![Carrier 50JZ024 Installation, Start-Up And Service Instructions Manual Download Page 24](http://html1.mh-extra.com/html/carrier/50jz024/50jz024_installation-start-up-and-service-instructions-manual_2561594024.webp)
Troubleshooting Chart
SYMPTOM
CAUSE
REMEDY
Compressor and outdoor fan will not start
Power failure
Call power company
Fuse blown or circuit breaker tripped
Replace fuse or reset circuit breaker
Defective thermostat, contactor, transformer, con-
trol relay, defrost board, or high pressure or loss-
of-charge/low pressure switch
Replace component
Insufficient line voltage
Determine cause and correct
Incorrect or faulty wiring
Check wiring diagram and rewire correctly
Thermostat setting too high
Lower thermostat setting below room tempera-
ture
Units have a 5-minute time delay
DO NOT bypass this compressor time
delay—wait for 5 minutes until time-delay relay is
deenergized
Compressor will not start but condenser fan
runs
Faulty wiring or loose connections in compressor
circuit
Check wiring and repair or replace
Compressor motor burned out, seized, or internal
overload open
Determine cause
Replace compressor
Defective run capacitor, overload, or PTC (posi-
tive temperature coefficient) thermistor
Determine cause and replace
One leg of 3-phase power dead
Replace fuse or reset circuit breaker Determine
cause
Low input voltage (20% low)
Determine cause and correct
Three-phase scroll compressor (size 030-
060units) may be a low pressure differential
Scroll compressor is rotating in the wrong direc-
tion
Correct the direction of rotation by reversing the
3-phase power leads to the unit
Compressor cycles (other than normally sat-
isfying thermostat)
Refrigerant overcharge or undercharge
Recover refrigerant, evacuate system, and re-
charge to capacities shown on nameplate
Defective compressor
Replace and determine cause
Insufficient line voltage
Determine cause and correct
Blocked outdoor coil
Determine cause and correct
Defective run/start capacitor, overload or start
relay
Determine cause and replace
Defective thermostat
Replace thermostat
Faulty outdoor-fan motor or capacitor
Replace
Damaged reversing valve
Determine cause and correct
Restriction in refrigerant system
Locate restriction and remove
Compressor operates continuously
Dirty air filter
Replace filter
Unit undersized for load
Decrease load or increase unit size
Thermostat set too low
Reset thermostat
Low refrigerant charge
Locate leak, repair, and recharge
Frosted coil with incorrect defrost operation
Check defrost time settings
Reset as necessary
Check defrost temperature switch
Replace as necessary
Air in system
Recover refrigerant, evacuate system, and re-
charge
Outdoor coil dirty or restricted
Clean coil or remove restriction
Excessive head pressure
Dirty air filter
Replace filter
Dirty indoor or outdoor coil
Clean coil
Refrigerant overcharged
Recover excess refrigerant
Air in system
Recover refrigerant, evacuate system, and re-
charge
(Heat) Indoor air restricted or recirculating
Determine cause and correct
Indoor or outdoor air restricted or air short-cycling
Determine cause and correct
Head pressure too low
Low refrigerant charge
Check for leaks, repair and recharge
Restriction in liquid tube
Remove restriction
Excessive suction pressure
(Heat) Outdoor coil frosted
Move timer on control board to 30 minutes be-
tween defrost cycles
(Cool) High Heat load
Check for source and eliminate
Reversing valve hung up or leaking internally
Replace valve
Refrigerant overcharged
Recover excess refrigerant
24
Summary of Contents for 50JZ024
Page 9: ...Fig 12 Wiring Schematics 208 230 1 60 C00097 9...
Page 10: ...Fig 13 Wiring Schematics 208 230 3 60 C00098 10...
Page 11: ...Fig 14 Wiring Schematics 460 3 60 C00099 11...
Page 26: ...26...
Page 27: ...27...