTS UNIT TOP 48 00 1219 0 SIDE OPPOSITE DUCTS 36 00 914 0 DUCT PANEL 12 00 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LES...

Page 5: ...S 1 Roof curb must be setup for unit being installed 2 Seal strip gasket must be applied as required 3 Dimensions are in inches 4 Attach ductwork to flanges of the curb 5 R A Return Air S A Supply Air...

Page 6: ...t duct connector or sheet metal sleeve must extend 24 in from electric heater element 1 Size ductwork for cooling air quantity cfm The minimum air quantity for proper electric heater operation is list...

Page 7: ...2 0 040 2 0 038 2 0 046 2 0 052 OUTDOOR COIL Rows Fins in Face Area sq ft 2 17 8 5 2 17 10 3 2 17 10 3 2 17 13 5 2 17 13 5 2 17 15 4 OUTDOOR FAN Nominal Airflow CFM Diameter Motor HP RPM 2350 22 1 8 8...

Page 8: ...orrection of improper voltage and or phase imbalance 4 Insulate low voltage wires for highest voltage contained within conduit when low voltage control wires are in same conduit as high voltage wires...

Page 9: ...Fig 12 Wiring Schematics 208 230 1 60 C00097 9...

Page 10: ...Fig 13 Wiring Schematics 208 230 3 60 C00098 10...

Page 11: ...Fig 14 Wiring Schematics 460 3 60 C00099 11...

Page 12: ...50 3 57 2 72 8 83 3 95 4 109 3 40 40 40 40 60 60 80 90 100 110 208 230 3 60 187 253 15 4 88 0 0 9 4 1 3 8 5 0 7 5 10 0 11 3 15 0 15 0 20 0 10 4 12 0 20 8 24 1 31 3 36 1 41 6 48 0 24 3 24 3 24 3 24 3 3...

Page 13: ...percent of voltage imbalance Voltage imbalance max voltage deviation from average voltage 100 x average voltage EXAMPLE Supply voltage is 460 3 60 AB 452 v BC 464 v AC 455 v 452 464 455 Average Voltag...

Page 14: ...leak is detected see following Check for Refrigerant Leaks section c Inspect all field and factory wiring connections Be sure that connections are completed and tight d Inspect coil fins If damaged d...

Page 15: ...h Accurater Metering Device Arrow indicates direction of flow Metering Position Bypass Position HPS Fig 21 Typical Heat Pump Operation Heating Mode 1 Hot gas from compressor flows through the 4 way va...

Page 16: ...and temperature sensing devices are required Connect the pressure gauge to the service port on the suction line Mount the tempera ture sensing device on the suction line and insulate it so that the ou...

Page 17: ...411 394 381 Cfm 1374 1290 1205 1116 1020 916 Med Watts 523 506 490 471 449 426 Cfm 1500 1408 1301 1190 1082 977 High Watts 645 628 610 595 584 575 Cfm 1474 1369 1267 1169 1069 962 42 Low Watts 660 639...

Page 18: ...TEMP F C 125 52 115 46 105 41 95 35 85 29 75 24 65 18 55 13 45 7 50JZ500066 Fig 24 Cooling Charging Chart 50JZ 030 Units C00083 030 60 Hz COOLING CHARGING CHART For Use with Units Using R410a Refrige...

Page 19: ...oling Charging Chart 50JZ 060 Units C00087 060 60 Hz COOLING CHARGING CHART For use with units using R410a Refrigerant 80 90 100 110 120 130 140 150 160 170 180 20 30 40 50 60 70 80 SUCTION LINETEMPER...

Page 20: ...COIL INDOOR COIL AND CONDENSATE DRAIN PAN Inspect the outdoor coil indoor coil and conden sate drain pan at least once each year The coils are easily cleaned when dry therefore inspect and clean the...

Page 21: ...at 610 psig High pressure may be caused by a dirty outdoor coil failed fan motor or outdoor air recirculation To check switch 1 Turn off all power to unit 2 Disconnect leads on switch 3 Apply ohmeter...

Page 22: ...or 60 sec on 030 060 sizes or 30 sec on 024 size after thermostat is satisfied This delay enables blower to remove residual cooling in coil after compression shutdown thereby improving efficiency of s...

Page 23: ...es with 750 psig service pressure rating Leak detectors should be designed to detect HFC refrigerant Puron as with other HFCs is only compatible with POE oils Vacuum pumps will not remove moisture fro...

Page 24: ...ities shown on nameplate Defective compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start cap...

Page 25: ...IST REMOVE AND STORE IN JOB FILE I PRELIMINARY INFORMATION Model No Serial No Date Technician II PRE START UP ___ Verify that all packing materials have been removed from unit ___ Remove all shipping...

Page 26: ...26...