background image

1. Place room thermostat SYSTEM switch or MODE control in

OFF position. Observe that blower motor starts when FAN
mode is placed in FAN ON position and shuts down within 60
sec (030-060 size) or 30 sec (024 size) when FAN MODE
switch is placed in AUTO position.

2. Place SYSTEM switch or MODE control in COOL position

and FAN mode in AUTO position. Set control below room
temperature. Observe that cooling cycle shuts down when
control setting is satisfied.

3. Place SYSTEM switch or MODE control in HEAT position.

Set control above room temperature. Observe that compressor,
outdoor fan, and indoor blower motors start. Observe that
heating cycle shuts down when control setting is satisfied.

4. When using an automatic changeover room thermostat, place

both SYSTEM or MODE control and FAN mode switches in
AUTO positions. Observe that unit operates in Cooling mode
when temperature control is set to ‘‘call for Cooling’’ (below
room temperature), and unit operates in Heating mode when
temperature control is set to "call for Heating" (above room
temperature).

IMPORTANT:

Three-phase, scroll compressors are direction ori-

ented. Unit must be checked to ensure proper compressor 3-phase
power lead orientation. If not corrected within 5 minutes, the
internal protector may shut off the compressor. The 3-phase power
leads to the unit must be reversed to correct rotation. When turning
backwards, the difference between compressor suction and dis-
charge pressures may be dramatically lower than normal.

CHECKING AND ADJUSTING REFRIGERANT CHARGE

— The refrigerant system is fully charged with R-410A refriger-

ant and is tested and factory sealed.

NOTE:

Adjustment of the refrigerant charge is not required

unless the unit is suspected of not having the proper R-410A
charge. The charging label and the tables shown refer to system
temperatures and pressures in cooling mode only. A refrigerant
charging label is attached to the outside of the service access door.
If charge level is suspect in Heating mode, reclaim all refrigerant
and charge to nameplate amount. (This information may be
obtained from the physical data table also.)

IMPORTANT:

When evaluating the refrigerant charge, an indi-

cated adjustment to the specified factory charge must always be
very minimal. If a substantial adjustment is indicated, an abnormal
condition exists somewhere in the cooling system, such as insuf-
ficient airflow across either coil or both coils.

REFRIGERANT CHARGE — The amount of refrigerant charge
is listed on the unit nameplate and /or the physical data table. Refer
to Carrier Refrigeration Service Techniques Manual, Refrigerants
Section.

NO CHARGE — Check for leak. Use standard evacuating tech-
niques. After evacuating system, weigh in the specified amount of
refrigerant (refer to system data plate).

LOW CHARGE COOLING — Use Cooling Charging Charts
(Fig. 23-28). Vary refrigerant until the conditions of the chart are
met. Note that charging charts are different from type normally
used. Charts are based on charging the units to correct superheat
for the various operating conditions. Accurate pressure gauge and
temperature sensing devices are required. Connect the pressure
gauge to the service port on the suction line. Mount the tempera-
ture sensing device on the suction line and insulate it so that the
outdoor ambient does not effect the reading. Indoor air CFM must
be within the normal operating range of the unit.

TO USE COOLING CHARGING CHARTS — Take the outdoor
ambient temperature and read the suction pressure gauge. Refer to
the chart to determine what the suction temperature should be.

NOTE: If the problem causing the inaccurate readings is a
refrigerant leak, refer to Check for Refrigerant Leaks section.

INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS

For heating and cooling operation, the recommended airflow
is 350 to 450 cfm for each 12,000 Btuh of rated cooling
capacity. for units with optional electric heat, the airflow must
not be reduced below the levels stated in Table 2.

Table 4 shows both heating and cooling airflows at various
external static pressures. Refer to these tables to determine the
airflow for the system being installed.

NOTE:

Be sure that all supply-and return-air grilles are open, free

from obstructions, and adjusted properly.

Airflow can be changed by changing the lead connection of the
blower motor.

Unit 50JZ three-speed motors (except size 030 and 048) are
factory wired for low speed operation. Unit 50JZ 030 and 048 are
factory wired for medium speed.

For 208/230v Motors:—The motor leads are color-coded as
follows:
3-SPEED
Black = high speed
Blue = medium speed
Red = low speed

To change the speed of the blower motor (BM), remove the fan
motor speed leg lead from the blower relay (BR). This wire is
attached to IGC terminal BM for single-phase and 3-phase units.
To change the speed, remove and replace with lead for desired
blower motor speed. Insulate the removed lead to avoid contact
with chassis parts.

For 460v GE Motors—The motor leads are color coded as follows:
3-SPEED
Black = high
Violet = jumper
Orange = medium
Red = low

To change the speed of the blower motor (BM), remove fan motor
speed lead from the blower relay (BR) and replace with the lead
for the desired blower motor speed. The motor speed lead is
attached to terminal BM. For low and medium speeds black must
be connected to the jumper wire. Insulate removed lead end to
avoid contact with chassis parts. To select high speed on 460v GE
motors, separate the black female quick connect (QC) from the
jumper lead male quick connect (QC) and connect the black lead
to the BR. Insulate the jumper to avoid contact with any chassis
parts.

Step 3—Defrost Control

QUIET SHIFT — Quiet Shift is a field-selectable defrost mode,
which will eliminate occasional noise that could be heard at the
start of defrost cycle and restarting of heating cycle. It is selected
by placing DIP switch 3 (on defrost board) in ON position.

When Quiet Shift switch is placed in ON position, and a defrost is
initiated, the following sequence of operation will occur. Revers-
ing valve will energize, outdoor fan will turn off, compressor will
turn off for 30 sec and then turn back on to complete defrost. At
the start of heating after conclusion of defrost reversing valve will
de-energize, compressor will turn off for another 30 sec, and the
outdoor fan will stay off for 40 sec, before starting in the heating
mode.

16

Summary of Contents for 50JZ024

Page 1: ...cautions in the literature tags and labels attached to the unit and other safety precautions that may apply Follow all safety codes Wear safety glasses and work gloves Use quenching cloth for unbrazin...

Page 2: ...house overhang is 48 in above the unit top The maximum horizontal extension of a partial over hang must not exceed 48 in IMPORTANT Do not restrict outdoor airflow An air restriction at either the out...

Page 3: ...ENTS 36 914 UNIT TOP 48 1219 SIDE OPPOSITE DUCTS 36 914 DUCT PANEL 12 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LESS THAN 12 IN 304 8 MM FROM WALL SYSTEM THEN THE SYSTEM PERFORMANCE MAY BE COMPROMISED...

Page 4: ...IL ACCESS SIDE 36 00 914 0 POWER ENTRY SIDE 36 00 914 0 EXCEPT FOR NEC REQUIREMENTS UNIT TOP 48 00 1219 0 SIDE OPPOSITE DUCTS 36 00 914 0 DUCT PANEL 12 00 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LES...

Page 5: ...S 1 Roof curb must be setup for unit being installed 2 Seal strip gasket must be applied as required 3 Dimensions are in inches 4 Attach ductwork to flanges of the curb 5 R A Return Air S A Supply Air...

Page 6: ...t duct connector or sheet metal sleeve must extend 24 in from electric heater element 1 Size ductwork for cooling air quantity cfm The minimum air quantity for proper electric heater operation is list...

Page 7: ...2 0 040 2 0 038 2 0 046 2 0 052 OUTDOOR COIL Rows Fins in Face Area sq ft 2 17 8 5 2 17 10 3 2 17 10 3 2 17 13 5 2 17 13 5 2 17 15 4 OUTDOOR FAN Nominal Airflow CFM Diameter Motor HP RPM 2350 22 1 8 8...

Page 8: ...orrection of improper voltage and or phase imbalance 4 Insulate low voltage wires for highest voltage contained within conduit when low voltage control wires are in same conduit as high voltage wires...

Page 9: ...Fig 12 Wiring Schematics 208 230 1 60 C00097 9...

Page 10: ...Fig 13 Wiring Schematics 208 230 3 60 C00098 10...

Page 11: ...Fig 14 Wiring Schematics 460 3 60 C00099 11...

Page 12: ...50 3 57 2 72 8 83 3 95 4 109 3 40 40 40 40 60 60 80 90 100 110 208 230 3 60 187 253 15 4 88 0 0 9 4 1 3 8 5 0 7 5 10 0 11 3 15 0 15 0 20 0 10 4 12 0 20 8 24 1 31 3 36 1 41 6 48 0 24 3 24 3 24 3 24 3 3...

Page 13: ...percent of voltage imbalance Voltage imbalance max voltage deviation from average voltage 100 x average voltage EXAMPLE Supply voltage is 460 3 60 AB 452 v BC 464 v AC 455 v 452 464 455 Average Voltag...

Page 14: ...leak is detected see following Check for Refrigerant Leaks section c Inspect all field and factory wiring connections Be sure that connections are completed and tight d Inspect coil fins If damaged d...

Page 15: ...h Accurater Metering Device Arrow indicates direction of flow Metering Position Bypass Position HPS Fig 21 Typical Heat Pump Operation Heating Mode 1 Hot gas from compressor flows through the 4 way va...

Page 16: ...and temperature sensing devices are required Connect the pressure gauge to the service port on the suction line Mount the tempera ture sensing device on the suction line and insulate it so that the ou...

Page 17: ...411 394 381 Cfm 1374 1290 1205 1116 1020 916 Med Watts 523 506 490 471 449 426 Cfm 1500 1408 1301 1190 1082 977 High Watts 645 628 610 595 584 575 Cfm 1474 1369 1267 1169 1069 962 42 Low Watts 660 639...

Page 18: ...TEMP F C 125 52 115 46 105 41 95 35 85 29 75 24 65 18 55 13 45 7 50JZ500066 Fig 24 Cooling Charging Chart 50JZ 030 Units C00083 030 60 Hz COOLING CHARGING CHART For Use with Units Using R410a Refrige...

Page 19: ...oling Charging Chart 50JZ 060 Units C00087 060 60 Hz COOLING CHARGING CHART For use with units using R410a Refrigerant 80 90 100 110 120 130 140 150 160 170 180 20 30 40 50 60 70 80 SUCTION LINETEMPER...

Page 20: ...COIL INDOOR COIL AND CONDENSATE DRAIN PAN Inspect the outdoor coil indoor coil and conden sate drain pan at least once each year The coils are easily cleaned when dry therefore inspect and clean the...

Page 21: ...at 610 psig High pressure may be caused by a dirty outdoor coil failed fan motor or outdoor air recirculation To check switch 1 Turn off all power to unit 2 Disconnect leads on switch 3 Apply ohmeter...

Page 22: ...or 60 sec on 030 060 sizes or 30 sec on 024 size after thermostat is satisfied This delay enables blower to remove residual cooling in coil after compression shutdown thereby improving efficiency of s...

Page 23: ...es with 750 psig service pressure rating Leak detectors should be designed to detect HFC refrigerant Puron as with other HFCs is only compatible with POE oils Vacuum pumps will not remove moisture fro...

Page 24: ...ities shown on nameplate Defective compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start cap...

Page 25: ...IST REMOVE AND STORE IN JOB FILE I PRELIMINARY INFORMATION Model No Serial No Date Technician II PRE START UP ___ Verify that all packing materials have been removed from unit ___ Remove all shipping...

Page 26: ...26...

Page 27: ...27...

Page 28: ...46231 50jz 1si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 101 Catalog No 565...

Reviews: